OPTISPEED™ LIQUID COOLED
VARIABLE SPEED DRIVE
SERVICE MANUAL
Supersedes: 160.00-M4 (1007)
Form 160.00-M4 (113)
MODELS VSD
VSD270, VSD292, VSD351, VSD385, VSD419, VSD424, VSD503, VSD608
00633VIP
270 HP – 60 HZ, 380 VAC (P/N 371-02767-XXX)
292 HP – 50 HZ, 400 VAC (P/N 371-03700-XXX)
292 HP – 50 HZ, 415 VAC (P/N 371-03700-XXX)
351 HP – 60 HZ, 460 VAC (P/N 371-02767-XXX)
385 HP – 50 HZ, 380 VAC (P/N 371-03789-XXX)
419 HP – 50 HZ, 400 VAC (P/N 371-03789-XXX)
419 HP – 50 HZ, 415 VAC (P/N 371-03789-XXX)
424 HP – 60 HZ, 575 VAC (P/N 371-04881-XXX)
503 HP – 60 HZ, 460 VAC (P/N 371-03789-XXX)
608 HP – 60 HZ, 575 VAC (P/N 371-04563-XXX)
Issue Date:
January 21, 2013
FORM 160.00-M4
ISSUE DATE: 1/21/2013
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus.
During installation, operation maintenance or service,
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants,
materials under pressure, rotating components, and
both high and low voltage. Each of these items has the
potential, if misused or handled improperly, to cause
bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and
recognize these inherent hazards, protect themselves,
and proceed safely in completing their tasks. Failure
to comply with any of these requirements could result
in serious damage to the equipment and the property in
which it is situated, as well as severe personal injury or
death to themselves and people at the site.
This document is intended for use by owner-authorized
operating/service personnel. It is expected that these
individuals possess independent training that will enable them to perform their assigned tasks properly and
safely. It is essential that, prior to performing any task
on this equipment, this individual shall have read and
understood this document and any referenced materials. This individual shall also be familiar with and
comply with all applicable governmental standards and
regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
Indicates a possible hazardous situation
which will result in death or serious injury
if proper care is not taken.
Identiies a hazard which could lead to
damage to the machine, damage to other
equipment and/or environmental pollution if proper care is not taken or instructions and are not followed.
Indicates a potentially hazardous situation which will result in possible injuries
or damage to equipment if proper care is
not taken.
Highlights additional information useful
to the technician in completing the work
being performed properly.
External wiring, unless speciied as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with Johnson Controls’ published speciications and must be performed only by a qualiied
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls’ policy for continuous product improvement, the information contained in this document is subject to change without
notice. Johnson Controls makes no commitment to
update or provide current information automatically to
the manual owner. Updated manuals, if applicable, can
be obtained by contacting the nearest Johnson Controls
Service office.
Operating/service personnel maintain responsibility for
the applicability of these documents to the equipment.
If there is any question regarding the applicability of
these documents, the technician should verify whether
the equipment has been modified and if current literature is available from the owner of the equipment prior
to performing any work on the chiller.
CHANGE BARS
Revisions made to this document are indicated with a
line along the left or right hand column in the area the
revision was made. These revisions are to technical information and any other changes in spelling, grammar
or formatting are not included.
ASSOCIATED LITERATURE
MANUAL DESCRIPTION
FORM NUMBER
Operation Manual (Unit) Model YT, (Centrifugal)
160.55-O1
Operation Manual (Unit) Model YK, (Centrifugal)
160.54-O1
Operation Manual (Control Panel) Model YT, (Centrifugal)
160.55-O1
Operation Manual (Control Panel) Model YK, (Centrifugal)
160.54-O1
Service Manual (Control Panel) Model YT, (Centrifugal)
160.55-M1
Service Manual (Control Panel) Model YK, (Centrifugal)
160.54-M1
Wiring Diagram (Control Panel) Model YT, (Centrifugal)
160.55-PW2
Wiring Diagram (Control Panel) Model YT, (Centrifugal) Model YK, (Centrifugal)
160.54-PW8
Wiring Field Connections (Variable Speed Drive) Model YT, (Centrifugal)
160.55-PW5
Wiring Field Connections (Variable Speed Drive) Model YK, (Centrifugal)
160.54-PW5
Operation Manual (Control Panel) Model VSD (Compressor Speed Drive)
160.00-O4
Renewal Parts (Variable Speed Drive)
160.00-RP4
The Control/VSD Cabinet contains lethal High AC and DC voltages. Before performing service inside
the cabinet, remove the AC supply feeding the chiller and verify using a non-contact voltage sensor.
The DC Voltage on the VSD DC Bus will take 5 minutes to bleed off, after AC power is removed.
Always check the DC Bus Voltage with a Voltmeter to assure the capacitor charge has bled off before
working on the system.
• NEVER short out the DC Bus to discharge the ilter capacitors.
• NEVER place loose tools, debris, or any objects inside the Control Panel/VSD Cabinet.
• NEVER allow the Control Panel VSD Cabinet doors to remain open if there is a potential for
rain to enter the panel. Keep doors closed and assure all latches are engaged on each door unless the unit is being serviced.
• ALWAYS lockout the disconnect supplying AC to the chiller.
• The 1L Line Inductor will reach operating temperatures of over 300° F. DO NOT open panel doors
during operation. Assure the inductor is cool whenever working near the inductor with power off.
JOHNSON CONTROLS
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
NOMENCLATURE
VSD 351 R K F T - 46
DRIVE TYPE
Variable Speed
HORSEPOWER RATING
270, 292, 351, 385, 419,
424, 503, 608
VOLTAGE RATING
40 = 400VAC, 60Hz
46 = 460VAC, 60Hz
50 = 400VAC, 50Hz
58 = 575VAC, 60Hz
68 = 415VAC, 50Hz
OPTIONAL 519 FILTER INSTALLED (FT) or NO FILTER (__)
RETROFIT PACKAGE (R), FACTORY PACKAGE (__)
4
CHILLER TYPE: YK (K), YT (T)
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
TABLE 1 - MODEL NUMBER AND PART NUMBERS
419 HP 50 HZ 415 VAC
270 HP 50 HZ 400 VAC
VSD270_T__-40
371-02767-X21
VSD419_T__-68
371-03789-X25
VSD270_K__-40
371-02767-X22
VSD419_K__-68
371-03789-X26
VSD270_TFT-40
371-02767-X25
VSD419_TFT-68
371-03789-X27
VSD270_KFT-40
371-02767-X26
VSD419_KFT-68
371-03789-X28
VSD270RT__-40
371-02767-X31
VSD419RT__-68
371-03789-X35
VSD270RK__-40
371-02767-X32
VSD419RK__-68
371-03789-X36
VSD270RTFT-40
371-02767-X35
VSD419RFT-68
371-03789-X37
VSD270RKFT-40
371-02767-X36
VSD419RKFT-68
371-03789-X38
419 HP 50 HZ 400 VAC
292 HP 50 HZ 400 VAC
371-03700-X01
VSD419_T__-50
371-03789-X05
VSD292 K -50
371-03700-X02
VSD419_K__-50
371-03789-X06
VSD292 TFT-50
371-03700-X05
VSD419_TFT-50
371-03789-X07
VSD292 KFT-50
371-03700-X06
VSD419_KFT-50
371-03789-X08
VSD292RT -50
371-03700-X11
VSD419RT__-50
371-03789-X15
VSD292RK -50
371-03700-X12
VSD419RK__-50
371-03789-X16
VSD292RTFT-50
371-03700-X15
VSD419RTFT-50
371-03789-X17
VSD292RKFT-50
371-03700-X16
VSD419RKFT-50
371-03789-X18
VSD292 T -50
424 HP 60 HZ 575 VAC
292 HP 50 HZ 415 VAC
VSD292_T__-50
371-03700-X21
VSD424_T__-58
371-04881-X01
VSD292_K__-50
371-03700-X22
VSD424_K__-58
371-04881-X02
VSD292_TFT-50
371-03700-X25
VSD424_TFT-58
371-04881-X03
VSD292_KFT-50
371-03700-X26
VSD424_KFT-58
371-04881-X04
VSD292RT__-50
371-03700-X31
VSD424RT__-58
371-04881-X11
VSD292RK__-50
371-03700-X32
VSD424RK__-58
371-04881-X12
VSD292RTFT-50
371-03700-X35
VSD424RTFT-58
371-04881-X13
VSD292RKFT-50
371-03700-X36
VSD424RKFT-58
371-04881-X14
503 HP 60 HZ 460 VAC
351 HP 60 HZ 460 VAC
VSD351 T -46
371-02767-X01
VSD503_T__-46
371-03789-X01
VSD351 K -46
371-02767-X02
VSD503_K__-46
371-03789-X02
VSD351 TFT-46
371-02767-X05
VSD503_TFT-46
371-03789-X03
VSD351 KFT-46
371-02767-X06
VSD503_KFT-46
371-03789-X04
VSD351RT-46
371-02767-X11
VSD503RT__-46
371-03789-X11
VSD351RK -46
371-02767-X12
VSD503RK__-46
371-03789-X12
VSD351RFT-46
371-02767-X15
VSD503RTFT-46
371-03789-X13
VSD351RKFT-46
371-02767-X16
VSD503RKFT-46
371-03789-X14
608 HP 60 HZ 575 VAC
385 HP 60 HZ 400 VAC
VSD385_T__-40
371-03789-X21
VSD608_T__-58
371-04563-X01
VSD385_K__-40
371-03789-X22
VSD608_K__-58
371-04563-X02
VSD385_TFT-40
371-03789-X23
VSD608_TFT-58
371-04563-X03
VSD385 KFT-40
371-03789-X24
\VSD608_KFT-58
371-04563-X04
VSD385RT__-40
371-03789-X31
VSD608RT__-58
371-04563-X11
VSD385RK__-40
371-03789-X32
VSD608RK__-58
371-04563-X12
VSD385RTFT-40
371-03789-X33
VSD608RTFT-58
371-04563-X13
VSD385RKFT-40
371-03789-X34
VSD608RKFT-58
371-04563-X14
JOHNSON CONTROLS
5
FORM 160.00-M4
ISSUE DATE: 1/21/2013
TABLE OF CONTENTS
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW ..............................................................................9
OptiSpeed Compressor Drive 270, 292, 351 and 424 Hp ....................................................................... 9
OptiSpeed Compressor Drive 385, 419, 503 and 608 HP .................................................................... 18
575 VAC Drive Differences .................................................................................................................... 18
Harmonic Filter Option General Information.......................................................................................... 18
Harmonic Filter Option 270, 292, 351 and 424 Hp ................................................................................ 30
Harmonic Filter Option 385, 419, 503 and 608 HP ............................................................................... 40
575 VAC Harmonic Filter Differences From 460 VAC Harmonic Filter .................................................. 40
SECTION 2 - OPTISPEED COMPRESSOR DRIVE CONTROL SYSTEM OVERVIEW ....................................... 47
The Control Center ................................................................................................................................47
OptiSpeed Drive Logic Control Board ................................................................................................... 48
OptiSpeed Harmonic Filter Logic Control Board ................................................................................... 49
Microcomputer Control Panel VSD Related Keypad Functions ............................................................ 49
OptiView Control Panel VSD Functions ................................................................................................ 50
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL ..........................................................................................51
Setpoint Requirements .......................................................................................................................... 51
Stability Requirements ..........................................................................................................................51
Full Open Vane Operation ..................................................................................................................... 51
Effects of Surge .....................................................................................................................................51
Drive Not Slowing Down........................................................................................................................52
Drive Does Not Respond To Chiller Surging ......................................................................................... 52
Stability Limit Adjustment ...................................................................................................................... 52
Surge Margin Adjustment ...................................................................................................................... 53
Software Version Changes .................................................................................................................... 53
SAFETY SHUTDOWNS ................................................................................................................................. 54
General Information...............................................................................................................................54
Motor or Starter - Current Imbalance .................................................................................................... 54
VSD - 105 % Motor Current Overload ................................................................................................... 54
VSD - High Converter Heatsink Temperature ....................................................................................... 55
VSD - High Inverter Baseplate Temperature (270, 292, 351, and 424 Hp drive only)........................... 55
VSD - High Phase (X) Inverter Baseplate Temperature (385, 419, 503, and 608 Hp drive only).......... 55
VSD - Precharge Lockout...................................................................................................................... 56
Harmonic Filter - High Baseplate Temperature ..................................................................................... 56
Harmonic Filter - High Total Demand Distortion .................................................................................... 56
CYCLING SHUTDOWNS ............................................................................................................................... 57
General Information...............................................................................................................................57
VSD - DC Bus Voltage Imbalance ......................................................................................................... 57
VSD - High DC Bus Voltage .................................................................................................................. 57
VSD - High Internal Ambient Temperature ............................................................................................ 58
VSD - High Phase A (or B, C) Instantaneous Current ........................................................................... 58
VSD - Initialization Failed ......................................................................................................................58
VSD - Invalid Current Scale Selection................................................................................................... 59
VSD - Logic Board Power Supply ......................................................................................................... 59
VSD - Logic Board Processor ............................................................................................................... 60
VSD - Low Converter Heatsink Temperature ........................................................................................ 60
VSD - Low DC Bus Voltage ................................................................................................................... 61
VSD - Low Inverter Baseplate Temperature .......................................................................................... 61
6
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
TABLE OF CONTENTS (CONT'D)
VSD - Phase A (B, C) Gate Driver ......................................................................................................... 61
VSD - Precharge - DC Bus Voltage Imbalance ..................................................................................... 62
VSD - Precharge - Low DC Bus Voltage ............................................................................................... 62
VSD - Run Signal ..................................................................................................................................62
VSD - Serial Communications ............................................................................................................... 62
VSD - Single Phase Input Power .......................................................................................................... 63
VSD - Stop Contacts Open ................................................................................................................... 64
Harmonic Filter - 110 % Input Current Overload ................................................................................... 64
Harmonic Filter - DC Bus Voltage Imbalance ........................................................................................ 64
Harmonic Filter - DC Current Transformer
1( or 2) ...................................................................................................................................................65
Harmonic Filter - High DC Bus Voltage ................................................................................................. 66
Harmonic Filter - High Phase A (B, C) Current ...................................................................................... 66
Harmonic Filter - Logic Board Or Communications ............................................................................... 66
Harmonic Filter - Logic Board Power Supply ........................................................................................ 66
Harmonic Filter - Low DC Bus Voltage .................................................................................................. 67
Harmonic Filter - Phase Locked Loop ................................................................................................... 67
Harmonic Filter - Precharge - Low DC Bus Voltage .............................................................................. 67
Harmonic Filter - Run Signal ................................................................................................................. 68
WARNING MESSAGES ................................................................................................................................. 69
General Information...............................................................................................................................69
Warning - Vanes Uncalibrated - Fixed Speed ....................................................................................... 69
Warning - Harmonic Filter - Operation Inhibited .................................................................................... 69
Warning - Harmonic Filter - Data Loss .................................................................................................. 69
SECTION 4 - START-UP PREPARATIONS............................................................................................................71
Circuit Breaker Setup ............................................................................................................................71
OptiView Control Center ........................................................................................................................ 72
Micro Computer Control Center ............................................................................................................ 73
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES .............................. 75
General Information...............................................................................................................................75
Verify Failure of the OSCD Power Module 270/292/351/424 Hp Drive ................................................. 75
Verify Failure of the OSCD Power Module 385/419/503/608 Hp Drive ................................................. 79
Verify Failure of the Harmonic Filter Module 270/292/351/385/424 and 419/503/608Hp Drive ............ 82
Replacement of the OSCD Power Module ............................................................................................ 82
Replacement of the Harmonic Filter Power Module .............................................................................. 84
VSD Frequently Asked Questions .................................................................................................................. 85
Temperature ................................................................................................................................................... 93
JOHNSON CONTROLS
7
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LIST OF FIGURES
FIGURE 1 - Elementary Wiring Diagram 270, 292 And 351 Hp On Units Manufactured
After December 2006........................................................................................................................... 10
FIGURE 2 - Elementary Wiring Diagram 270, 292 And 351 Hp On Units Manufactured
Before December 2006........................................................................................................................ 12
FIGURE 3 - Elementary Wiring Diagram 424 Hp On Units Manufactured After December 2006 ........................... 14
FIGURE 4 - Elementary Wiring Diagram 424 Hp On Units Manufactured
Before December 2006........................................................................................................................ 16
FIGURE 5 - Elementary Wiring Diagram 385/419/503 Hp On Units Manufactured
After December 2006........................................................................................................................... 20
FIGURE 6 - Elementary Wiring Diagram 385/419/503 Hp On Units Manufactured
Before December 2006........................................................................................................................ 22
FIGURE 7 - Elementary Wiring Diagram 608 Hp On Units Manufactured After December 2006 ........................... 24
FIGURE 8 - Elementary Wiring Diagram 608 Hp On Units Manufactured
Before December 2006........................................................................................................................ 26
FIGURE 9 - Power Assembly Elementary Wiring Diagram 385/419/503 Hp........................................................... 28
FIGURE 10 - Power Assembly Elementary Wiring Diagram 608 Hp....................................................................... 28
FIGURE 11 - VSD Input Current Without Filter ....................................................................................................... 31
FIGURE 12 - VSD Input Current With Filter ............................................................................................................ 31
FIGURE 13 - Harmomic Filter Elementary Wiring Diagram 270, 292 And 351 Hp On Units
Manufactured After December 2006 .................................................................................................. 32
FIGURE 14 - Harmomic Filter Elementary Wiring Diagram 270, 292 And 351 Hp On Units
Manufactured Before December 2006............................................................................................... 34
FIGURE 15 - Harmomic Filter Elementary Wiring Diagram 424 Hp On Units Manufactured
After December 2006......................................................................................................................... 36
FIGURE 16 - Harmomic Filter Elementary Wiring Diagram 424 Hp On Units Manufactured
Before December 2006...................................................................................................................... 38
FIGURE 17 - Harmonic Filter Wiring Diagram 385, 419 And 503 Hp
After December 2006......................................................................................................................... 42
FIGURE 18 - Harmonic Filter Wiring Diagram 385, 419 And 503 Hp
Before December 2006...................................................................................................................... 42
FIGURE 19 - Harmonic Filter Wiring Diagram 608 Hp After December 2006 ......................................................... 44
FIGURE 20 - Harmonic Filter Wiring Diagram 608 Hp Before December 2006 ...................................................... 44
FIGURE 21 - Adaptive Capacity Control Board For Optiview Control Center ......................................................... 47
FIGURE 22 - Adaptive Capacity Control Board ....................................................................................................... 48
FIGURE 23 - 270/292/351/424 HP Drive IGBT Module Veriication #1................................................................... 76
FIGURE 24 - 270/292/351/424 HP Drive IGBT Module Veriication #2................................................................... 77
FIGURE 25 - 270/292/352/424 HP Drive IGBT Module Veriication #3................................................................... 78
FIGURE 26 - 385/419/503/608 HP Drive IGBT Module Veriication #1................................................................... 79
FIGURE 27 - 385/419/503/608 HP Drive IGBT Module Veriication #2................................................................... 80
FIGURE 28 - 385/419/503/608 HP Drive IGBT Module Veriication #3................................................................... 81
FIGURE 29 - OSCD Power Module ........................................................................................................................ 83
LIST OF TABLES
TABLE 1 - Model Number and Part Numbers ........................................................................................................... 5
TABLE 2 - OSCD - Thermistor Characteristics ....................................................................................................... 60
TABLE 3 - Circuit Breaker Settings ......................................................................................................................... 71
TABLE 4 - Software Reference List 60 HZ Only ..................................................................................................... 89
TABLE 5 - Software Reference List 50 HZ Only ..................................................................................................... 91
TABLE 6 - SI Metric Conversion ............................................................................................................................. 93
8
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
OptiSpeed Compressor Drive 270, 292, 351
and 424 Hp
The new YORK OptiSpeed Compressor Drive (OSCD)
is a liquid cooled, transistorized, PWM inverter in
a highly integrated package. This package is small
enough to mount directly onto the chiller motor, and
small enough to be applied in many retrofit chiller applications. The power section of the drive is composed
of four major blocks: an AC to DC rectifier section
with an integrated pre-charge circuit, a DC link filter
section, a three phase DC to AC inverter section and an
output suppression network.
An electronic circuit breaker with ground fault sensing connects the AC line to an AC line inductor and
then to the DC converter. The line inductor will limit
the amount of fault current so that the electronic circuit breaker is sufficient for protecting the OSCD. Input fuses to the OSCD are no longer needed. The following description of operation is specific for the 351
Hp OSCD unless otherwise noted. Refer to Figure 1
on page 10. The AC to DC semi-converter uses 3
Silicon Controlled Rectifiers (SCR’s) and 3 diodes.
One SCR and one diode are contained in each module.
Three modules are required to converter the 3 phase
input AC voltage into DC voltage (1SCR-3SCR) in
a three-phase bridge configuration (Figure 1 on page
10). The modules are mounted on a liquid cooled
heatsink. The use of the SCR’s in the semiconverter
configuration permits pre-charge of the DC link filter
capacitors when the chiller enters the prelube cycle,
and they also provides a fast disconnect from the AC
line when the chiller enters the coastdown cycle.
When the chiller enters the coastdown cycle the OSCD
is turned off, the SCR’s in the semi-converter are no
longer turned on, and remain in a turned off or nonconducting mode until the next pre-charge cycle. The DC
link filter capacitors will start to discharge through the
bleeder resistors. When the chiller enters the prelube
cycle, the OSCD drive is commanded to pre-charge,
the SCR’s are gradually turned on with a delay angle
to slowly charge the DC link filter capacitors. This is
called the pre-charge period, which last for 20-seconds.
After the 20-second time period has expired, the SCR’s
are gated fully on. The SCR Trigger board (031-02060)
provides the turn on, and turn off commands for the
SCR’s during precharge, and during normal running
condition as commanded by the OSCD Logic board
(031-02077).
JOHNSON CONTROLS
1
Although many of these parts are similar
to the parts used in previous Variable
Speed Drive (VSD) designs, these parts
are only compatible with drives having the
base part numbers included on the cover
of this form. Failure to use the correct
parts may cause major damage to these
and other components in the drive. For
example, the VSD logic board 031-02077000 used in this drive is not compatible
with 031-01433-000 logic board used in
previous designs.
The igures for all horsepower drives are
included in this form, but the component
identiications are speciic for the 351
horsepower drive.
The DC Link filter section of the drive consists of one
basic component, a series of electrolytic filter capacitors (C1-C6). These capacitors provide a large energy
reservoir for use by the DC to AC inverter section of
the OSCD. The capacitors are contained in the OSCD
Power Unit. In order to achieve a suitable voltage capability between the DC Link voltage, and the rating of
the filter capacitors, two capacitors are placed in series
to form a “pair”, and then paralleling a suitable number
of “pairs” to form a capacitor “bank”. In order to assure an equal sharing of the voltage between the series
connected capacitors, and to provide a discharge path
for the capacitor bank when the OSCD is powered off,
“bleeder” resistors (1RES and 2RES) are connected
across the capacitor banks. Four bleeder resistors are
required on the 575 VAC OSCD. Refer to Figure 3 on
page 14 The “Bleeder” resistors are mounted on the
side of the Power Unit.
The DC to AC inverter section of the OSCD serves
to convert the DC voltage back to AC voltage at the
proper magnitude and frequency as commanded by the
OSCD Logic board. The inverter section is actually
composed of one power unit. This power unit is composed of very fast switching transistors called an Insulated Gate Bipolar Transistor (IGBT) module (1MOD)
mounted on the same liquid cooled heatsink as the
semi-converter modules, the DC Link filter capacitors
(C1-C6), a semi-converter, and an OSCD Gate Driver
board (031- 02061).
9
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13100a
FIGURE 1 - ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006
10
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13101a
FIGURE 1 - ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
11
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13100b
FIGURE 2 - ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006
12
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13101b
FIGURE 2 - ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
13
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13102a
FIGURE 3 - ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED AFTER DECEMBER 2006
14
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13103a
FIGURE 3 - ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
15
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13102b
FIGURE 4 - ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006
16
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13103b
FIGURE 4 - ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
17
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
The gate driver board conditions the turn on, and turn
off commands to the IGBT’s output transistors as commanded by the OSCD Logic board. The gate driver
board is mounted directly on top of the IGBT module,
and it is held in place with mounting screws and soldered to the IGBT module. This improves reliability
by eliminating the gate wires and their possible failure.
In order to minimize the parasitic inductance between
the IGBT module and the capacitor bank, copper plates
which electrically connect the capacitors to one another
and to the IGBT module are connected together using a
“laminated bus” structure. This “laminated bus” structure is actually composed of a pair of copper plates
sandwiched between and coated with an insulating material acting as the separator/insulator. The “laminated
bus” structure forms a parasitic capacitor which acts
as a small valued capacitor, effectively canceling the
parasitic inductance of the copper plates themselves.
To further cancel the parasitic inductances, a series of
small film capacitors (C7-C9) are connected between
the positive and negative plates at the IGBT module.
The OSCD output suppression network is composed of
a series of capacitors (C10-C12) and resistors (3RES8RES) connected in a three-phase delta configuration.
The parameters of the suppression network components are chosen to work in unison with the parasitic
inductance of the DC to AC inverter sections in order
to simultaneously limit both the rate of change in voltage and the peak voltage applied to the motor windings. By limiting the peak voltage to the motor windings, as well as the rate-of-change in motor voltage, we
can avoid problems commonly associated with PWM
motor drives, such as stator-winding end-turn failures
and electrical fluting of motor bearings.
Other sensors and boards are used to convey information back to the OSCD Logic board, and provide safe
operation of the OptiSpeed Compressor Drive. The
IGBT module contains a thermistor temperature sensor
(RT1) that provides temperature information back to
the OSCD logic board via the gate driver board. The
AC to DC semi-converter heatsink temperature is also
monitored using a thermistor temperature sensor (RT2).
This sensor is directly connected to the OSCD Logic
Board. The Bus Voltage Isolator board (031-01624)
utilizes three resistors on the board to provide a “safe”
resistance between the DC link filter capacitors located
in the OSCD power unit and the OSCD logic board. It
provides the means to sense the positive, midpoint and
negative voltage connection points of the OSCD DC
link. Three Current Transformers (3T-5T) monitor the
18
output current from the OSCD power unit and are used
to protect the motor from overcurrent conditions.
The 575 VAC OSCD require different part
number boards then the 460 VAC OSCD
or the 50Hz OSCD.
OptiSpeed Compressor Drive 385, 419, 503
and 608 HP
The 385, 419, 503 and 608 Hp OSCD’s function in the
same manner as the 351 Hp and have the same components, but more of them. The power requirements of
these higher horse power drives require more capacitors in the DC Link, and 3 IGBT modules are needed.
One module is used for each output phase. Each IGBT
module contains a thermistor, and they are connected
to the OSCD logic board. The IGBT gate driver board
is mounted on top of the IBGT module as in the 351
Hp, but it only contains 2 drivers. The modules and the
boards are not interchangeable between the different
horsepower drives.
575 VAC Drive Differences
From 460 VAC Drive the 424 and 608 Horsepower
OSCD are 575 VAC versions of the 460 VAC 351 and
503 Hp OSCD. A few changes to the OSCD are required.
First, the input SCR’s voltage rating is increased as
well as the voltage rating for the Bus caps. The OSCD
drive logic is change to accommodate the higher bus
voltage. More bleeder resistors of a higher resistance
value are required to support the higher bus voltage.
Wiring Field Connections (Variable Speed Drive) Replacement Parts List (Variable Speed Drive) (Form
160.00-RP4) contains all of the different part number
required for these products. It is very important not to
mix parts between different voltage ranges OSCD.
Harmonic Filter Option General Information
The OptiSpeed Compressor Drive (OSCD) system may
also include an optional harmonic filter and high frequency trap designed to meet the IEEE Std 519 -1992,
“IEEE Recommended Practices and Requirements for
Harmonic Control in Electrical Power Systems”. The
harmonic filter is offered as a means to improve the input current waveform drawn by the OSCD from the AC
line, thus reducing the possibility of causing electrical
interference with other sensitive electronic equipment
connected to the same power source.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
THIS PAGE INTENTIONALLY LEFT BLANK.
JOHNSON CONTROLS
19
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13104a
FIGURE 5 - ELEMENTARY WIRING DIAGRAM 385/419/503 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006
20
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13105a
FIGURE 5 - ELEMENTARY WIRING DIAGRAM 385/419/503 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
21
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13104b
FIGURE 6 - ELEMENTARY WIRING DIAGRAM 385/419/503 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006
22
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13105b
FIGURE 5 - ELEMENTARY WIRING DIAGRAM 385/419/503 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
23
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13107a
FIGURE 7 - ELEMENTARY WIRING DIAGRAM 608 HP ON UNITS MANUFACTURED AFTER DECEMBER 2006
24
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13108a
FIGURE 7 - ELEMENTARY WIRING DIAGRAM 608 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
25
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13107b
FIGURE 8 - ELEMENTARY WIRING DIAGRAM 608 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006
26
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13108b
FIGURE 8 - ELEMENTARY WIRING DIAGRAM 608 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
27
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13106A
FIGURE 9 - POWER ASSEMBLY ELEMENTARY WIRING DIAGRAM 385/419/503 HP
LD13109A
FIGURE 10 - POWER ASSEMBLY ELEMENTARY WIRING DIAGRAM 608 HP
28
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13106B
FIGURE 9 - POWER ASSEMBLY ELEMENTARY WIRING DIAGRAM 385/419/503 HP (CONT'D)
LD13109B
FIGURE 10 - POWER ASSEMBLY ELEMENTARY WIRING DIAGRAM 608 HP (CONT'D)
JOHNSON CONTROLS
29
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
Figure 11 on page 31 is a typical input current
waveform for the OSCD system without the optional
harmonic filter when the system is operating at 50%
load. Figure 12 on page 31 is a typical input current
waveform for the OSCD system with the optional harmonic filter installed when operating at the same load
conditions. The waveforms show that the input current
waveform is converted from a near square waveform to
a fairly sinusoidal waveform when the harmonic filter
is installed. In addition, the power factor of the system
with the harmonic filter installed corrects the system
power factor to nearly unity.
Harmonic Filter Option 270, 292, 351 and 424
Hp
The power section of the Harmonic Filter is composed
of three major blocks: a pre-charge section, a threephase inductor and a Filter Power Unit. The following description of operation is specific for the 351 Hp
OSCD unless otherwise noted. (see Figure 13 on page
32).
The igures for all horsepower harmonic
ilters are included in this form, but the
component identiications are speciic for
the 351 horsepower drive.
The pre-charge section is formed by three resistors
(9RES - 11RES), and two contactors, pre-charge
contactor 1M and supply contactor 2M. The pre-charge
network serves two purposes, to slowly charge the DC
link filter capacitors associated with the Filter Power
Unit (via the diodes within the IGBT module 2MOD)
and to provide a means of disconnecting the filter power unit from the AC line. When the chiller is turned off,
both contactors are de-energized and the filter power
unit is disconnected from the AC line. When the chiller
starts to run, the pre-charge resistors are switched into
the circuit via contactor 1M for a fixed time period of
5 seconds. This permits the filter capacitors in the filter
power unit to slowly charge. After the 5-second time
period, the supply contactor is energized, and the precharge contactor is de-energized, permitting the filter
power unit to completely charge to the peak of the input power voltage. Three power fuses (8FU - 10FU)
connect the filter power components to the AC line.
Very fast semiconductor power fuses are utilized to ensure that the IGBT module does not rupture if a catastrophic failure were to occur on the DC link of the
filter power unit.
30
FORM 160.00-M4
ISSUE DATE: 1/21/2013
The three phase inductor (2L) provides some impedance for the filter to “work against”. It effectively limits the rate of change in current at the input to the filter
to a reasonable level.
The Filter Power Unit is the most complicated power
component in the optional filter. Its purpose is to generate the harmonic currents required by the OSCD’s
AC-to-DC converter so that these harmonic currents
are not drawn from the AC line. The Filter Power Unit
is identical to the OSCD’s Power Unit in the 351 Hp
drive, except for 2 less capacitors in the filter capacitor
“bank” (C13-C16), a smaller IGBT module (2MOD)
mounted to a direct liquid cooled heatsink, and a Harmonic Filter Gate Driver board (031-02061-002).
The Harmonic Filter Gate Driver board provides turn
on, and turn off commands to the IGBT module as determined by the Harmonic Filter Logic board. In order to assure an equal sharing of the voltage between
the series connected capacitors on the Filter Power
Unit, “bleeder” resistors 12RES and 13RES are connected across the cap bank. The “Bleeder” resistors are
mounted on the side of the Filter Power Unit to provide
a discharge path for the DC Link filter capacitors. In
order to counteract the parasitic inductances in the mechanical structure of the Filter Power Unit, the filter incorporates “laminated bus” technology and a series of
small film capacitors (C23-C25). The “laminated bus”
technology used is identical to that used in the OSCD’s
DC to AC inverter section of the drive.
Other sensors and boards are used to convey information back to the Filter Logic Board, and provide safe
operation of the harmonic filter. The IGBT module contains a thermistor temperature sensor (RT3) that provides temperature information back to the Filter Logic
Board via the Harmonic Filter Gate Driver Board. This
sensor protects the Filter IGBT module from over temperature conditions. DC Current Transformers DCCT1
and DCCT2 sense the current generated by the optional
filter. These two sensors are used to protect against a
filter over current, or a filter overload condition. Current Transformers 6T and 7T sense the input current
drawn by the OSCD’s AC to DC converter. These two
CT’s are no longer present in the standard OSCD.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD07407
FIGURE 11 - VSD INPUT CURRENT WITHOUT FILTER
LD07408
FIGURE 12 - VSD INPUT CURRENT WITH FILTER
JOHNSON CONTROLS
31
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13110a
FIGURE 13 - HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED AFTER DECEMBER 2006
32
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13111a
FIGURE 13- HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED AFTER DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
33
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13110b
FIGURE 14 - HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED BEFORE DECEMBER 2006
34
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13111b
FIGURE 14- HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 270, 292 AND 351 HP ON UNITS MANUFACTURED BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
35
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13112a
FIGURE 15 - HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006
36
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13113a
FIGURE 15 - HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
AFTER DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
37
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13112b
FIGURE 16 - HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006
38
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13113b
FIGURE 16 - HARMOMIC FILTER ELEMENTARY WIRING DIAGRAM 424 HP ON UNITS MANUFACTURED
BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
39
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
The Line Voltage Isolation board (031-02022-000 400
and 460 VAC input, 031-02022-001 575 VAC input)
provides AC line voltage information. This board steps
the line voltage down to a safe level and provides isolation to the Filter Logic board. This information is used
to determine a low bus voltage condition, and what the
proper bus voltage should be. The Bus Isolation board
(031-01624) incorporates three resistors to provide
a “safe” impedance between the DC filter capacitors
located in the Filter Power Unit and the Filter Logic
Board. It provides the means to sense the positive, midpoint and negative connection points of the filter’s DC
link. This information is used to determine bus voltage
imbalance, high bus voltage, and low bus voltage shut
downs.
The “trap” filter is standard on all OSCD that contain
the optional Harmonic Filter. The “trap” filter is composed of a series of capacitors (C17-C22), inductors
(3L-5L) and resistors (14RES-19RES). The “trap” filter acts as a low resistance for a range of frequencies
centered at the switching frequency of the filter. The
purpose of the trap is to block currents at the switching
frequency of the harmonic filter from getting onto the
power mains.
Harmonic Filter Option 385, 419, 503 and 608
HP
The 385, 419, 503 and 608 Hp harmonic filter functions in the same manner as the 351 Hp and have the
many of the same components, but more of them. The
40
FORM 160.00-M4
ISSUE DATE: 1/21/2013
power requirements of these higher horse power drives
require more capacitors in the DC Link, and a higher
current rated IGBT module is needed. The IGBT module contains a thermistor, and it is connected to the harmonic filter logic board. The IGBT gate driver board is
mounted on top of the IBGT module as in the 351 Hp.
The modules and the boards are not interchangeable
between the different horsepower drives.
575 VAC Harmonic Filter Differences From
460 VAC Harmonic Filter
The 424 and 608 Horsepower harmonic filters are 575
VAC versions of the 460 VAC 351 and 503 Hp harmonic filters. A few changes to the OSCD are required.
First, the input IGBT’s voltage rating is increased as
well as the voltage rating for the Bus caps. The harmonic filter logic is change to accommodate the higher
bus voltage and changes in carrier frequency. The trap
assembly has changed because of the changes in the
carrier frequency for the harmonic filter. More bleeder
resistors of a higher resistance value are required to
support the higher bus voltage.
Wiring Field Connections (Variable Speed Drive) Replacement Parts List (Variable Speed Drive) (Form
160.00-RP4) contains all of the different part number
required for these products. It is very important not to
mix parts between different voltage ranged OSCD.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
THIS PAGE INTENTIONALLY LEFT BLANK.
JOHNSON CONTROLS
41
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13116a
FIGURE 17 - HARMONIC FILTER WIRING DIAGRAM 385, 419 AND 503 HP
AFTER DECEMBER 2006
LD13116b
FIGURE 18 - HARMONIC FILTER WIRING DIAGRAM 385, 419 AND 503 HP
BEFORE DECEMBER 2006
42
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13117a
FIGURE 17 - HARMONIC FILTER WIRING DIAGRAM 385, 419 AND 503 HP
AFTER DECEMBER 2006 (CONT'D)
LD13117b
FIGURE 18 - HARMONIC FILTER WIRING DIAGRAM 385, 419 AND 503 HP
BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
43
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
FORM 160.00-M4
ISSUE DATE: 1/21/2013
LD13115a
FIGURE 19 - HARMONIC FILTER WIRING DIAGRAM 608 HP AFTER DECEMBER 2006
LD13115b
FIGURE 20 - HARMONIC FILTER WIRING DIAGRAM 608 HP BEFORE DECEMBER 2006
44
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 1 - HARMONIC FILTER COMPONENT OVERVIEW
1
LD13114a
FIGURE 19 - HARMONIC FILTER WIRING DIAGRAM 608 HP AFTER DECEMBER 2006 (CONT'D)
LD13114b
FIGURE 20 - HARMONIC FILTER WIRING DIAGRAM 608 HP BEFORE DECEMBER 2006 (CONT'D)
JOHNSON CONTROLS
45
FORM 160.00-M4
ISSUE DATE: 1/21/2013
THIS PAGE INTENTIONALLY LEFT BLANK.
46
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 2 - OPTISPEED COMPRESSOR DRIVE
CONTROL SYSTEM OVERVIEW
The OSCD control system can be connected to a Microcomputer Control Center or to an OptiView Control
Center. Regardless of which control center is used each
component performs the same function.
The OSCD control system is composed of various
components located within both the Control Center
and the OSCD. Thus integrating the Control Center
with the OSCD. The OSCD system utilizes various
microprocessors and Digital Signal Processors (DSPs)
which are linked together through a network of parallel
and serial communications links.
The Control Center
The Control Center contains two boards that act upon
OSCD related information, the Microboard and the
Adaptive Capacity Control board (ACC). The ACC
board performs two major functions in the OSCD control system - (1) to act as a gateway for information
flow between the Control Center and the OSCD. (2) To
determine the optimum operating speed for maximum
chiller system efficiency.
The ACC board acts as an information gateway for all
data flowing between the OSCD and the Control Center. The ACC board communicates via a bi-directional
serial port with the OSCD logic board (via J8 on the
ACC board) and uni-directional serial port from the
optional Filter logic board (via J9 on the ACC board)
using a pair of shielded cables. Once the information
is received by the ACC board, the information is then
passed onto the Control Center via a software communication link. The Microcomputer Control Center communicates in a parallel fashion via two ribbon cables
connecting the ACC board to the Microboard (J1 and
J2 on the ACC board, Figure 22 on page 48). The
OptiView Control Center communicates through a bidirectional serial port via a three wire shielded cable
connecting the ACC board to the Microboard (J10 on
the ACC board, Figure 13).
In order to achieve the most efficient operation of a
centrifugal compressor, the speed of the compressor
must be reduced to match the “lift” or “head” of the
load. This “lift” or “head” is determined by the evaporator and condenser refrigerant pressures. However, if
the compressor speed is reduced too much, the refrigerant gas will flow backwards through the compressor
wheel causing the compressor to “surge”, an undesirJOHNSON CONTROLS
2
LD13118a
FIGURE 21 - ADAPTIVE CAPACITY CONTROL
BOARD FOR OPTIVIEW CONTROL
CENTER
able and extremely inefficient operating condition.
Thus there exists one particular optimum operating
speed (on the “edge” of surge) for a given head, which
provides the optimum system efficiency. The compressor’s inletguide vanes, which are used in fixed speed
applications to control the amount of refrigerant gas
flowing through the compressor, are controlled together with the compressor speed on an OSCD chiller system, to obtain the required chilled water temperature
while simultaneously requiring minimum power from
the AC line.
The ACC board automatically generates its own
“Adaptive” three-dimensional surge surface map while
the chiller system is in operation. This “Adaptive” operation is accomplished through the use of a patented
surge detection algorithm. The novel surge detection
system utilizes pressure information obtained from the
chiller’s two pressure transducers or the OSCD’s instantaneous power output to determine if the system
is in “surge”. Thus the adaptive system permits construction of a customized compressor map for each individual chiller system.
Benefits of this new adaptive system include: (1) a
customized compressor map for each chiller which
eliminates inefficient operation due to the safety margin built into the previous designs to compensate for
compressor manufacturing tolerances (2) the ability
to update the system’s surge surface as the unit ages
and (3) automatic updating of the compressor map if
changes in refrigerant are implemented at a later date.
47
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 2 - OPTISPEED COMPRESSOR DRIVE CONTROL SYSTEM OVERVIEW
RED
BLACK
WHITE
375-27735-401
-402
TO
POWER
SUPPLY
J5
J22
1
1
126
J4
J3
J23
J24
575-27733-203
125
MICRO BOARD
031-01065-000
1
49
1
124
1
J5 N/C
1
1
TO VANE POT
J6
575-22733-202
51
J2
RED
WHITE
BLACK
1
J8
SHIELD
1
J25
J1
1
1
J9
1
J26
WHITE
SHIELD
U22
1
U21
1
BRAM
GREEN
EPROM
BLACK
RED
1
ADAPTIVE
CAPACITY
CONTROL
031-01579-000
J7
N/C
1
TO
E
LT
FI
CONTROL PANEL
TB6
R
LO
TO
IC
D
G
VS
LO
GI
C
WHITE "2"
CONDUIT
TO
VSD
CABINET
2
BLACK "L"
L
53
24
16
J10
16
REAR
OF
PLUG
4
1
5
2
6
3
53
24
LD03405a
FIGURE 22 - ADAPTIVE CAPACITY CONTROL BOARD
OptiSpeed Drive Logic Control Board
Within the OSCD enclosure, the OSCD logic board
and optional Filter logic board are interconnected via
a 16-position ribbon cable. The Filter Logic board derives its control power from the OSCD Logic board
over this ribbon cable. In addition, various logic level
“handshake” signals convey the operating status of the
OSCD to the Filter and vice versa over this cable. Finally, the cable includes a unidirectional serial communications link, which permits the transmission of a
limited amount of data, such as the run command, from
the OSCD to the optional Harmonic Filter.
The OSCD Logic board performs numerous functions,
control of the OSCD’s cooling fans and pumps, when
to pre-charge the bus capacitors, and generates the
PWM.
• The cooling fans and pumps are commanded to
turn on whenever the OSCD is commanded to run.
They will turn off when the drive is commanded
to stop. If the OSCD is shutdown due to a hightemperature condition, then the fans and pumps
will continue to run until the value of the hightemperature has dropped below a speciied value.
The cooling fans and pumps will also run if the J2
connector is removed.
• The OSCD Logic board sends a command signal
to the SCR gate driver board to precharge the bus
capacitors. For pre-charge to become active J6 Pin
3 must be low, and J6 Pin 5 must be at 7.5 VDC.
• The PWM generation is required so that the output of the OSCD will provide to the motor the
proper voltage for a given output frequency.
The PWM generation is sent to the IGBT gate
driver board via J8, J9, and J10.
48
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 2 - OPTISPEED COMPRESSOR DRIVE CONTROL SYSTEM OVERVIEW
The OSCD Logic board also determines shutdown
conditions by monitoring the three phases of motor
current, heatsink temperature, baseplate temperature,
internal ambient temperature, and the DC Link voltage.
• The output motor current is monitored by the
current transformers mounted in the center of
the drive. They are connected to the OSCD logic
board on J6.
• The heatsink temperature is monitored by a thermistor mounted on the same side of the chill plate as
the SCR/Diode blocks. This sensor is connected
to the OSCD logic board on J2.
• The baseplate temperature is monitored by a
thermistor mounted inside the IGBT module.
Each IGBT module in the 503 Hp drive has a
thermistor. Any one of the 3 thermistors can cause
an over temperature fault. They are connected to
the OSCD logic board via the IGBT gate drive
board and then onto J2.
• The internal ambient temperature is monitored by
a thermistor mounted on the OSCD Logic board.
• The DC Bus voltage is monitored by the DC link
isolator board. It is connected to the OSCD logic
board on J3.
OptiSpeed Harmonic Filter Logic Control
Board
The optional Harmonic Filter logic board determines
when to precharge the filter power unit, when to switch
the IGBT’s in the filter power unit, and collects data to
determine power calculations. Data such as input line
voltage, filter DC bus voltage, output current of the filter power unit, and temperature of the filter power unit
IGBT’s are collected and sent to the Control Center.
This data is also used by the filter logic board to determine if a shutdown is required.
• The Harmonic Filter Logic board sends a command signal to the pre-charge contactor to become active J4 Pin 1 must be 115 VAC
• The Harmonic Filter Logic board sends a command signal to the supply contactor to become active J4 Pin 3 must be 115 VAC
• It turns on and off the Harmonic Filter IGBT’s via
J2
• It sends communications to the ACC board via J8.
JOHNSON CONTROLS
The Harmonic Filter Logic board also determines shutdown conditions by monitoring the two phases of input
current, two phases of filter output current, baseplate
temperature of the harmonic filter IGBT, input line
voltage, and the DC Link voltage.
• The input current is monitored by the current
transformers mounted near the ilter inductor.
They are connected to the ilter logic board on J3
pins 1-4.
• The ilter current is monitored by the DC current
transformers mounted between the wires to ilter
inductor and the ilter’s IGBT module. They are
connected to the ilter logic board on J3 pins 5-7
and 10-12.
• The baseplate temperature is monitored by a
thermistor mounted inside the harmonic ilter
IGBT module. This sensor is connected to the ilter logic board via the IGBT gate drive board and
then onto J6 pins 1 and 2.
• The input voltage is monitored by the AC line
voltage isolator board and is connected to the ilter logic board on J5 pins 1-4. Measuring AC voltage from pins 1-2, 2-3, 3-1, should have a value of
5.2 VAC with a 460 VAC line voltage.
• The DC Bus voltage is monitored by the DC link
isolator board. It is connected to the ilter logic
board on J5 pins 5-7.
Microcomputer Control Panel VSD Related
Keypad Functions
Refer to Service Model TM (Variable Speed Drive)
(Form 160.00-M1) for related keypad functions. Some
of the displayed data in this form is different from the
160.00-M1.
Under the Options Key – the following changes will
be displayed:
VSD PHASE A INVERTER HEATSINK TEMP = ___°F.
VSD PHASE B INVERTER HEATSINK TEMP = ___°F.
VSD PHASE C INVERTER HEATSINK TEMP = ___°F.
These three temperature values are replaced with:
VSD BASEPLATE TEMP = ___°F.
for the 270, 292, 351 385, and 424 Hp drive. The 419,
503 and 608 Hp drive will still display 3 phases of
Baseplate temperature. When the Filter is present the
following data will be changed.
49
2
SECTION 2 - OPTISPEED COMPRESSOR DRIVE CONTROL SYSTEM OVERVIEW
FILTER HEATSINK TEMP = ___°F.
This temperature data will now be called.
FILTER BASEPLATE TEMP = ___°F.
The names for the above data were changed because
the temperature sensor is now inside the IGBT module
instead on the chill plate where the IGBT’s are mounted. This new sensor gives a better indication of true
temperature of the IGBT module.
50
FORM 160.00-M4
ISSUE DATE: 1/21/2013
OptiView Control Panel VSD Functions
Refer to the specific OptiViewControl Panel service
book for detailed information. All of the OSCD related
information is contained under the Motor and Compressor Screens.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
The YORK OptiSpeed Compressor Drive utilizes a different approach to speed reduction compared to earlier
variable speed products. There is no preprogrammed
surge map – the YORK adaptive system experiments
with the speed and vanes to find the optimum speed
for any given condition. It does not always encounter a
“Surge” in the process, but when it does, the Adaptive
Capacity Control (ACC) stores into memory, the conditions surrounding the Surge, and therefore remembers to avoid the stored operating point anytime in the
future. This sounds a bit mysterious, but the process is
really quite simple. Once you have an understanding of
the steps involved, you will be able to watch the chiller
adjust itself to different conditions, and understand exactly why it is performing in the manner it does.
Early versions of the ACC software required that the
drive always start and run up to full speed. ACC software starting with version C.ACC.01.04 applies a slow
ramp up of the drive speed. This new software lowers
the peak current demand from the drive during start up,
saves additional energy, and reduces the possibility of
the chiller running in a stall condition.
The new software will ramp the drive speed up to 30
Hz quickly, and then takes 5 minutes to ramp up to 60
Hz. During this slow ramp up period the vanes will
open to meet the cooling demand. If the leaving chilled
liquid temperature is within +0.5 or lower of the leaving chilled liquid temperature setpoint, then the drive
speed will stop increasing and start to search for a
surge map point. On extremely hot days the chiller will
surge during the slow ramp period. The new software
has a method to limit the surging. If 2 surges were to
occur during the slow ramp period, then the speed of
the drive will increase quickly to 60 Hz.
All versions of software require that two conditions be
met for speed reduction to occur. These two conditions
are:
Setpoint Requirements
The leaving chilled liquid temperature must be within
+0.5 °F or lower from the leaving chilled liquid temperature setpoint. Speed reduction will not occur until the leaving chilled liquid temperature reaches this
range.
JOHNSON CONTROLS
Stability Requirements
The leaving chilled liquid temperature must be stable,
with the vanes not driving open or closed to maintain
the temperature. Lack of stability will be evidenced by
the vanes hunting, the leaving chilled liquid temperature varying, and the green LED on the ACC board will
be on, to indicate instability. Once the above conditions
are met, the ACC board may begin to lower the speed
of the compressor motor 1/10 of a hertz at a time. As
the ACC board lowers the speed, the leaving chilled
liquid temperature will begin to creep up, due to the
reduction in speed. As this occurs, the control center
will begin to open the vanes slightly, just enough to
maintain the leaving chilled liquid temperature within +/- 0.5°F of the leaving chilled liquid temperature
setpoint. The ACC board will continue to lower speed,
with the leaving chilled liquid temperature control in
turn driving the vanes to a more open position. This
process will continue until one of three following situations occurs.
Full Open Vane Operation
Once the vanes reach the full open position, the ACC
board knows it can no longer reduce speed and maintain the leaving chilled liquid temperature setpoint.
The ACC board will maintain operation at this point,
with the vanes full open, and the speed at the last point
reached when the vanes hit 100%. If there is an increase
in load while at this point, the ACC board will increase
speed until the vanes are closed to 95% of open. The
ACC board will then be allowed to continue to reduce
speed again.
Effects of Surge
If in the process of reducing speed and opening vanes
the compressor should surge, the ACC board will boost
the speed up by 0.8 Hz. The ACC board will store in
memory a value that is (condenser pressure/evaporator pressure) - 1, the vane position present at the time
of the surge, and the speed of the drive. The value for
(condenser pressure/evaporator pressure) – 1 is displayed as Delta P/P on the Control Panel. The ACC
board will then knownot to reduce speed this low
again, if the same delta pressure, and the vane position conditions are encounter again in the future. As the
51
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
chiller encounters more delta pressure and vane position combinations, which result in surge, it will store
more points, and eventually this storing of points creates a “Surge Map”.
Surges may be detected in two ways, by monitoring the
pressure differential across the compressor, or by monitoring the compressor motor current. Either detection
will light the Red LED on the ACC board, indicating a
surge was detected. The chiller may surge 6 to 8 times
before the ACC board can raise the speed enough to
get the chiller back out of surge. Each surge is counted
on the surge counter, which may be called up on the
control center. This surge counter will always display
the total number of surges encountered by the chiller as
determined by the ACC board, but not the total number
of points contained in the surge map.
Surging which occurs at fixed speed will increment the
surge counter as well, but only surges that occur when
speed reduction is possible are recorded in the surge
map. We know of one chiller, which ran in continuous
surge for two weeks due to a cooling tower problem.
The customer’s fixed speed chiller was surging continuously for 2 weeks also. During this time, the VSD
surge counter accumulated over 18,000 surges.
Drive Not Slowing Down
The ACC board may begin the process of reducing
speed, but may stop speed reduction prematurely if
instability is encountered. This is the same instability
discussed as one of the two conditions which must be
met to begin reducing speed initially (See “Stability
Requirements”). Once the system again becomes unstable, no additional speed reduction can occur. The
most common causes for instability are:
• Rapid changes to chilled or condenser liquid low.
(Variable speed pumps may not work well)
• Valves on air-handler coils closing rapidly causes
changes in heat-load.
• Extremely short chilled liquid loop.
• Parallel chiller with poor control is causing temperature variations.
• Parallel chiller with poor control of chilled or condenser water lows.
• Dirty condenser tubes or high condenser liquid
temperature.
• Chillers with very light loads.
• Liquid level control not working properly.
52
If you experience a problem with an OSCD not reducing
speed at all, make certain the system is not in manual
speed control, or locked into fixed speed. Refer to the
section on “Manual Speed Control” in the “Frequently
Asked Questions” section. Also, make certain the wiring at J3 on the ACC board is properly connected per
the wiring diagram in this same manual. Either situation
will cause the chiller to maintain full speed. If the OSCD
is reducing speed, but not running as slow as you expect
it should, it is likely because it is either in an unstable
condition, or running just above a mapped surge point.
As described above, the chiller must achieve stability, which is evidenced by the Green LED being extinguished. Instability will cause the Green LED to be
illuminated. To determine if the chiller is running just
above a surge point, switch the system to manual speed
control, and force the speed lower by one or two hertz.
If you encounter a surge, this explains why the chiller
would not reduce speed. If you find the chiller does
drop speed without surging, instability was likely preventing further speed reduction.
Drive Does Not Respond To Chiller Surging
The ACC control uses information from the condenser
and evaporator pressure transducers to determine if
the chillers has surged. If the chiller is surging and the
speed of the drive is not increasing, then the wiring to
the ACC board on J3 should be verified. Many times
where an OSCD is retrofitted to and existing chiller
the wiring to J3 is forgotten. A few new chillers with
OSCD’s have the wiring to the J3 of the ACC or at the
control center microboard wired incorrectly.
Stability Limit Adjustment
Stability Limit Adjustment allows the system to properly function with larger amounts of temperature instability. Refer to Service (Control Panel) Model YT, (Centrifugal) (Form 160.55.M1), or Service (Control Panel)
Model YK, (Centrifugal) (Form 160.54.M1) for the
location of this parameter. Stability Limit has a range
of 1000-7000. Although the leaving chilled liquid temperature Setpoint Requirement is satisfied, the Stability
Requirement must also be satisfied. When the Stability
Limit is adjusted to a value of 1000, then the leaving
chilled liquid temperature can not change more than
0.067°F/second. When the Stability Limit is adjusted
to a value of 6999, the leaving chilled liquid temperature can not change more than 0.47°F/second. If you
are having a problem with a lightly load chiller and the
temperature is not stable, then adjust the Stability Limit
to 7000. The value of 7000 will disable this parameter.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Surge Margin Adjustment
Surge Margin Adjustment allows the surge map to increase the frequency portion of the surge map. This parameter is rarely used, and it decreases the efficient of
the OSCD chiller system. Some people believe that this
value can help with a stall condition. This is not true.
Actually, increasing the Surge Margin Adjustment will
cause the stall condition to be worse. Increasing the
speed of the compressor will cause the vane to close
even more and increase the stall noise and vibration.
Software Version Changes
• Software version C.ACC.01.03 improved the
communications between the ACC board and the
OSCD logic board.
JOHNSON CONTROLS
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
• Software version C.ACC.01.03a made additional
improvements to the communications between
the ACC board and the OSCD logic board.
• Software version C.ACC.01.04 added a slow
ramp when the chiller is started. This version requires that a pulldown demand limit be set to 80%
for 5 minutes.
• Software version C.ACC.01.05 changes how the
ACC control will detect a surge. This version is
required for new compressor designs. This software is backwards compatible with older compressors as well.
53
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
SAFETY SHUTDOWNS
Motor or Starter - Current Imbalance
General Information
Message: MOTOR OR STARTER – CURRENT
The Shutdowns are organized in alphabetical orderbased on the OptiView Control Center messages. The
Microcomputer Control Center messages are also included under these headings.
Whenever a Safety Shutdown is generated by the
OSCD or Harmonic Filter Logic Board, a series of
events will occur.
• If the chiller is not running at the time of the shutdown, the OSCD Logic Board will not turn on the
IGBT gate drivers.
• The K1 relay on the OSCD logic board will deenergize causing an open circuit between J12-3 wire
#53 and J12-4 wire #16. This action will indicate
to the Control Center that the OSCD has shut-
down. The K1 relay will remain de-energized
until the cause of the shutdown has been corrected.
• If the chiller is running at the time of the shutdown, the Control Center will start a coastdown
period (150 seconds for centrifugal chillers).
The message “VSD Shutdown - Requesting Fault
Data”...will be displayed when the Control Center
is requesting the fault data from the OSCD.
The OSCD or Harmonic Filter Logic Board will
send a shutdown code via the serial communications link to the ACC board and then to the Control Center. The Micro Board will interpret the
shutdown code, and display a shutdown message
on the display of the Control Center.
After the coastdown period has timed out, the chiller
may be restarted, if the shutdown is no longer active.
Place the Compressor Switch in the Stop/Reset position, and then into the Start position and release. The
chiller will start if no faults are active.
54
IMBALANCE
The OSCD logic board generates this shutdown. This
shutdown will become active when the highest of the
three motor currents exceeds 80% of the programmed
FLA. After these conditions are met, if any one phase
of motor current exceeds 30% of the average current
for 45 seconds, a Safety shutdown will occur. Review
the following example.
If
current in the A phase = 200A
current in the B phase = 200A
current in the C phase = 118A
Then
IAVE = 200 + 200 + 118
3
IAVE = 173A
IACCEPTABLE = 173 * ± 30% = 121A, 225A
Therefore
Since phase “C” current = 118A which is less than the
acceptable 121A, the chiller would shutdown if this
imbalance exists for 45 seconds.
Possible Problems:
• Verify that all six of the gate driver LED’s are lit.
• Verify that the output CT’s are reading current
correctly.
VSD - 105 % Motor Current Overload
Message: 105% MOTOR CURRENT OVERLOAD
The OSCD logic board generates this shutdown, by
reading the current from the 3 output current transformers. The shutdown is generated when the OSCD
logic board has detected that the highest of the three
output phase currents has exceeded 105% of the programmed 100% full load amps (FLA) value for more
than 40 seconds. The 100% FLA setpoint is determined
by adjustment of the FLA trimpot on the OSCD logic
board. This shutdown requires a manual reset via the
Reset push-button on the OSCD logic board.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Possible Problems:
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
Possible Problems:
• FLA value not properly set for the application.
• Improper coolant level for the drive.
• High condenser pressure.
• Shipping coolant not drained at start-up.
• Too much refrigerant in the chiller causing carry
over.
• Clogged chill plate.
• Refrigerant level sensor or system not working
properly.
VSD - High Converter Heatsink Temperature
Message: HIGH CONVERTER HEATSINK TEMP
A thermistor sensor is positioned on the bottom of the
copper chill plate where the SCR/Diode blocks are located. If at anytime this thermistor detects a temperature of 170°F (76°C) or higher a shutdown will occur.
The cooling fans and coolant pump on the OSCD will
continue to run after the shutdown, until the thermistor
temperature has dropped to below 160°F (71°C). This
shutdown requires a manual reset via the Reset pushbutton on the OSCD logic board.
Possible Problems:
• Low condenser water low.
• Dirty tube and shell heat exchanger.
• Failure of the coolant pump.
3
VSD - High Phase (X) Inverter Baseplate
Temperature (385, 419, 503, and 608 Hp drive
only)
Message: HIGH PHASE (X) BASEPLATE
TEMPERATURE FAULT
The X will indicate the phase that the high
temperature has occurred.
• Low condenser water low.
A thermistor sensor is located inside the IGBT Module
on the OSCD power unit. If at anytime this thermistor
detects a temperature of 175°F (79°C) or higher a shutdown will occur. The cooling fans and coolant pump
on the OSCD will continue to run after the shutdown,
until the thermistor temperature has dropped to below
165°F (74°C). This shutdown requires a manual reset
via the Reset push-button on the OSCD logic board.
• Dirty tube and shell heat exchanger.
Possible Problems:
• Improper coolant level for the drive.
• Leaks within the cooling system.
• Shipping coolant not drained at start-up.
• Clogged chill plate.
• Failure of the coolant pump.
• Improper coolant level for the drive.
• Failure of a fuse for the coolant pump.
• Shipping coolant not drained at start-up.
VSD - High Inverter Baseplate Temperature
(270, 292, 351, and 424 Hp drive only)
• Clogged chill plate.
Message: HIGH INVERTER BASEPLATE
• Dirty tube and shell heat exchanger.
TEMPERATURE FLT
A thermistor sensor is located inside the IGBT Module
on the OSCD power unit. If at anytime this thermistor
detects a temperature of 175°F (79°C) or higher a shutdown will occur. The cooling fans and coolant pump
on the OSCD will continue to run after the shutdown,
until the thermistor temperature has dropped to below
165°F (74°C). This shutdown requires a manual reset
via the Reset push-button on the OSCD logic board.
JOHNSON CONTROLS
• Low condenser water low.
• No thermal grease used on the IGBT module.
• Failure of the coolant pump.
• Improper torque used during the mounting of the
IGBT module.
55
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
VSD - Precharge Lockout
Message: PRE-CHARGE FAULT LOCKOUT
If the OSCD fails to meet the pre-charge criteria (refer
to pre-charge faults), then the pre-charge circuit will
wait for a period of 10 seconds. During which time the
unit’s cooling fans and coolant pump shall remain energized in order to cool the input SCR’s. Following this
10-second cool-down period pre-charge shall again be
initiated. The unit shall attempt to meet the pre-charge
criteria three consecutive times. If the OSCD fails to
meet the pre-charge criteria on three consecutive tries,
the OSCD will shut down, lockout, and display this
message. In order to initiate pre-charge again, the Control Center’s compressor switch must first be placed
into the STOP/ RESET position.
Harmonic Filter - High Baseplate Temperature
Message: HIGH FILTER BASEPLATE TEMPERATURE
FAULT
A thermistor sensor is located inside the IGBT Module
on the harmonic filter power unit. If at anytime this
thermistor detects a temperature higher then the shutdown threshold as determined by the harmonic filter
logic board. Refer to the chart below for the shutdown
threshold value. A manual reset is required by pressing
the “Overtemp Reset” pushbutton located on the Filter
Logic board.
DRIVE HP RATING
THRESHOLD SHUTDOWN
VALUE
270, 292, 351
175°F, 79°C
385, 419,424,503,608
190°F, 88°C
Possible Problems:
• Improper coolant level for the drive.
• Shipping coolant not drained at start-up.
• Clogged chill plate.
Harmonic Filter - High Total Demand
Distortion
Message: FLTR HIGH TDD FLT
The control center determines this shutdown by using data supplied from the harmonic filter logic board.
This shutdown indicates that the filter is not operating correctly or the input voltage to the OSCD/filter
system is not sinusoidal. This shutdown will occur if
the Total Demand Distortion (TDD) in any one phase
exceeds 25% continuously for 45 seconds. TDD is an
acronym for Total Demand Distortion, a term defined
by the IEEE Std 519-1992 standard as “the total root
- sum - square harmonic current distortion, in percent
of the maximum demand load current (15 or 30 min
demand)”. In the filter option supplied by York, the
displayed TDD is the total RMS value of the harmonic
current supplied by the power mains to the OSCD system divided by the FLA of the OSCD, in percent. The
harmonic filter option was designed to provide an input
current TDD level of 8% or less for the OSCD system.
A standard OSCD less the optional filter typically has
an input current TDD level on the order of 28 - 30%.
In order to initiate a chiller run again, the Control Center’s compressor switch must first be placed into the
STOP/RESET position.
Possible Problems:
• Failure of the harmonic ilter logic board.
• Wiring error or failure between the harmonic ilter
logic board and the harmonic ilter power unit.
• Verify that the 6 LED’s are lit on the harmonic ilter IGBT gate driver board. If one LED is not lit,
then the IGBT gate driver board and IGBT module needs to be replaced.
• Ensure that all wiring to the ilter logic board and
the ilter IGBT module are properly phased.
• Low condenser water low.
• Dirty tube and shell heat exchanger.
• Failure of the coolant pump.
• No thermal grease used on the IGBT module.
56
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
CYCLING SHUTDOWNS
General Information
The Shutdowns are organized in alphabetical order
based on the OptiView Control Center Panel messages.
The Microcomputer Control Panel messages are also
included under these headings.
Whenever the OSCD or Harmonic Filter Logic Board
generates a Cycling Shutdown a series of events will
occur.
• If the chiller is not running at the time of the shutdown, the OSCD Logic Board will not turn on the
IGBT gate drivers.
• The K1 relay on the OSCD logic board will deenergize causing an open circuit between J12-3 wire
#53 and J12-4 wire #16. This action will indicate
to the Control Center that the OSCD has shutdown. The K1 relay will remain deenergized until
the cause of the shutdown has been corrected.
• If the chiller is running at the time of the shutdown, the Control Center will start a coastdown
period ( 150 seconds for centrifugal chillers ).
• The message “VSD Shutdown - Requesting Fault
Data”...will be displayed when the Control Center
is requesting the fault data from the OSCD.
• The OSCD or Harmonic Filter Logic Board will
send a shutdown code via the serial communications
link to the Adaptive Capacity Control Board and
then to the Control Center. The Micro Board will interpret the shutdown code, and display a shutdown
message on the display of the Control Center.
After the coastdown period has timed out, the chiller
will automatically restart, if the shutdown is no longer
active. Leave the Compressor Switch in the Run position. The chiller will start if no faults are active.
VSD - DC Bus Voltage Imbalance
Message: BUS VOLTAGE IMBALANCE FAULT
Te DC link is filtered by many large, electrolytic capacitors, which are rated for 450 VDC. These capacitors are wired in series to achieve a 900 VDC capability for the DC link. It is important that the voltage is
shared equally from the junction of the center, or series capacitor connection, to the negative bus and to
the positive bus. This center point should be approximately ½ of the total DC link voltage. If the voltage is
greater than ± 88 VDC from the ½ of the total DC link
voltage, then this shutdown will occur.
JOHNSON CONTROLS
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
First verify the operation of the DC bus voltage isolation board, and all associated wiring to the OSCD logic
board. Many times the actual bus voltage imbalance
conditions are caused by a shorted capacitor, or a leaky
or shorted IGBT transistor in the power unit. In order
to check for these conditions, connect a 12 VDC source
(such as a battery charger used to charge automobile
batteries) and apply 12 VDC between the positive bus
and negative bus plates on the power unit while measuring the voltage from center to plus, and center to
minus. The bank, which is causing the imbalance, will
be evident via unequal voltage readings.
Possible Problems:
• Bleeder resistors failure due to overheating. Ensure that thermal grease is applied when the resistors are replaced.
• OSCD’s built after 5/05 no longer use thermal
grease on the bleeder resistors. They use a thermal
pad and a 2.4 k ohm resistor.
• Ensure that both of the bleeder resistors are of the
same value. If one 2.0 k ohm resistor were to fail,
then both resistors should be replaced with the 2.4
k ohm resistor and a thermal pad.
• Failure of the bus voltage isolation board. Use 2
DC volt meters to verify the voltage across the
2 halves of the DC bus. If the voltage is correct,
then measure the DC bus voltage at the J3 connector of the OSCD logic board.
• A shorted or open capacitor in one half of the
bank.
VSD - High DC Bus Voltage
Message: BUS OVER-VOLTAGE FAULT
The DC bus voltage is continuously monitored by the
OSCD logic board through the bus voltage isolation
board. If the level exceeds 745 VDC (for 400 or 460
VAC line voltage) and 909 VDC (for 575 VAC line
voltage), a shutdown is initiated. This shutdown will
protect the capacitors from a voltage that exceeds this
rating.
Possible Problems:
• Ensure that the line voltage is within the speciication for you application. For example, the line
voltage speciication for a 460 VAC drive is 414
to 508 VAC or a 10% variation.
• Ensure that this shutdown is not a result of a storm.
Verify that the compressor motor is not shorted.
57
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
VSD - High Internal Ambient Temperature
Message: HIGH AMBIENT TEMPERATURE FLT
The ambient temperature of the OSCD is monitored
by a temperature sensor mounted on the OSCD logic
board. The high ambient trip threshold is set for 145°F
(63°C) for all Hp’s except the 424 Hp which has a trip
threshold of 153°F (67°C). If this fault occurs, the fans
and coolant pump will remain turn on until the internal
ambient temperature has fallen to 137°F (58°C) for all
Hp’s except the 424 Hp will continue to run the fans
and pumps until the internal ambient temperature has
fallen to 145°F (63°C).
Possible Problems:
• Improper coolant level for the drive.
• Internal fan failure at the cooling coil.
• Entering condenser water temperature of greater
then 114°F or 45°C.
• Dirty shell and tube heat exchanger. Regular
maintenance of tube cleaning once a year is required.
• Low Condenser Flow - The OSCD system requires 8 feet of head on the condenser to maintain
adequate GPM. If the head is less than 8 feet, it
will be necessary to correct the low problem, or
add a booster pump as is sometimes applied on
remote mounted retroit OSCDs.
• Failure of the fan or pump relay.
VSD - High Phase A (or B, C) Instantaneous
Current
Message: PHASE A (OR B, C) OVERCURRENT FAULT
This shutdown is generated by the OSCD logic board.
If any one phase of motor current as measured by
the Output Current Transformers exceeds a threshold
as determined by the OSCD logic board a shutdown
will occur. Refer to the chart below for the shutdown
threshold value.
DRIVE HP RATING THRESHOLD SHUTDOWN VALUE
270, 292, 351, 424
771 amps peak
385, 419, 503, 608
1200 amps peak
If an Instantaneous Current Fault occurs, but the chiller
restarts and runs without a problem, the cause may be
attributed to a voltage sag on the utility power feeding
the OSCD that is in excess of the specified dip voltage rating for this product. This is especially true if the
58
chiller was running at, or near, full load. If there is a
sudden dip in line voltage, the current to the motor will
increase, since the motor wants to draw constant horsepower. The change in the output current due to an input
power fluctuation is a very quick event on the order
of several line cycles. The chiller vanes cannot close
quickly enough to correct for this sudden increase in
current, and the chiller will trip on this fault.
Possible Problems:
• Normal condition if a large power consuming
device is started, such as another chiller, or large
machinery. If this is the case then the chiller will
auto restart.
• OSCD logic board failure. Rotate the J8, J9, and J10
connectors on the OSCD logic board. If the fault continues on the same output phase, then the OSCD logic
board has failed. If the fault follows the output phase
then continue. Be sure to return the connectors to their
correct location after this test. If the connectors are not
returned, then the KW reading will not be correct.
• Shorted OSCD power unit. Perform troubleshooting check for Failure of the OSCD Power Module.
• Power supply failure on the IGBT gate driver
board will be indicated by one of the six LED not
being lit.
• Shorted motor, Meg the motor phase to phase and
phase to ground.
• The motor or compressor has a locked rotor. Ensure that the coupling between the motor and
compressor is free to rotate.
• Power factor correction capacitors are applied on
the same input line as the drive.
• Too much refrigerant in the chiller causing carry
over.
• Refrigerant level sensor or system not working
properly.
VSD - Initialization Failed
Message: VSD INITIALIZATION FAILED
At power-up, the OSCD logic board will go through a
process called initialization. At this time, memory locations are cleared, jumper positions are checked, and
serial communications links are established between
the OSCD logic board, ACC board, and the Control
Center.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Possible Problems:
• The Control Center and the OSCD must be energized at the same time. The practice of pulling the
fuse in the control center to make wiring changes
will create a problem. Power-up must be done by
closing the main disconnect on the OSCD cabinet
with all fuses in place. Be sure you do not have
an open fuse, causing loss of power to the OSCD
logic board.
• The EPROMs must be correct for each board,
and they must be correctly installed. There are
a total of seven (7) EPROMs in each OSCD Micropanel system. These EPROMs are created
as a set, and cannot be intermixed between earlier
and later styles of units. Also, the ACC EPROM
must be in the ACC board, and the Micropanel
EPROM in the Microboard, etc. All pins must be
properly inserted into the EPROM sockets. Refer
to the Software Reference List.
• Serial data communications must be established.
See the write-ups for the messages, “Serial Receive Fault”. If communication among the OSCD
logic, the ilter logic, the ACC board and the
Microboard does not take place at initialization,
the “VSD Initialization Failed” message will occur before any other message can be generated.
You can check to see that serial communications has been established by selecting the Motor
Screen and verifying the drive horsepower. A zero
displayed value for this parameter (and all other
OSCD parameters) indicates a serial communications link or EPROM problem.
• If the Harmonic Filter option is included, make
sure the Harmonic Filter Logic board is not in
continuous reset. This will be evidenced by the
LEDs on the ilter logic board alternately blinking. This situation is addressed elsewhere in this
literature. To rule out the Harmonic Filter as the
cause of initialization failure, you can disconnect
the ilter by switching the ilter logic board’s SW1
switch to the OFF position, and removing the 16
wire ribbon cable between the Harmonic Filter
logic and OSCD logic boards.
• Many times when the OSCD logic board is replaced the small U40 chip is not transferred to the
new board. Ensure that the U40 chip is properly
installed.
JOHNSON CONTROLS
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
VSD - Invalid Current Scale Selection
Message: INVALID CURRENT SCALE FAULT
This shutdown is generated by the OSCD logic board.
The J1 connector on the OSCD logic board contains
jumpers along with wires from the output CTs. Since
the part number of the logic board is the same on all
horsepower sizes, the jumpers tell the logic board the
size of the OSCD being employed in order to properly
scale the output current. If the jumper configuration is
found by the logic board to be invalid, the system will
be shut down and the above message will be generated.
Possible Problems:
• The wire jumpers on the J1 connector or pins in
the J1 connector of the OSCD logic board may not
be properly installed, loose, or missing. Refer to
the chart below for the proper jumper coniguration.
DRIVE HP RATING
WIRE JUMPER CONFIGURATION
270, 292, 351, 424
J1-9 to J1-10
385, 419, 503, 608
J1-9 to J1-11
If the wire jumper is not connected then the OSCD will
tell the control center that an 1100 Hp drive is connected. The current displayed on the control center will
be correct.
VSD - Logic Board Power Supply
Message: MAIN BOARD POWER SUPPLY
This shutdown is generated by the OSCD logic board,
and it indicates that one of the low voltage power supplies for the OSCD logic board has dropped below their
allowable operating limits. The power supplies for the
logic boards are derived from the secondary of the 120
to 24 VAC transformer (Figure 1 on page 10) which
in turn is derived from the 480 to 120 VAC control
transformer (Figure 1 on page 10).
Possible Problems:
• This message normally appears when the power
is removed and reapplied. This is not a failure,
but the rest of the steps should be followed if this
shutdown persists.
• The small control transformer that provides power to the OSCD is failing. Measure the output of
the transformer with a DVM. The voltage should
be between 24 – 32 VAC.
59
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
• The input voltage to the small control transformer
is too low. Measure the input voltage of the
transformer with a DVM. The voltage should
be between 108 – 132 VAC.
• A power supply on the OSCD logic board may
have failed. Measure the DC voltage test points
on the OSCD logic board at TPC (+15V), TPD
(+10V), TPE (+5V), TPF (+7.5V) and TPG
(-15V) with respect to TPH (Ground). These
power supplies have a tolerance of +/- 5%. If the
measured voltage is not within the 5% tolerance
then the power supply has failed, and the OSCD
logic board should be replaced.
VSD - Logic Board Processor
Message: PWM COMMUNICATIONS FAULT
This shutdown is generated by the OSCD logic board.
If a communications problem occurs between the two
microprocessors on the OSCD logic board, then is
shutdown will occur.
Possible Problems:
• If this shutdown should occur, replace the OSCD
logic board.
VSD - Low Converter Heatsink Temperature
Message: LOW CONV HEATSINK TEMP.
This shutdown is generated by the OSCD logic board.
A thermistor sensor is located on the SCR/Diode block
side of the copper chill plate on the OSCD Power Unit.
If at anytime this thermistor detects a temperature of
37°F (3°C) or lower a shutdown will occur.
Possible Problems:
• In most cases, the problem will actually be an
open thermistor or broken wiring to the thermistor. Remove the J2 connector from the OSCD
logic board. With a DVM measure the resistance
of the thermistor.
DO NOT insert the probes of the meter
into the J2 connector where it makes a
connection with the OSCD logic board.
This will cause the sockets in the J2
connector to spread apart and cause an
intermittent connection. Instead insert the
probes into the back of the J2 connector.
Refer to Table 2 below for thermistor resistance verses
temperature values.
• Also, make certain one side of the circuit is not
shorted to the cabinet. Sometimes a thermistor
wire can be pinched against the enclosure.
TABLE 2 - OSCD - THERMISTOR CHARACTERISTICS
60
TEMP°F NOMINAL
TEMP°C NOMINAL
R-THERMISTOR
IN OHMS FOR CONVERTER*
R-THERMISTOR
IN OHMS FOR BASEPLATE
70
21
11900
4900
80
27
9300
4230
90
32
5600
3750
100
38
4600
3150
110
43
4660
2730
120
49
3760
2350
130
54
3050
1980
140
60
2490
1600
150
66
2040
1400
160
71
1690
1200
170
77
1400
950
180
82
1170
800
190
89
981
700
200
93
50
625
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
VSD - Low DC Bus Voltage
VSD - Phase A (B, C) Gate Driver
Message: LOW DC BUS VOLTAGE FLT
Message: PHASE A (B,C) GATE DRIVER FLT
The OSCD logic board determines this shutdown
with information from the bus isolator board. If the
line voltage were to quickly drop the current seen by
the motor could exceed its rating. The low bus voltage shutdown will prevent this from happening. The
shutdown is generated when the DC link voltage drops
below 500 VDC for 460 VAC input voltage, 414 VDC
for 400 VAC input voltage, or 600 VDC for 575 VAC
input voltage when the drive is running.
A second level of overcurrent current protection exists
on the OSCD gate driver board. The collector-to-emitter voltage of each IGBT is checked while the device
is turned on. This is also called the collector-to-emitter
saturation voltage. If the voltage across the IGBT is
greater than a set threshold as defined on the gate driver board, the IGBT is turned off and a shutdown pulse
is sent to the OSCD logic board shutting down the entire OSCD system. This fault can also be caused if an
IGBT is not being turned on when it should.
Possible Problems:
• A common cause for this shutdown is a severe sag
in the AC line to the drive. Monitor the incoming three phase AC line for severe sags, and also
monitor the DC link voltage with a digital meter.
• There could be a wiring problem between the DC
link, bus isolator board, or the OSCD logic board.
Refer to the wire diagram for the wire numbers.
Measure the voltage at J3 on the OSCD logic board.
• The input voltage to the SCR trigger board must be
properly phased with the SCR gate wiring. If the
wiring is not correct, then misiring of the SCR will
result and may cause the circuit breaker to trip.
• Verify that the SCR/Diode assembly is not open.
Care must be taken when making this
measurement. The value should be
around 600 VDC when the drive is running.
VSD - Low Inverter Baseplate Temperature
Message: LOW INVERTER BASEPLATE
TEMPERATURE FLT.
This shutdown is generated by the OSCD logic board.
A thermistor sensor is located inside the IGBT Module,
or Modules on the OSCD power unit. Temperature information is sent from the thermistor to the IGBT gate
driver board, and then to the OSCD logic board. If at
anytime this thermistor detects a temperature of 37°F
(3°C) or lower a shutdown will occur.
Possible Problems:
• Refer to problems listed for the VSD – Low
Converter Heatsink Temperature shutdown. The
thermistor chart will not be the same for this
thermistor.
JOHNSON CONTROLS
Possible Problems:
• A power supply problem on the gate driver board.
Verify that the 6 LED’s on the gate driver board
are lit on the 292/351/424 Hp OSCD. Verify that
the 2 LED’s on each gate driver board are lit on
the 419/503/608 Hp OSCD. The gate drive board
is located on top of the IGBT module. If any one
of the LED’s are not lit, then the bad gate driver
board has failed and requires replacement of the
OSCD power module.
• The power supplies for the gate driver boards are
generated on the SCR trigger board. Verify the
wiring between the SCR trigger board and the
IGBT gate driver boards. To ensure that power
supplies are good measure the voltage from TPF
and TPG to ground. The voltage should be around
12.5 VDC. Also ensure that the voltage on J7 between pins 5 and 6, and pins 7 and 8 is 5 VDC.
• A failure may have occurred in the OSCD logic
board. If the problem repeatedly occurs in one
phase, swap all three gate driver board cables at
the OSCD logic board J8, J9, and J10. Plug J8 into
J9, J9 into J10, and J10 into J8. If the display now
reports a trip in a different phase, the problem is
not in the OSCD logic board. The cables must be
returned to their proper location for proper KW
reading to occur.
• The fault could also be cause by a problem in the
drive line. Ensure that the compressor is free to
rotate. Also ensure that the motor is not grounded
phase to ground or phase to phase.
• Too much refrigerant in the chiller causing carry
over.
• Refrigerant level sensor or system not working
properly.
61
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
VSD - Precharge - DC Bus Voltage Imbalance
Message: PRECHARGE BUS V IMBALANCE
The definition for this fault is identical to “ VSD - DC
Bus Voltage Imbalance”, except that the fault has occurred during the precharge period, which begins during pre-lube. Refer to “ VSD - DC Bus Voltage Imbalance” shutdown for possible problems.
VSD - Precharge - Low DC Bus Voltage
Message: PRECHARGE LOW VOLTAGE FAULT
The OSCD logic board determines this shutdown with
information from the bus isolator board. This fault has
two different timing events. First, the DC Bus voltage
must be equal to or greater than 50 VDC for 460 VAC
input voltage, 41 VDC for 400 VAC input voltage, and
60 VDC for 575 VAC input voltage 4 seconds after precharge has begun. Second, the DC Bus voltage must be
equal to or greater than 500 VDC for for 460 VAC input voltage, 414 VDC for 400 VAC input voltage, and
600 VDC for 575 VAC input voltage 20 seconds after
pre-charge has begun. This shutdown is important to
determine if the converter or the cap. bank is shorted.
Possible Problems:
• Shorted cap. bank. Place a DC volt meter across
the laminated bus structure. Measure the voltage.
If voltage is present, then the caps. are not shorted.
If voltage is not present, then take an ohm meter
and verify if the cap. bank is shorted or not.
• The OSCD logic board is not getting bus voltage
information. Place a DC volt meter at J3 on the
OSCD logic board pins 1 and 3. Start the drive.
If the voltage does not come up, then verify the
wiring between the bus voltage isolation board,
OSCD logic board, and the laminated bus structure.
• The converter is not being told to turn on. Verify
that J4 on the SCR trigger board is properly installed. Verify that J6 on the OSCD logic board
is properly installed. Measure the DC voltage at
J4 on the SCR trigger board pin 3 to ground. The
voltage should go to 0 VDC when the drive enters precharge. If this does not happen, then verify
the wiring between the SCR trigger board and the
OSCD logic board.
62
• The converter is not turning on. Verify the wiring between the SCR trigger board and the SCR
gates. Also verify the wiring between L1-L3 on
the SCR trigger board and L1-L3 to the input of
the drive at the circuit breaker and up to the SCR
anode connection.
• Measure the DC voltage at J1-J3 on the SCR trigger board. The voltage should be 1-3 VDC when
the drive enters precharge. If the voltage is around
15 VDC, then the SCR trigger board has failed or
the SCR gate is open. If the voltage is 0 VDC, the
SCR trigger board had failed or the SCR gate is
shorted.
VSD - Run Signal
Message: RUN RELAY FAULT
Two run signals are generated by the Control Center,
one via wire #24 and the second via the serial communications. Upon receipt of either of the two run signals
by the OSCD logic board, a 5-second timer will begin
on the OSCD logic board. If the missing run signal is
not received within the 5-second window the OSCD
logic board will shut down, and the Control Center will
display the shutdown message.
Possible Problems:
• This shutdown could occur if there is a problem
with the wiring between the Control Center and
the OSCD logic board. Check the #24 to #25
horseshoe jumper in the Control Center, and all
other wiring involved in energizing #24 in the
OSCD.
• Verify that the serial communications wiring between the micro board, the ACC board, and OSCD
logic board are connected properly.
• Verify the control center microboard communications is working properly. Refer to reference material for more information.
VSD - Serial Communications
Message: SERIAL RECEIVE FAULT
The OSCD logic board generates this message. When
the communications between the micro board and the
ACC board, or the ACC board and OSCD logic board
is disrupted for a least 22 seconds.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Possible Problems:
• Ensure that the chiller system is properly grounded for electrical noise. The OSCD is the source of
ground for the chiller. Ground is then conducted
to the rest of the chiller by the mounting connections of the drive, compressor motor, and the Control Center. All connections are to be made with
external tooth lock washers. These washers will
cut through the paint on the chiller and provide a
ground connection. The grounding system is critical for proper communications.
• Check the shielded cable between J11 on the
OSCD logic board and J8 on the ACC board.
Check for continuity and also check to see that
none of the conductors are shorted together or
shorted to ground. The terminal block in the
lower left corner of the OSCD cabinet serves as
a junction point for this cable, and it is possible
for strands of wire to bridge across the terminals
at this location.
• Verify that the shielded cable is properly grounded. Ensure that the chiller and the Control Center are properly ground through the OSCD. The
shield should not be connected to chassis ground
at the mounting plate for the conduit. The shield
should only have one connection the Control Center enclosure. Remove the shield from the ground
and verify that no other ground connections exist
with an ohm meter. The shield should not go to
ground through the ACC board. This has been a
common problem on ield retroits. (If the optional harmonic ilter is installed, then repeat this and
the above step for the cable connected between
the J9 connector on the ACC board and J8 connector on the ilter logic board.)
• Ensure that the ACC board is properly grounded.
In some cases, the ACC board is grounded through
a very long wire. Changes were made to directly
ground the ACC board to the Control Center enclosure. J6 pin 1 is the ground connection for the
ACC board. This pin should be connected to the
Control Center enclosure right next to the ACC
board.
• Ensure that newer software is installed in the ACC
board. Communications were improved with software version C.ACC.01.03a and later.
JOHNSON CONTROLS
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
• Improper connection of the J9 connector on the
ACC board. The J9 connector on the ACC board
is for the communications from the harmonic ilter
logic board. If the harmonic ilter is not installed,
then the cable connected to J9 can be a source of
electrical noise. The J9 connected should be removed from the ACC board if the optional harmonic ilter is not installed.
• If the harmonic ilter is installed, then the fault can
be generated when the communications between
the OSCD logic board and the harmonic ilter
logic board, or the harmonic ilter logic board and
the ACC board is disrupted. If possible disconnect
the harmonic ilter logic board to determine if it
is at fault. If the communications work properly
with the harmonic ilter logic board disconnected,
then verify the software version. If the software
version is correct, then replace the board.
• If all of this has been done and communications
can never be established, even at power-up, you
may have a bad communications driver on either
the OSCD logic or the ACC boards. Change out
both the ACC and OSCD logic boards.
VSD - Single Phase Input Power
Message: SINGLE PHASE POWER SUPPLY
This shutdown is generated by the SCR Trigger board
and relayed to the OSCD logic board to initiate a system shutdown. The single phase control uses circuitry
to detect if any one phase has dropped below 230 VAC
for a 460 VAC 60 Hz or 400 VAC 50 Hz line, or 300
VAC on a 575 VAC 60 Hz line. The trigger board will
detect the loss of a phase within one half line cycle of
the phase loss. An LED on the SCR Trigger board will
indicate that the board is detecting the fault, and not a
wiring problem between the SCR trigger board and the
OSCD logic board.
Possible Problems:
• This message is typically displayed every time
power to the OSCD is restored or if the input
power dips to a very low level. This is not an indication of a problem with the OSCD.
• Verify the input fuses to the SCR trigger board are
not open. The fuses that supply power to the SCR
trigger board also supply power to the oil pump
motor and the oil heater. A failed fuse may indicate a failure in one of these other components.
63
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
• Verify continuity between the J4 connector on
the SCR trigger board and the J6 connector on
the OSCD logic board. A failure in the wiring can
cause this shutdown.
VSD - Stop Contacts Open
Message: INVERTER INITIATED STOP FAULT
Whenever the OSCD initiates a fault, it first opens the
K1 relay on the OSCD logic board. When the relay
opens the voltage between wire #53 and #16 will be
115 VAC. It then sends a message through the serial
port to the ACC board, detailing the cause of the fault.
If wire #53 to #16 circuit ever opens without receiving an accompanying cause for the trip over the serial
link (within 11 communication tries, approximately 22
seconds) this message will be displayed. This message
will also be displayed if the verification jumper on J1
pins 7 and 8 are loose or not connected to the OSCD
logic board. This fault maybe replaced with a Serial
Communications fault if the serial link has failed.
Possible Problems:
• Ensure that all wiring from wire #1 to #53 horseshoe jumper in the Control Center and all other
wiring involving #53 and #16 are properly connected.
• Ensure that 115 VAC is available to wire #53 at
the J1 connector.
• Verify that the J1 connector on the OSCD logic
board is properly installed. Also ensure that the
J1 pin 7 and 8 jumper is installed and the pins are
properly seated.
• Ensure that the control panel input/output board is
working properly.
Harmonic Filter - 110 % Input Current
Overload
Message: FLTR OVERLOAD FLT
This shutdown is generated by the harmonic filter logic
board. The three phases of filter current are measured
by the output DCCTs’,and information is sent to the
harmonic filter logic board. If any one phase of filter
current exceeds a threshold for 40 seconds a shutdown
will occur. Refer to the following table for the shutdown threshold value.
Possible Problems:
• Verify that the values of Total Harmonic Distortion (THD) are low and balanced. Turn off the
OSCD and monitor the THD for each phase. The
value should be around 5%. If the value of THD
is much higher or if it is not balanced, then the
harmonic content of the line is too high and the
harmonic ilter is responding to it.
• Ensure that the values of Total Demand Distortion (TDD) are balanced. If the currents are not
balanced, then there may be a problem in the harmonic ilter power unit or the harmonic ilter logic
board. Verify the wiring between the harmonic ilter logic board and the harmonic ilter power unit.
Harmonic Filter - DC Bus Voltage Imbalance
Message: FLTR BUS V IMBALANCE FLT
The DC bus voltage isolation board provides a high
resistance between the harmonic filter DC link and
the harmonic filter logic board. This resistance limits
the current flowing between the bus capacitors and the
Harmonic filter logic board. The harmonic filter logic
board then determines if this fault has occurred.
The filter DC link is filtered by large, electrolytic capacitors, which are rated for 450 VDC. These capacitors are wired in series to achieve a 900 VDC capability
for the DC link. The 424 and 608 Hp drives use higher
voltage rated capacitors, but 2 in series are still required. It is important that the voltage be shared equally across each capacitor, or the capacitor rating may be
exceeded and possibly fail. The DC isolation board is
connected to the plus bus, minus bus, and where the
2 series capacitors are connected to each other. The
harmonic filter logic board then measures the voltage
between the plus bus and the series connection, and the
minus bus and the series connection of the bus capacitors. If at anytime while the harmonic filter is running
these 2 measurements become unequal by 50 VDC (for
460 and 400 VAC input voltage) 65 VDC (for 575 VAC
input voltage), then a shutdown will occur.
DRIVE HP RATING THRESHOLD SHUTDOWN VALUE
270/292/351/424
128 amps RMS
388/419/503/608
176 amps RMS
64
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Possible Problems:
• Bleeder resistors failure due to overheating. Ensure that thermal grease is properly applied when
the resistors are replaced. With power removed
from the drive and the DC link voltage discharged
below 10 VDC, disconnect the harmonic ilter
bleeder resistors. Measure the ohm value of the
bleeder resistors. The ohm value should be 3000
ohms within 5%. Drives built after 5/05 no longer
use thermal grease, but use a thermal pad. Ensure
that the resistors are properly tightened to the assembly. No torque speciication is required.
• Verify all wiring between the DC link and the harmonic ilter logic board. Also check for loose connections.
• Failure of the bus voltage isolation board. With
power removed from the drive and the DC link
voltage discharged below 10 VDC, disconnected
the bus voltage isolation board from the circuit.
Using an ohm meter measure from J1-1 to J2-1.
The ohm value should be 150 K ohms. Repeat this
test for the remaining 2 connections. If any one of
the reading is not 150 K ohms to within 1%, then
the board needs to be replaced.
• Shorted capacitor in one half of the DC link. Place
one DC volt meter from the plus bus to the series
connection of the capacitors, the other from the
series connection of the capacitors to the minus
bus. Start the drive. When the drive starts to rotate the motor the harmonic ilter will start to precharge. The precharge of the harmonic ilter takes
5 seconds. During this time, the voltage should
remain equal to within the speciication above. If
a capacitor is shorted, then one of the volt meters
will have a low voltage reading. This is the side of
the DC link that has failed. Remove power from
the drive, and ensure that the DC link voltage is
below 10 VDC. Remove the laminated bus structure from the harmonic ilter power unit. With an
ohm meter measure the resistance of the DC link
capacitors. A low reading would indicate a failed
capacitor. Replace the cap. When replacing the
capacitor ensure that the top of the capacitor is at
the same height as the other capacitors in the DC
link.
JOHNSON CONTROLS
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
• An open capacitor can cause this problem as well.
Using an analog meter on Rx10. Connect the meter to one side of the capacitor bank. The meter
should irst read a short and then the resistance
should increase. The same test with the same results should be repeated for both side of the capacitor bank in both polarities. If the needle of the
meter shows a resistance without irst showing a
short, then repeat the test. If the reading does not
change then the capacitor is open and should be
replaced.
• Failure of the harmonic ilter logic board. Measure
the voltage of the DC link at the harmonic ilter
logic board. This measurement is taken at J5 pins
5 and 6, J5 pins 6 and 7. During the precharge of
the harmonic ilter these 2 measurements should
remain equal to within the speciication above. If
the measurements are correct, then the harmonic
ilter logic board has failed.
Harmonic Filter - DC Current Transformer
1( or 2)
Message: FILTER DCCT 1 (OR 2) ERROR
During initialization, with no current flowing through
the Direct Current Current Transductors (DCCT’s), the
DCCT’s output voltages are measured and compared
with a preset limit in the harmonic filter logic board.
If the measured values exceed the preset limits, the
DCCT’s are presumed to be bad and this shutdown will
be generated.
Possible Problems:
• Verify the wiring between the DCCT’s and the
harmonic ilter logic board.
• Power supply failure to the DCCT. Check for the
presence of the +15 VDC power supplies by measuring the voltages at ilter logic board J3 pins 6
and 10 with respect to signal ground (J3 pin 2).
Check for the presence of the -15 VDC power
supplies by measuring the voltages at ilter logic board J3 pins 7 and 11 with respect to signal
ground (J3 pin 2). If the power supply is not correct, then replace the harmonic ilter logic board.
• The output voltage from the DCCT is not correct. While the OSCD is powered but not running, measure the DC voltage from J3 pin 5 and
J3 pin 12 with respect to signal ground (J3 pin 2)
on the harmonic ilter logic board. Neither voltage should be greater than +/- 0.147 VDC. If the
above step is correct, and this step fails, then replace the failed DCCT.
65
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
Harmonic Filter - High DC Bus Voltage
Message: FLTR BUS OVER-VOLTAGE FLT
The harmonic filter logic board continuously monitors
the harmonic filter DC link voltage if the level of the
DC link voltage exceeds a range of 822 to 900 VDC
(for 460 and 400 VAC input voltage) 999 to 1099 VDC
(for 575 VAC input voltage), this shutdown is initiated.
Keep in mind that the harmonic filter has its own DC
bus as part of the harmonic filter power unit. The harmonic filter DC Link is not connected in any way with
the drive’s DC Link.
Possible Problems:
• Verify that the line voltage is not greater then the
speciied input voltage range for this model of
drive.
• Voltage surge on the input line voltage. Ensure
that power quality has not changed during the
shutdown. This could include storms, line switching, or rapid changes in line loading.
Harmonic Filter - High Phase A (B, C) Current
Message: FLTR PHASE A (B,C) OVERCURRENT
The output current of the harmonic filter is read by
the Direct Current-Current Transducer (DCCT). This
current information is sent to the harmonic filter logic board where it is compared against a threshold. If
the output current of the harmonic filter power unit is
greater than the threshold, then the harmonic filter will
turn off for 5-6 line cycles. After that time the filter operation will resume. If the harmonic filter operation is
stopped 3 times within a period of 60 line cycles, then
the filter and OSCD power units are shut down and this
message is generated.
DRIVE HP RATING THRESHOLD SHUTDOWN VALUE
270/292/351/424
378 ±59 amps Pk
385/419/503/608
523 ±84 Amps Pk
Possible Problems:
• Line voltage transients. If the OSCD shutdown
and auto-restarts without any additional problems,
then the problem is likely due to a sag or surge in
the line voltage.
• Filter power unit failure. In some cases, the IGBT
in the harmonic ilter power unit has failed. Refer to troubleshooting procedure for failure of the
Harmonic Filter Module to determine this failure.
66
Harmonic Filter - Logic Board Or
Communications
Message: IEEE-519 FILTER FAULT
This shutdown states that the hardware on the harmonic filter logic board is indicating a fault, but the software on the harmonic filter logic board does not state
why. The filter logic board signals a fault condition by
opening a transistor. The OSCD logic board detects the
open transistor at the J7 connector pin 9. In turn, the
OSCD logic board then opens it’s fault relay to indicate a fault to the Control Center. When fault data is
requested of the harmonic filter logic board it does not
respond with fault information.
Possible Problems:
• Verify the 16-pin ribbon cable for continuity between the OSCD logic and Harmonic Filter logic
boards. Focus on this test around pin 9 of the cable.
• Ensure that the communication system is working between the Harmonic Filter logic board, the
Adaptive Capacity Control board, and the OSCD
logic board.
Harmonic Filter - Logic Board Power Supply
Message: FLTR POWER SUPPLY FLT
This shutdown indicates that one of the low voltage
power supplies on the harmonic filter logic board have
dropped below their permissible operating voltage
range. The filter logic board receives its power from
the OSCD logic board via the ribbon cable, which connects the two. The power supplies for the OSCD logic
boards are in turn derived from the secondary of the
120 to 24 VAC transformer (Figure 3 on page 14),
which in turn is derived from the AC line input to 120
VAC control transformer (Figure 1 on page 10).
Possible Problems:
• Verify that CR10 LED is lit on the harmonic ilter logic board. This LED indicates that the power
supplies on the board are ok. If the CR10 LED is
lit, then likely the harmonic ilter logic board has
failed, and it needs to be replaced.
• If CR10 LED is not lit, then verify the ribbon cable for continuity between the OSCD logic and
Harmonic Filter logic boards.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
• Verify the power supply voltages on the harmonic
ilter board. With a voltage meter verify the following voltages.
J7 pin 3-7 is +15 VDC
J7 pin 4-7 is +5 VDAC
J7 pin 5-7 is -5 VDC
J7 pin 6-7 is -15 VDC
Harmonic Filter - Low DC Bus Voltage
Message: FLTR LOW BUS VOLTAGE FLT
The harmonic filter dynamically generates its own filter DC link voltage by the interaction of the harmonic
filter choke and switching its IGBT’s. This DC level is
actually higher than the level obtained by simply rectifying the input line voltage. Note: The DC link voltage is always higher on the harmonic filter power
unit than on the OSCD VSD power unit. Thus the
harmonic filter actually performs a voltage “boost”
function. This is necessary in order to permit current to
flow into the AC line from the harmonic filter when the
AC line is at its peak level. This particular shutdown
and its accompanying message are generated when the
harmonic filter’s DC link voltage drops to a level less
than 80 VDC (for 460 and 400 VAC input voltage) 100
VDC (for 575 VAC input voltage), below the harmonic
filter DC link voltage setpoint. The harmonic filter DC
link voltage setpoint is determined by the harmonic
filter logic board by measuring the three phase input
line-toline voltage. The harmonic filter logic board
measures the input line voltage through the AC line
isolator board. This setpoint is set to the peak of the
sensed input line to line voltage plus 59 volts(for 460
and 400 VAC input voltage) 118 VDC (for the 608 Hp
drive) and 88 volts (for the 424 Hp drive), but not to
exceed 760 volts (for 460 and 400 VAC input voltage)
993 VDC (for 575 VAC input voltage). The setpoint
will vary with changes in the input line to line voltage.
Possible Problems:
• If this shutdown occurs occasionally, the likely
cause is a severe sag in the input line voltage. A
power monitor should be installed to determine if
a power problem exists.
JOHNSON CONTROLS
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
• Verify the operation of the AC line voltage isolator board. Measure the output of the line voltage
isolation board at connector J5, pins 1, 2, and 3
on the harmonic ilter logic board. With 480 VAC
present on the input to the line voltage isolation
board, approximately 5.2 VAC should be present
from pins 1 to 2, pins 2 to 3, and pins 3 to 1. The
voltages should be balanced as opposed to the
voltage being exactly 5.2 VAC.
3
Harmonic Filter - Phase Locked Loop
Message: FLTR PHASE LOCK LOOP FLT
This shutdown indicates that a circuit called a “phase
locked loop” on the harmonic filter logic board has lost
synchronization with the incoming power line for a period of time.
Possible Problems:
• This is normally an indication that one of the harmonic ilter’s input power fuse is open. Check the
operation of the harmonic ilter power fuses 8FU,
9FU and 10FU.
• If the fuses are OK, then measure the output of the
line voltage isolation board at connector J5, pins
1, 2, and 3 on the harmonic ilter logic board. With
480 VAC present on the input to the line voltage
isolation board, approximately 5.2 VAC should be
present from pins 1 to 2, pins 2 to 3, and pins 3 to
1. The voltages should be balanced as opposed to
the voltage being exactly 5.2 VAC.
Harmonic Filter - Precharge - Low DC Bus
Voltage
Message: FLTR PCHARGE LOW BUS V FLT
This shutdown requires that two minimum voltage
thresholds must be exceeded in order to complete precharge. The first minimum voltage value occurs with in
1/10 of a second. The second minimum voltage value
occurs near the end of the precharge at 5 seconds after
the filter precharge relay is energized. View chart below for specific values. The unit is shut down, and this
message is generated if these conditions are not met.
NOMINAL
INPUT
VOLTAGE
VALUE
FIRST
MINIMUM
VOLTAGE
VALUE
SECOND
MINIMUM
VOLTAGE
VALUE
400-460 VAC
41 VDC
425 VDC
575 VAC
60 VDC
630 VDC
67
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
Harmonic Filter - Run Signal
Possible Problems:
• Verify that the harmonic ilter pre-charge relay
is energized during pre-charge. If it is not, then
verify wiring between the pre-charge relay and J4
pins 1 and 2 on the harmonic ilter logic board.
• Verify that the harmonic ilter pre-charge resistors
are the correct ohm value, and are not damaged.
DRIVE HP RATING
PRE-CHARGE RESISTOR VALUE
270/292/351/424
10 ohms
385/419/503/608
16 ohms
• Measure the harmonic ilter bus voltage during
pre-charge to ensure that the bus is charging to
the correct value or not. If bus is charging properly, then measure the bus voltage at J5 pin 5 to 7.
The value at J5 should be nearly the same as the
bus voltage measured on the bus. If the measurement is not the same, then measure the 3 resistors
on the DC bus isolator board. Disconnect the DC
bus isolator board and measure resistance at the
terminals of the board. The measurement should
be 150K ohms +/- 1%. If this measurement is not
correct, then replace the DC bus isolator board. If
the measurement is correct, then replace the harmonic ilter logic board.
68
Message: FLTR RUN RELAY FLT
When a digital run command is received at the harmonic filter logic board from the OSCD logic board
via the 16 position ribbon cable, a 1/10 second timer is
begun. A redundant run command must also occur on
the serial data link from the OSCD logic board via the
ribbon cable before the timer expires or the OSCD will
be shut down and this message will be displayed.
Possible Problems:
• Verify the 16-pin ribbon cable for continuity between the OSCD logic and Harmonic Filter logic
boards. Focus on this test around pin 12 of the
cable.
• If the problem persists, replace the OSCD logic
board and if the problem remains, the ilter logic
board.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
WARNING MESSAGES
General Information
A WARNING message will indicate that the operation
of the OptiSpeed Compressor Drive or the Harmonic
Filter is affected in some manner, but the OptiSpeed
Compressor Drive is still functioning.
Warning - Vanes Uncalibrated - Fixed Speed
Message: VANES UNCALIBRATED – FIXED SPEED
This message is displayed when the Pre-Rotation Vanes
are not calibrated or have failed to calibrate, and the
OptiSpeed Compressor Drive is enabled. Under this
condition the OSCD will run at a constant maximum
frequency. This message will no longer appear after a
successful calibration.
Possible Problems:
• Ensure that the vane pot. is adjusted for zero vane
opening. With the vanes fully closed, the DC voltage measured at J4 on the Adaptive Capacity Control board pin 1 to 2 should be 0.3 to 0.7 VDC. If
this value is not correct, then adjust the vane pot.
coupling.
• Verify the communications between the Adaptive
Capacity Control, OptiSpeed Compressor logic,
chiller Control Logic, and the Harmonic Filter
logic boards.
• Ensure that the harmonic ilter logic board is not
in a reset condition. This is where the fault LED is
lashing on the harmonic ilter logic board. Verify
that the correct EPROM versions are installed,
and that the EPROM’s are installed in the proper
orientation. Ensure that the (2) 8 pin chips are
properly installed as well. Many times the 8 pin
chips are missed during a board replacement.
SECTION 3 - VSD ADAPTIVE CAPACITY CONTROL
Warning - Harmonic Filter - Operation
Inhibited
Message: FILTER - OPERATION INHIBITED
This message is displayed when the function of the
Harmonic Filter is inhibited at the Control Center. This
message is no longer displayed when the function of
the Harmonic Filter is enabled at the Control Center.
The function of the harmonic filter can only be inhibited or turned on when the chiller is stopped.
Warning - Harmonic Filter - Data Loss
Message: FILTER DATA LOSS
This message is displayed when the communications
link between the OSCD logic, and the harmonic filter
logic, or the ACC boards are interrupted for at least
a period of 20 seconds. This message can also occur
as a background message when the chiller is running.
When this message is displayed all filter related values
are replaced with X’s. If communications is re-established, the message will disappear, and normal values
will again be displayed.
Possible Problems:
• Verify the 16-pin ribbon cable for continuity between the OSCD logic and Harmonic Filter logic
boards. Focus this test around pin 9 of the cable.
• The integrity of the shielded communications cable between the harmonic ilter logic board and
the ACC board should also be checked.
• Ensure that the OSCD and the Control Center are
properly grounded.
• Possibly a board failure has occurred. Replace the
harmonic ilter logic board.
• Verify that the correct line number harmonic ilter logic board is installed. Different line number
boards are used for different horsepower OSCD.
JOHNSON CONTROLS
69
3
FORM 160.00-M4
ISSUE DATE: 1/21/2013
THIS PAGE INTENTIONALLY LEFT BLANK.
70
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 4 - START-UP PREPARATIONS
Circuit Breaker Setup
The circuit breaker used on the OSCD has many settings for overload, short circuit, and ground fault protection. Generally, these setting are adjusted by the
manufacture, but these setting should be verified before
starting the chiller. The breaker settings on the 292/351
Hp OSCD are a little different then the 419/503 Hp
OSCD. The 292/351 Hp OSCD have settings for Instantaneous Short Circuit Trip Time and Ground Fault
Trip Time have an ON and OFF adjustment. Verify that
these two adjustments are set to the ON position. With
the introduction of the 424 and 608 Hp drives new circuit breakers are being used.
TABLE 3 - CIRCUIT BREAKER SETTINGS
SETTINGS FOR THE 292/351 HP OSCD CIRCUIT BREAKER PART NUMBER 224-30987-000 (USED BEFORE 6/06)
ABBREVIATION OF
ADJUSTMENT
SETTING VALUE
Long Time Overload Protection Coarse Multiplier
“IO”
“1”
Long Time Overload Protection Fine Multiplier
“IR”
“1”
“ISD”
“1.5”
NAME OF ADJUSTMENT
Short Time Overload Protection Multiplier
Instantaneous Short Circuit Protection Multiplier
“II”
“2”
Ground Fault Protection Multiplier
“IG”
“0.2”
Short Time Overload Trip Time
Instantaneous Short Circuit Trip Time
Ground Fault Trip Time
“TR”
“0.5”
“TSD”
“0.1” ON
“TG”
“0.1” ON
4
SETTINGS FOR THE 270/292/351/424 HP OSCD CIRCUIT BREAKER PART NUMBER 224-35428-000
(USED AFTER 6/06)
ABBREVIATION OF
ADJUSTMENT
SETTING VALUE
Long Time Pickup
“IR”
“E”
Long Time Delay
“TLD”
“2”
Short Time Delay
NAME OF ADJUSTMENT
“ISD”
“2”
Ground Fault Pickup
“IG”
“0.2”
Ground Fault Delay
“TSD”
“J”
SETTINGS FOR THE 385/419/503/608 HP OSCD CIRCUIT BREAKER
NAME OF ADJUSTMENT
Short Delay Pickup
Short Delay Time
Ground Fault Pickup
Ground Fault Time
JOHNSON CONTROLS
SETTING VALUE
“2”
“inst”
“1”
“inst”
71
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 4 - START-UP PREPARATIONS
OptiView Control Center
Make certain the correct EPROMs are all installed in
the proper locations by referring to the EPROM Reference List in this form. The list at the end of this form
contains the earliest versions in which the product is
supported. Be sure the dimple in the end of the chip
is oriented in the correct direction. Ensure that jumper
JP37 is cut on the OptiView panel micro board 03101730-XXX.
Verify the circuit breaker settings (refer to the first
section in the start-up preparations). Apply power to
the OSCD, and check the System Status Line on the
Control Center. After a few seconds you should get
the message, “System Ready to Start”. If you do not,
turn off power, wait five minutes for the voltage to discharge, verify voltage is no longer present, and then
double check all wiring and connections.
At this point, start-up is as simple as one, two, three...
1. If initial power-up is successful, set the Full Load
Amps (FLA) on the OSCD by selecting the VSD
Details Screen. On this screen is displayed the
“Full Load Amps (some value)”. Adjust this value to the FLA stamped on the compressor motor
name plate by turning the small multi-turn trimpot
located in the left-center area of the OSCD logic board inside the OSCD enclosure. Clockwise
rotation of the trimpot will increase the value of
FLA. You will need to alternate between making an adjustment, and checking the value on the
Control Center, until the displayed value is correct
within one amp.
2. Next, drain the coolant from the OSCD. The
OSCD is now shipped with a 50/50 mix of Propylene Glycol and York Corrosion Inhibitor. This
type of coolant is being used to protect the cooling loop from damage due to freezing conditions
during the shipping process. This coolant mixture
does not have the thermodynamic properties required by the OSCD during a running condition.
Thus, this 50/50 mixture must be drained and
replaced with YORK Corrosion Inhibitor as currently used in the OSCD. Propylene Glycol is the
same material used to winterize recreational
vehicles. Although, it is non-toxic, follow any
applicable local codes when discarding the solution.
3. Next, ill the coolant loop using York’s Corrosion
Inhibitor, part number 013-02987-000. Pour the
72
solution into the top of the header pipe until the
level is within a ½ inch of the top. Then run the
pump by unplugging connector P2 on the OSCD
logic board. The level in the ill-pipe will drop
quickly. Add more coolant so the level is maintained at ½ inch from the top of the pipe. Continue
to run the pump for 15 minutes, adding more coolant as needed, then reinstall P2, make certain the
level is ½ inch from the top, and install the pipe
plug in the header pipe using telon tape to assure coolant does not evaporate through the pipe
threads. Do not wrap the threads with more than 2
wraps of Telon tape. Too much tape can cause the
ill pipe to crack. Note the pipe plug has straight
threads, and could fall into the reservoir.
4. The BRAM on the ACC board should be cleared
to ensure that the surge map is clean, and no data
is stored that may keep the OSCD from slowing
down. This procedure should not be performed on
a regular basis, and will cause extra surging of the
compressor.
• Enter an Access Code of 1380
• Select the Motor Screen
• Select the ACC Details Screen
• Press the Surge Map Clear key
• A window will appear prompting for a code.
Enter the value of 0368, and press the check
key.
• Open the OptiView Control Center door
and press the small SW1 button on the ACC
board. This must be preformed within 20
seconds of pressing the check key. Also the
small button must be pressed for 1-3 seconds.
• A message will appear that the surge map has
been cleared. To verify that the surge map is
cleared check that the vane position no longer reads 0 and now displays X.
5. The vanes must now be calibrated. The vane
pot itself was previously installed, and should
have been set so that neither end of travel runs
up against either end-stop of the pot. The closed
end of the pot should be set for a feedback voltage somewhere between 0.3 and 0.7 VDC, as
measured from the wiper (white wire) to common
(black wire). The full-open feedback voltage must
be greater than the closed value by 0.10 VDC.
For example, you might get a range of 0.54 VDC
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 4 - START-UP PREPARATIONS
closed, to 1.12 VDC at full open. This range of
voltage will be scaled by the Adaptive Capacity
Control Board (ACC) to a range of 0% to 100%
open. The ACC will store the voltage that corresponds with the percentage of vanes in it’s BRAM
chip.
Start”. If you do not, turn off power, wait five minutes
for the voltage to discharge, verify voltage is no longer
present, and then double check all wiring and connections.
This scaling is accomplished by an automatic calibrationroutine in the OptiView Control Center. To perform
theauto-calibration perform the following:
1. If initial power-up is successful, set the Full Load
Amps (FLA) on the OSCD by pressing the “Options” key. You will see a display of “VSD 100%
Job FLA = (some value) Amps”. Adjust this value
to the correct FLA as stamped on the motor name
plate by turning the small multi-turn trimpot located in the left-center area of the OSCD logic board
inside the OSCD enclosure. Clockwise rotation of
the trimpot will increase the value of FLA. You
will need to alternate between making an adjustment, and checking the value on the display, until
the displayed value is correct within one amp.
• Enter an Access Code of 1380
• Select the Compressor Screen
• Select the Pre Rotation Vane Calibrate Screen
• Press the Start Calibration key
• The Calibration in Progress and Pre Rotation Vane
Opening LEDs’ will light.
• The vanes will run to the full open position and
stop.
• After a short period of time, the Pre Rotation Vane
Closing LED will light.
• The vanes will run to the full closed position and
stop.
• A message will appear on the screen, “PRV Calibration was Successful”
• If “ PRV Calibration was Successful” is not displayed, then verify the operation of the vane arm,
vane pot, the cable between the vane pot and the
ACC board, and that the shield of the vane pot. is
connected to the OptiView Control Panel enclosure.
If any difficulty is encountered with these procedures,
refer to the other sections of this publication for solutions.
Micro Computer Control Center
Make certain the correct EPROMs are all installed in
the proper locations by referring to the EPROM Reference List in this Form. Be sure the dimple at the end of
the chip is oriented in the correct direction.
Verify the circuit breaker settings (refer to the first section in the start-up preparations). Apply power to the
OSCD, and check the front panel display. After a few
seconds you should get the message, “System Ready to
JOHNSON CONTROLS
At this point, start-up is as simple as one, two, three...
2. Next drain the coolant from the OSCD. The
OSCD is now shipped with a 50/50 mix of Propylene Glycol and York Corrosion Inhibitor. This
type of coolant is being used to protect the cooling loop from damage due to freezing conditions
during the shipping process. This coolant mixture
does not have the thermodynamic properties required by the OSCD during a running condition.
Thus, this 50/50 mixture must be drained and replaced with YORK coolant as currently used in
the OSCD. Propylene Glycol is the same material
used to winterize recreational vehicles. Although
it is non-toxic we suggest permission should be
obtained before discarding it into a sewer.
3. Next, ill the coolant loop using York’s pre-mixed
Corrosion Inhibitor solution, part number 01302987-000. Pour the solution into the top of the
header pipe until the level is within a ½ inch of
the top. Then run the pump by unplugging connector P2 on the OSCD logic board. The level in
the ill-pipe will drop quickly. Add more coolant
so the level is maintained at ½ inch from the top
of the pipe. Continue to run the pump for 15 minutes, adding more coolant as needed, then reinstall
P2, make certain the level is ½ inch from the top,
and install the pipe plug in the header pipe using
telon tape to assure coolant does not evaporate
through the pipe threads. Do not wrap the threads
with more than 2 wraps of Telon tape. To much
tape can cause the ill pipe to crack.
73
4
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 4 - START-UP PREPARATIONS
4. The BRAM on the ACC board should be cleared
to ensure that the surge map is clean, and no data
is stored that may cause the OSCD from slowing
down. This procedure should not be performed
on a regular basis, and will cause extra surging
of the compressor.
• Enter an Access Code of 1397
• Enter Program Mode
• Press the CHILLED LIQUID TEMPS key
under the DISPLAY section. The following
message shall appear:
Message: BRAM OPTION :
• Enter the number 368 (the value will be replaced
with stars on the display) then press the ENTER
key, the following message shall appear.
Message: BRAM OPTION IN PROGRESS . . .
• While the above message is present press and hold
SW1 push button on the ACC board for 3 seconds.
If the button is not pressed within 20 seconds the
option will be aborted. The switch is located at the
left center of the board. The following message
shall appear.
Message: BRAM OPTION COMPLETE
• To verify that the surge map is cleared check that
the vane position no longer reads 0 and now displays X.
5. The vanes must now be calibrated. The pot itself
was previously installed, and should have been set
so that neither end of travel runs up against either end-stop of the pot. The closed end of the pot
should be set for a feedback voltage somewhere
between 0.3 and 0.7 VDC, as measured from the
wiper (white wire) to common (black wire). The
full-open feedback voltage must be greater than
the closed value by 0.1 VDC. For example, you
might get a range of 0.54 VDC closed, to 1.12
VDC at full open. This range of voltage will be
scaled by the Adaptive Capacity Control Board
(ACC) to a range of 0% to 100%. The ACC will
store the voltage that corresponds with the percentage of vanes in it’s BRAM chip.
74
This scaling is accomplished by an automatic calibration routine in the Micro Computer Control Center. To
perform the auto-calibration preform the following:
• Enter an Access Code of 1380
• Change the operating mode of the Micro Computer Control Center to the VSD Service Mode
(not Service mode)
• Check to ensure that the Micro Computer Control
Center is in the Program Mode
• Press the Open key.
• A message will appear on the display, “Calibration in Progress - Vanes Opening”
• The vanes will run to the full open position and
stop.
• After a few seconds, a message will appear on the
display, “Calibration in Progress - Vanes Closing”
• The vanes will run to the full closed position and
stop.
• A message will appear on the display, “Calibration Successful”
• If so, press the Enter key to accept this calibration.
Calibration is not accepted unless the Enter key is
depressed.
If “Calibration Successful” is not achieved, then press
the cancel key to abort the procedure. Verify the operation of the vane arm, vane pot. the cable between the
vane pot and the ACC board, and that the shield of the
vane pot. is connected to the OptiView Control Panel
enclosure.
If any difficulty is encountered with these procedures,
refer to the other sections of this publication for solutions.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT
REPLACEMENT PROCEDURES
General Information
The following procedures are designed to guide the service technician along the path that leads to the identification of the cause for the problem. The service technician should understand the operation of the OptiSpeed
Compressor Drive and function of each major component. It is recommended that the service technician
read and understand the information contained in this
instruction prior to troubleshooting this product. Also,
the service technician must understand the system interface, and be able to utilize system wiring diagrams
to follow signal flow throughout the system. Due to the
integration of the OptiSpeed Compressor Drive with
the Graphic Control Center and Micro Computer Control Center, a good working knowledge of the Control
Center is also necessary (Ref. Forms listed at the beginning of this form ).
Several levels of documentation are required for the
troubleshooting process. The OptiSpeed Compressor
Drive wiring diagram, supplied with every OSCD is
the top level document. It provides the overall wiring
and configuration. Sections of this instruction provide
the required lower levels. Specifically, block diagrams
provide signal flow and simplified representations of
all board circuitry.
Begin the troubleshooting process by selecting the appropriate procedure. It is not necessary to sequentially
perform all of them. Perform a procedure only if there
is a problem with that function.
JOHNSON CONTROLS
Verify Failure of the OSCD Power Module
270/292/351/424 Hp Drive
General Information
This product contains voltages that could
cause injury! Before performing any of
these procedures, place the compressor
switch in the “stop” position. Wait 5
minutes. Ensure the DC bus voltage is
50 vdc or less on the display of the chiller
panel. Remove all ac power sources and
perform lockout tagout procedures. Use
a non-contact voltage sensor to ensure
no ac power is present in the enclosure.
Measure the DC bus voltage at J3 pins
1-3 on the LCD logic board using a DVM
to ensure the bus voltage is less than 50
VDC.
• Be certain the OSCD has been de-energized for
over ive minutes, and then double check for presence of voltage using a VOM. The DC bus must
be fully discharged.
• It is not necessary to remove any wiring to perform this test.
• This test will be conducted for an analog meter
and a digital meter. The analog meter must be adjusted to ohms on the Rx1 scale, and the meter
should be adjusted for a 0 ohm reading with the
probes connected together. The digital meter must
be adjusted for the diode check. In this test we are
not looking for an exact resistance measurements,
but rather to verify if the semi-conductor switches
are open or shorted.
75
5
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
0.38 VDC READING
ON DIGITAL METER
POSITIVE PROBE
ON NEGATIVE BUS
CONNECTION
NEGATIVE PROBE ON
OUTPUT WIRE 1T1
50016c
FIGURE 23 - 270/292/351/424 HP DRIVE IGBT MODULE VERIFICATION #1
Test Procedure
Place the positive probe of the meter on the first right
hand terminal of the IGBT module. This is the negative
bus connection. Place the negative probe of the meter
on the first left hand terminal of the IGBT module. The
wire should be marked 1T1. The analog meter reading
will be around 5-10 ohms. The digital meter reading
will be around 0.36 VDC. Refer to Figure 15.
76
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
ANALOG METER
READING FULL
SCALE
POSITIVE PROBE
ON POSITIVE BUS
CONNECTION
5
NEGATIVE PROBE
ON OUTPUT WIRE
1T1
FIGURE 24 - 270/292/351/424 HP DRIVE IGBT MODULE VERIFICATION #2.
Place the positive probe of the meter on the second
right hand terminal of the IGBT module. This is the
positive bus connection. The analog meter reading will
be near full scale to the left of the meter movement.
The digital meter reading will be OL. These 2 readings will take several seconds for the meter to reach
the suggested values. Refer to Figures 16 and Figure
25 on page 78.
JOHNSON CONTROLS
Place the positive probe of the meter on the 3rd right
hand terminal of the IGBT module. This is the negative
bus connection. Place the negative probe of the meter
on the 3rd left hand terminal of the IGBT module. The
wire should be marked 1T2. The analog meter reading
will be around 5-10 ohms. The digital meter reading
will be around 0.36 VDC.
77
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
DIGITAL METER
READING
OVERLOAD
POSITIVE PROBE
ON POSITIVE BUS
CONNECTION
NEGATIVE PROBE
ON OUTPUT WIRE
1T1
50018c
FIGURE 25 - 270/292/352/424 HP DRIVE IGBT MODULE VERIFICATION #3.
Place the positive probe of the meter on the 4th right
hand terminal of the IGBT module. This is the positive
bus connection. The analog meter reading will be near
full scale to the left of the meter movement. The digital
meter reading will be OL. These two readings will take
several seconds for the meter to reach the suggested
values.
Place the positive probe of the meter on the 6th right
hand terminal of the IGBT module. This is the positive
bus connection. The analog meter reading will be near
full scale to the left of the meter movement. The digital
meter reading will be OL. These two readings will take
several seconds for the meter to reach the suggested
values.
Place the positive probe of the meter on the 5th right
hand terminal of the IGBT module. This is the negative
bus connection. Place the negative probe of the meter
on the 5th left hand terminal of the IGBT module. The
wire should be marked 1T3. The analog meter reading
will be around 5-10 ohms. The digital meter reading
will be around 0.36 VDC.
Repeat the above 6 steps, but reverse the location of the
positive and negative probes of the meter. The readings
will also be reverse as in where the reading are OL or
full scale the readings will be 0.36 VDC or 5-10 ohms.
78
If any one of the readings is not correct, then the IGBT
module and gate driver board must be replaced.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
OVERLOAD
READING
POSITIVE
PROBE ON THE
POSITIVE BUS
CONNECTION
NEGATIVE
PROBE ON THE
OUTPUT WIRE
1T3
5
50019c
FIGURE 26 - 385/419/503/608 HP DRIVE IGBT MODULE VERIFICATION #1
Verify Failure of the OSCD Power Module
385/419/503/608 Hp Drive
General Information
Refer to information under verify failure of the OSCD
power module for general information.
Test Procedure
Place the positive probe of the meter on the first left
hand terminal of the IGBT module. This is the positive
bus connection. Place the negative probe of the meter on the large copper motor output connection of the
IGBT module. The wire should be marked 1T3. The
analog meter reading will be near full scale to the left
of the meter movement. The digital meter reading will
be OL. These 2 readings will take several seconds for
the meter to reach the suggested values. Refer to Figure 18.
JOHNSON CONTROLS
79
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
FORM 160.00-M4
ISSUE DATE: 1/21/2013
0.36 VDC READING
ON DIGITAL METER
POSITIVE PROBE
ON THE NEGATIVE
BUS CONNECTION
NEGATIVE PROBE
ON THE OUTPUT
WIRE 1T3
50050C
FIGURE 27 - 385/419/503/608 HP DRIVE IGBT MODULE VERIFICATION #2
Place the positive probe of the meter on the second left
hand terminal of the IGBT module. This is the negative bus connection. The analog meter reading will be
around 5-10 ohms. The digital meter reading will be
around 0.36 VDC. Refer to Figure 19.
Place the positive probe of the meter on the first left
hand terminal of the IGBT module. This is the positive
bus connection. Place the negative probe of the meter
on the large copper motor output connection large copper motor output connection of the IGBT module. The
wire should be marked 1T2. The analog meter reading
will be near full scale to the left of the meter movement. The digital meter reading will be OL. These
two readings will take several seconds for the meter to
reach the suggested values.
80
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
0.36 VDC READING
ON DIGITAL METER
POSITIVE PROBE ON
THE NEGATIVE BUS
CONNECTION
NEGATIVE PROBE
ON THE OUTPUT
WIRE 1T1
FIGURE 28 - 385/419/503/608 HP DRIVE IGBT MODULE VERIFICATION #3
Place the plus probe of the meter on the second left
hand terminal of the IGBT module. This is the negative bus connection. The analog meter reading will be
around 5-10 ohms. The digital meter reading will be
around 0.36 VDC.
Place the positive probe of the meter on the second left
hand terminal of the IGBT module. This is the negative bus connection. The analog meter reading will be
around 5-10 ohms. The digital meter reading will be
around 0.36 VDC. Refer to Figure 20.
Place the positive probe of the meter on the first left
hand terminal of the IGBT module. This is the positive
bus connection. Place the negative probe of the meter
on the large copper motor output connection large copper motor output connection of the IGBT module. The
wire should be marked 1T1. The analog meter reading
will be near full scale to the left of the meter movement. The digital meter reading will be OL. These 2
readings will take several seconds for the meter to
reach the suggested values.
Repeat the above steps, but reverse the location of the
positive and negative probes of the meter. The readings
will also be reverse as in where the reading are OL or
full scale the readings will be 0.36 VDC or 5-10 ohms.
JOHNSON CONTROLS
If any one of the readings is not correct, then the IGBT
module must be replaced.
81
5
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
Verify Failure of the Harmonic Filter Module
270/292/351/385/424 and 419/503/608Hp Drive
General Information
Refer to information under verify failure of the OSCD
power module for general information.
This test is the same for all horsepower drives. In the
270/292/351/424 Hp the harmonic filter power unit
is mounted at the bottom right of the drive. In the
385/419/503/608 Hp the harmonic filter power unit is
mounted at the center right of the drive. Refer to figures
under the section for the 270/351/292 Hp for details.
Test Procedure
• Place the positive probe of the meter on the irst
right hand terminal of the IGBT module. This is
the negative bus connection. Place the negative
probe of the meter on the irst left hand terminal
of the IGBT module. The wire should be marked
517. The analog meter reading will be around
5-10 ohms. The digital meter reading will be
around 0.36 VDC.
• Place the positive probe of the meter on the second right hand terminal of the IGBT module. This
is the positive bus connection. The analog meter
reading will be near full scale to the left of the
meter movement. The digital meter reading will
be OL. These 2 readings will take several seconds
for the meter to reach the suggested values.
• Place the positive probe of the meter on the 3rd
right hand terminal of the IGBT module. This is
the negative bus connection. Place the negative
probe of the meter on the 3rd left hand terminal
of the IGBT module. The wire should be marked
518. The analog meter reading will be around
5-10 ohms. The digital meter reading will be
around 0.36 VDC.
• Place the positive probe of the meter on the 4th
right hand terminal of the IGBT module. This is
the positive bus connection. The analog meter
reading will be near full scale to the left of the
meter movement. The digital meter reading will
be OL. These 2 readings will take several seconds
for the meter to reach the suggested values.
• Place the positive probe of the meter on the 5th
right hand terminal of the IGBT module. This is
the negative bus connection. Place the negative
probe of the meter on the 5th left hand terminal
of the IGBT module. The wire should be marked
82
FORM 160.00-M4
ISSUE DATE: 1/21/2013
519. The analog meter reading will be around
5-10 ohms. The digital meter reading will be
around 0.36 VDC.
• Place the positive probe of the meter on the 6th
right hand terminal of the IGBT module. This is
the positive bus connection. The analog meter
reading will be near full scale to the left of the
meter movement. The digital meter reading will
be OL. These 2 readings will take several seconds
for the meter to reach the suggested values.
• Repeat the above 6 steps, but reverse the location
of the positive and negative probes of the meter.
The readings will also be reverse as in where the
reading are OL or full scale the readings will be
0.36 VDC or 5-10 ohms.
• If any one of the readings is not correct, then the
IGBT module must be replaced.
Replacement of the OSCD Power Module
The following step by step procedure includes several
helpful hints which should make the process easier,
and minimize the possibility of damage to other components or to the OSCD.
Save all of the packing material. This material is to be
re-used when returning a defective power module as
required for warranty.
This product contains voltages that could
cause injury! Before performing any of
these procedures, place the compressor
switch in the “stop” position. Wait 5
minutes. Ensure the dc bus voltage is 50
vdc or less on the display of the chiller
panel. Remove all ac power sources and
perform lockout tagout procedures. Use
a non-contact voltage sensor to ensure
no ac power is present in the enclosure.
Measure the dc bus voltage at j3 pins 1-3
on the lcd logic board using a dvm to
ensure the bus voltage is less than 50 vdc.
• Be certain the OSCD has been de-energized for
over ive minutes, and then double check for presence of voltage using a VOM. The DC bus must
be fully discharged.
• 270/292/351/424 Hp Drive Only: Drain the coolant from the heat exchanger into a suitable container and discard.
• Remove the connector on the IGBT Gate Driver
Board.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
• Remove and discard the 6 Phillips head screws
from the power wire connector tang or tangs, and
the remaining 6 Phillips head screws from the bus
connections.
• 385/419/503/608 Hp Drive Only: Apply a thin
coat of thermal grease on to the back side of the
IGBT module. The thermal grease should be provided in the service kit.
• Remove the bolt holding the power wire to the
output of the IGBT.
• 385/419/503/608 Hp Drive Only: Place the new
OSCD power module on the chill plate so that the
connector is towards the right of the OSCD enclosure. Carefully slide the OSCD power module
power connections under the bus structure. The
replacement assembly should still be loose.
• Remove and discard the 8 Allen screws from the
IGBT module.
• 270/292/351/424 Hp Drive Only: Carefully remove the OSCD power module by sliding it away
from the bus structure while lifting slightly. DO
NOT place any stress on the bus structure. The
bottom of the IGBT module will be wet. Ensure
that the coolant does not drip onto any other components inside of the OSCD enclosure. This coolant is conductive, and as little as one drop falling on the Harmonic Filter gate driver board can
cause it to fail!
• 270/292/351/424 Hp Drive Only: Remove the
3 O-rings from the copper chill plate and discard
them.
• Insert the 8 Allen head screws through the new
IGBT module and engage a few threads in the
chill plate, but DO NOT tighten. The new OSCD
power module should still be loose.
• Align the OSCD power module so that 6 of the
Phillips head screws can be installed through
the bus structure and into the IGBT module. DO
NOT tighten these screws.
• Tighten the Allen head screws to 48 in.-lbs. (5.5
Nm) ± 10% in the sequence shown in Figure 21.
• 270/292/351/424 Hp Drive Only: Wipe the chill
plate clean with a clean soft cloth. DO NOT leave
lint or any materials on the chill plate. DO NOT
clean using compressed air.
• 270/292/351/424 Hp Drive Only: Lightly lubricate the new O-rings with O-ring lubricant. Provided in the kit.
• 270/292/351/424 Hp Drive Only: Install the new
Orings into the chill plate grooves.
• 270/292/351/424 Hp Drive Only: Place the new
OSCD power module on the chill plate so that the
connector is towards the front of the OSCD enclosure. Carefully slide the OSCD power module
power connections under the bus structure. The
replacement assembly should still be loose.
• 385/419/503/608 Hp Drive Only: Carefully remove the OSCD power module by sliding it away
from the bus structure while lifting slightly. DO
NOT place any stress on the bus structure.
• 385/419/503/608 Hp Drive Only: Wipe the chill
plate clean with a clean soft cloth. DO NOT leave
lint or any materials on the chill plate. DO NOT
clean using compressed air. Rubbing alcohol
works well to remove the thermal grease from the
chill plate.
JOHNSON CONTROLS
(FRONT OF PANEL)
LD07412
FIGURE 29 - OSCD POWER MODULE
83
5
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
• Install the power wire connector tang or tangs using 6 Phillips head screws, and torque the screws
to 48 in.-lbs. (5.5 Nm) ± 10%. If a copper output
power tang or tangs are used install them with the
bolt that was saved. Torque the bolt to 40-50 inlbs. Then install the 6 Phillips head screws, and
torque the screws to 48 in.-lbs. (5.5 Nm) ± 10%.
• Remove the 6 Phillips head screws (not yet tightened) at the bus structure and install the 3 square
capacitors to the bus structures with these screws.
Torque the screws to 48 in.-lbs. (5.5 Nm) ± 10%.
• Install the connector on the IGBT Gate Driver
Board.
• 270/292/351/424 Hp Drive Only: Close the drain
valve on the heat exchanger and reill the system
with the coolant supplied and check for leaks.
• 270/292/351/424 Hp Drive Only: Follow the directions included in the Start-Up Preparations for
running the OSCD’s water pump to ensure all entrapped air is vented and the cooling loop is properly illed.
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Replacement of the Harmonic Filter Power
Module
The procedure to replace the harmonic filter power
module is the same as for the replacement of the OSCD
Power Module, except for the following.
• 270/292/351/424 Hp Drive Only: On early models of the OSCD compressor drive the cooling
system did not properly drain out of the Harmonic
Filter Power Module. Early models can be determined by look at the far end of the heat exchanger.
If the three hoses are connected to a 6 inch plastic
riser pipe, then this is the style that will not properly drain.
• 270/292/351/424 Hp Drive Only: Drain the coolant as described above. Then remove one of the
coolant hoses feeding the Harmonic Filter Power
Module. Failure to completely drain the coolant
system will cause coolant to leak into the VSD
enclosure.
• 385/419/503/608 Hp Drive Only: The IGBT
module for the harmonic ilter power unit is installed in the same manner as the 270/292/351/424
Hp drive, but will not have the draining problems.
In-Warranty Parts Return – Any OSCD parts failing
within the standard warranty period must be returned.
Refer to YORK Warranty Return Policy for instructions.
84
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
VSD FREQUENTLY ASKED QUESTIONS
Why doesn’t the measured input amps of the
OSCD agree with the rated FLA?
The input current to the OSCD may be considerably
lower, compared to the output current. This is due to
the power factor at the input to the OSCD being greater
than .95, and nearly unity when the Harmonic Filter
option is included. Chiller FLA must be measured at
the motor terminals, where the power factor is the normal motor power factor. Use a true RMS reading meter
to make these measurements.
How can I manually control the speed of the
drive?
For the OptiView Control Panel, first enter the Service Access Level. Select the VSD Tuning Screen from
the Compressor Screen. From this screen the speed
of the drive can be set to a specific frequency, raise
or lowered by a specific amount of frequency, or set
for fixed speed (60Hz). Press the AUTO key to return
speed control to the ACC board.
For the Micro Computer Control Center, first enter
the VSD Service mode. Once in the VSD Service mode,
make certain you are NOT in program mode by pressing the program button and watching the display. With
the panel NOT in program, you can adjust the frequency setpoint using the increment and decrement keys
which are combined with the vanes open and closed
buttons. You can also select fixed 60HZ by pressing
the 60HZ key. The OSCD will begin to change speed,
moving toward the manual setpoint you entered. It may
take some time to attain the programmed frequency. To
exit the manual OSCD speed mode, press the Auto key.
Be sure the unit is in Auto speed mode before exiting
the VSD service mode, otherwise the unit will stay in
the manual speed mode after exiting the VSD service
mode.
How can the Pre Rotation Vanes be manually
controlled when an OptiSpeed Compressor
Drive is installed?
Regardless of which control center is used, the method of manual vane control remains the same as with
a fixed speed chiller. Refer to the appropriate chiller
Service Manual for these controls.
On a retrofit OptiSpeed Compressor Drive,
what is the DV/DT Network for?
The combination of long runs of wire between the
OSCD and the compressor motor, with the fast rise
JOHNSON CONTROLS
time of the output voltage of the OSCD can cause excessively high voltage potential at the motor terminals.
Without the DV/DT Network, the insulation in the
compressor motor may be overly stressed. The DV/DT
Network reduces the high voltage potential to below
the motor’s voltage specification. The design of the
DV/DT network currently in production has a requirement for installation on top of the motor terminal box.
DO NOT add any additional wire between the motor
terminal connections and the DV/DT Network. The additional wire will reduce the DV/DT Network’s effectiveness, and potentially shorted the life of the motor.
On all OSCD’s, a similar circuit is located on the back
wall of the OSCD enclosure near the motor connections. Since this filter is already present inside the
cabinet on all OSCD, some installers have questioned
whether the internal circuit must be disabled when using the terminal box mounted accessory. The answer is
no - you do not need to disconnect the DV/DT network
inside the OSCD cabinet.
Is a Condenser Water Strainer used with the
shell and tube heat exchanger?
Since the shell and tube heat exchanger can be cleaned
with a rifle brush, no extra precautions are needed to
keep the heat exchanger clean. No strainer is provided with this OSCD. The intent is to have the heat exchanger cleaned annually. Gaskets are available (refer
to the service parts list).
What is the timing of the Anti-Recycle when
an OSCD is applied?
The anti-recycle time is much quicker with an OSCD
than with a starter. The reason is the elimination of
inrush current on start-up. The OptiSpeed compressor drive slowly accelerates the compressor motor so
that the motor does not consume more than 100% of
the motor’s nameplate full load amps. The anti-recycle
time is five (5) starts in succession, followed by a ten
minute wait. After ten minutes, you get five more successive starts. This is permitted on OSCD units only,
due to the low current draw and reduced motor heating
during startup.
Why does the condenser pressure transducer
on a YT chiller need to be changed when an
OSCD is applied?
For the OptiSpeed compressor drive to perform well it
requires cooler condenser water. The cooler condenser
water lowers the condenser pressure below the standard condenser pressure transducer’s range. Thus, a
85
5
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
new pressure transducer is required with a wider range
of pressure. The new pressure transducer part number
is 025-29148-009. Its range is 4 to 34 PSIA, with a
proportional output of 0.5 to 4.5 VDC. The OSCD software for YT chillers require the use of this transducer.
What is the proper wire sizing when using an
OptiSpeed Compressor Drive?
The input power wires to the OSCD are sized at 1.25
times the full-load amps of the compressor motor, plus
oil pump amps and control transformer amps. Note this
differs from the 1.38 multiplier used on earlier drives.
OptiSpeed compressor drive to Compressor Motor
wires need only be 1.25 times the compressor motor
FLA, since the oil pump and control power are not part
of the equation at this point.
Does the surge counter reflect the number of
points in the surge map?
No, the surge counter increments each time the ACC
detects a chiller surge, not each time a surge is added
to the map. It is not uncommon to receive a chiller with
some number of surges recorded in memory. The only
way to zero this value is to zero the BRAM memory
which stores the compressor surge map and other nonvolatile data. Zeroing of the BRAM generally is not
done unless some condition has caused false data to
be stored - see section titled “Zeroing BRAM” below.
Also, be aware it is not uncommon to find very high
numbers of surges. We had one chiller which surged
for two weeks, running 60 HZ, along with a fixedspeed chiller which was also surging due to tower
problems. After two weeks, the customer decided it
was time to fix the tower! In this case we logged over
18,000 surges.
Under what conditions should I zero the
BRAM on the ACC board?
An internal lithium battery maintains the BRAM memory even if the power is removed. This chip is located
on the ACC board. It stores the compressor surge map
information, and other data such as the vane pot calibration. There are only 3 reasons where this memory
should be cleared - when the chiller has been running
and storing invalid surge information due to a mis-calibrated vane pot, when the chiller has been running and
storing invalid data due to a faulty condenser or evaporator transducer, and when the chiller is first started
with an OSCD. Vane position and refrigerant pressures
are two of the three pieces of information stored in the
surge map, and if these values are false, the map created with false information will be a false map.
86
FORM 160.00-M4
ISSUE DATE: 1/21/2013
Any other conditions which may be abnormal will only
cause the chiller to run at an abnormal part of the map,
but will still be valid data for the conditions. For example, if the cooling tower should by-pass water, causing a false high-head, the ACC will figure out the best
mode of operation for these conditions, even though
they are abnormal. When the problem with the tower is
fixed, the ACC will determine a new optimum operation on a different part of the map. Neither set of stored
values is incorrect. If the same tower problem ever develops again, the chiller will already know what to do.
If you believe you need to zero the BRAM, call YORK
factory service for assistance.
Should I require the customer to install
isolation between the Power Conduits and
the OptiSpeed Compressor Drive?
We no longer require a section of non-metallic conduit
at the entrance and exit to/from the OSCD as we did on
previous products. If any customer or installer wishes
to continue to follow this practice, we have no objections.
How does the MicroComputer Control Center
provide power to the ACC board?
The ACC board is power by +30 VDC unregulated
from the control center’s power supply board. There
are two connectors on this power supply which can furnish +30 VDC unregulated. The plug designated in the
retrofit drawings is sometimes already being used by
the liquid level control. It is permissible to daisy chain
off this same wiring, or you may elect to utilize the
alternate +30 VDC unregulated connection.
What Instructions do I use to install a retrofit
OptiSpeed Compressor Drive?
There are 3 drawings shipped with each retrofit kit.
These drawings are:
• Vane Pot Installation and Set-Up
• Piping Installation
• Control Panel Retroit
How do I connect a 12 lead motor to a
OptiSpeed Compressor Drive?
Most of these 12 lead motors actually have two sets of
parallel windings, and therefore have two one’s, two
two’s, etc. OSCD’s and Solid-State Starters are connected to the motor in the delta configuration, that is 1
and 6, 2 and 4, 3 and 5. The T1 lug will then have two
one’s and two sixes tied to it.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
There were a few motors, made several years ago,
which were numbered 1 through 12. These motors had
the first set of wires marked 1 to 6. Numbering then
continued, with the second 1 numbered 7, the second 2
numbered 8, and so on, up to 12. In other words, take
the numbers above six, subtract 6 from the number, and
re-label as the result.
What is the Peak Input Voltage value?
The displayed value is the Phase to Neutral voltage at
the input to the drive in terms of peak voltage, as would
be measured with an oscilloscope.
Phase to neutral is normally the phase-to-phase voltage
divided by the square root of three, or 265 VAC phase
to neutral, for a 460 VAC system. The peak value of
the 265 VAC measurement is approximately that number times the square root of two, or 375 volts in this
example.
How do I reset the KWH Meter?
For the OptiView Control Panel, first enter the Service Access Level. Select the VSD Screen. Press the
KWH key, and select the default selection. The KWH
value will now be zero.
For the Micro Computer Control Center, first enter the “VSD Service Mode”, making sure the Control Center is in “Program Mode”, and pressing the
“Operating Hours / Start Counter” button. The display
will show, “Reset Hours? Y/N”. Use the advance day /
Scroll key to select “Y”, and press “Enter”. The KWH
value will now be zero.
Is the Real Time Clock Chip on the
microboard and the BRAM Chip on the ACC
and OSCD logic boards the same chip?
If you are familiar with the RTC Clock chip used on the
control center microboard, you may notice what appears to be clock chips on the ACC board and on the
OSCD logic board. These two boards contain similar
black plastic chips which are battery backed random
access memory (BRAM). They have a different number of pins from the RTC Clock chips, and cannot be
replaced by the familiar clock chip.
When is a Booster Pump required on a
Retrofit OptiSpeed Compressor Drive?
Detailed information is supplied in Installation (Form
160.05-N4). In general, the OSCD requires 8 ft of head
for proper water flow to the OSCD heat exchanger.
If this amount of head is not available, then a booster
pump is required.
JOHNSON CONTROLS
Can I apply an OptiSpeed Compressor Drive
to a generator?
Yes, the OSCD can be applied to a generator. No modifications are required for a generator application. We
have several OSCD installations running on generator
power without difficulty. It is necessary that the generator’s output voltage be maintained within the specified
range of 414 to 508 VAC for a 460 VAC line, 360 to 440
for a 400 VAC line, or 517 to 632 VAC for a 575 VAC
line and frequency be maintained within +/- 1 HZ (on
all applications). This is usually not a problem for most
generators, since motor current at startup is limited to
less than 1X the Full Load Amps (FLA). The transfer of
power between the utility and generator and back again
must be delayed as to cause the chiller to fault and then
restart. Not providing this delay may cause failure within the OSCD or instability within the generator.
My chiller will not slow down, why?
The OSCD will not reduce the motor speed until the
leaving chilled water temperature is below +0.5 degree
from setpoint. Once in this window, the speed still cannot be reduced until the operation is deemed to be stable, based upon the vanes are not continually moving
open and closed to maintain temperature. This hunting
effect is normally due to one of the following:
• Chilled liquid and Condenser liquid lows are not
with in the design range . The rate of change in
low maybe too fast for the chiller to be determined as stable.
• Return liquid temperature is varying due to 3-way
valves or other system coniguration, and the
chiller is simply following changes in load.
• Vane stroke is too large. Remove the sensitivity
jumper in the Micro Computer Control Center, or
program a lower sensitivity on the OptiView Control Center. Also, check the vane motor to see that
the fullest possible stroke is being utilized. Moving the vane motor arm pivot point closer to center, and extending the degrees of travel by adjusting the internal end stops, will reduce the amount
of vane action for the same period of operation.
• Verify that the condenser tubes are clean.
• Verify that the liquid level control is working
properly, and maintaining a refrigerant level in
the condenser.
• Ensure that the condenser liquid temperature is
proper for the load on the chiller. In many cases,
the condenser liquid temperature is still at 85°F.
87
5
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
Failure to reduce speed may also be due to the system
having been placed in Manual Speed when in VSD
•
Service Mode. Other causes are a missing or disconnected wiring harness at ACC board J3, or a faulty
ACC board itself.
What is the function of the Green LED on
ACC Board?
This LED will light if:
• The system is in Manual speed control.
• The chiller is running in current limit.
• The leaving chilled liquid temperature is greater
that +0.5 of setpoint.
• The rate of change in temperature of the leaving
chilled water is greater than that programmed by
the stability limit function.
• The chiller is not running.
I believe that the chiller is surging, but the
surge counter is not increasing. What could
be the problem?
When a surge is detected, the ACC board will light the
red LED. Failure to light the red LED may be due to
one of the following:
• The condition is “Stall”, Not Surge - Stall is a very
noisy condition which is due to gas pulsations hitting the impeller wheel in a random fashion. System pressures and motor current may luctuate in
brief, random pulses, but this is not a surge. This
is normal for a chiller that has reduced speed, but
the condenser water temperature is too high. True
surge will be characterized by a repeated howling
sound, with pressure and motor current swinging
in a cyclical manner.
• The wire harness connecting the ACC board J3 to
the Micro-board may be missing or disconnected.
This harness passes system pressure information
to the ACC board.
Why is the OSCD Circuit Breaker Tripping?
Circuit breaker tripping is now normal for a failed OptiSpeed Compressor Drive. This drive no longer contains input fuses. The AC choke now reduces the current flowing into the short, and the circuit breaker is
now fast enough to provide proper protection. A tripped
circuit breaker may be due to a shorted condition inside
the drive, or the presence of a ground fault condition,
or may be due to the breaker itself being faulty.
Check for shorts at the input and output of the drive.
Check for leakage current to ground. This could also
be a problem in one of the input SCR’s. In some cases,
the precharge current may cause the SCR to fail. It was
determined in some applications the circuit breaker
would trip because the input SCR was falsely turned
on by a high rate of change in voltage on the input line.
Snubbers were added across the input SCR to prevent
this problem. Refer to Wiring Field Connections (Variable Speed Drive) Replacement Parts List (Variable
Speed Drive) (Form 160.00-RP4) (406)) or later for
part numbers.
What is the TEST Button for on OSCD Logic
Board?
When the OSCD is not running, this button may be
used to test operation of the logic outputs from the
OSCD logic board, as well as the operation of the gate
driver board on the IGBT module. When this button is
depressed, six output LEDs on the OSCD logic board
alternately light the three plus (+) LEDs, then the three
minus (-) LEDs. At the same time, six LEDs on the gate
driver board will alternate between dim and bright intensity. Several conditions can inhibit this test function:
• If any OSCD fault exists.
• The chiller is not running.
• If the unit is in pre-charge.
The coolant normally has a pink or rose color when
new. After several months of operation, this color may
dissipate, and the coolant may appear almost colorless.
The lack of the color in the coolant does not necessarily
88
indicate a problem. Most colorless samples test above
1000 PPM nitrite, which is normal. There is no need to
flush the system unless you find the coolant becoming
opaque or cloudy. In this case we suggest you obtain a
sample for analysis, then flush the system with coolant
and install fresh coolant. The coolant must be changed
every year regardless of color or test results.
• The ACC board may be defective.
Do I have a problem with my coolant? The
pink color is no longer visible?
FORM 160.00-M4
ISSUE DATE: 1/21/2013
• If the SCR trigger is enabled.
• If the OSCD unit is running.
• A 4 minute timer is part of this function to ensure
that the DC Link Voltage is discharged to a safe
level. This timer must time out before the Test
Button will function.
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
If a new filter logic board is installed in the drive the
gate driver LED's on the filter gate driver board will
now flash just like the VSD gate driver board. The part
number of the new filter logic board is 031-02932-xxx.
TABLE 4 - SOFTWARE REFERENCE LIST 60 HZ ONLY
OPTIVIEW CONTROL CENTER MINIMUM VERSIONS REQUIRED FOR THE 351 HP DRIVE
PART NUMBER
MINIMUM VERSION NUMBER
Microboard U45
LOCATION
031-01796-003
C.MLM.00.03
YT Microboard U46
031-02004-001
C.MLM.02.02B.102
YK Microboard U46
031-01797-001
C.MLM.01.05B.102
YKP Microboard U46
031-02073-001
C.MLM.04.01B.100
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-006
C.VSD.01.10
OSCD Logic Board U40
031-01619-003
C.VSD.03.02
OSCD Logic Board U45
031-01618-001
C.VSD.02.02
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-006
C.FTR.01.14
5
OPTIVIEW CONTROL CENTER MINIMUM VERSIONS REQUIRED FOR THE 424/608 HP DRIVE
(FOR 031-02430-000 BOARD ONLY)
LOCATION
PART NUMBER
MINIMUM VERSION NUMBER
YT Microboard U46
031-02469-001
C.OPT.02.09.008
YK and YKP Microboard U46
031-02474-001
C.OPT.01.15A.307
Microboard U45
031-01796-003
C.MLM.00.03
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-009
C.VSD.01.23
OSCD Logic Board U40
031-01619-003
C.VSD.03.04
OSCD Logic Board U45
031-01618-001
C.VSD.02.02
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-008
C.FTR.01.20
OPTIVIEW CONTROL CENTER MINIMUM VERSIONS REQUIRED FOR THE 503 HP DRIVE
LOCATION
PART NUMBER
MINIMUM VERSION NUMBER
YT Microboard U46
031-02004-001
C.MLM.02.04.104
YK and YKP Microboard U46
031-01797-001
C.MLM.01.08.105
Microboard U45
031-01796-003
C.MLM.00.03
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-006
C.VSD.01.13A
OSCD Logic Board U40
031-01619-003
C.VSD.03.04
OSCD Logic Board U45
031-01618-001
C.VSD.02.02
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-006
C.FTR.01.18
MICRO COMPUTER CONTROL CENTER VERSIONS REQUIRED FOR THE 351 HP DRIVE
LOCATION
PART NUMBER
MINIMUM VERSION NUMBER
YT Microboard U17
031-01676-003
C.YTV.05.20
YK Microboard U17
031-01675-003
C.YKV.06.24
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-006
C.VSD.01.10
OSCD Logic Board U40
031-01619-003
C.VSD.03.02
JOHNSON CONTROLS
89
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
FORM 160.00-M4
ISSUE DATE: 1/21/2013
TABLE 4 - SOFTWARE REFERENCE LIST 60 HZ ONLY (CONT'D)
OSCD Logic Board U45
031-01618-001
C.VSD.02.02
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-006
C.FTR.01.14
MICRO COMPUTER CONTROL CENTER VERSIONS REQUIRED FOR THE 424/608 HP DRIVE
LOCATION
PART NUMBER
MINIMUM VERSION NUMBER
YT Microboard U17
031-01676-003
C.YTV.05.24
YK Microboard U17
031-01675-003
C.YKV.06.32
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-009
C.VSD.01.23
OSCD Logic Board U40
031-01619-003
C.VSD.03.04
OSCD Logic Board U45
031-01618-001
C.VSD.02.02
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-008
C.FTR.01.20
MICRO COMPUTER CONTROL CENTER VERSIONS REQUIRED FOR THE 503 HP DRIVE
LOCATION
YT Microboard U17
PART NUMBER
MINIMUM VERSION NUMBER
031-01676-003
C.YTV.05.22
YK Microboard U17
031-01675-003
C.YKV.06.30
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-006
C.VSD.01.13A
OSCD Logic Board U40
031-01619-003
C.VSD.03.04
OSCD Logic Board U45
031-01618-001
C.VSD.02.02
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-006
C.FTR.01.18
90
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
SECTION 5 - TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES
TABLE 5 - SOFTWARE REFERENCE LIST 50 HZ ONLY
OPTIVIEW CONTROL CENTER MINIMUM VERSIONS REQUIRED FOR THE 292 HP DRIVE
LOCATION
PART NUMBER
MINIMUM VERSION NUMBER
Microboard U45
031-01796-003
C.MLM.00.03
YT Microboard U46
031-02004-001
C.MLM.02.02B.102
YK Microboard U46
031-01797-001
C.MLM.01.05B.102
YKP Microboard U46
031-02073-001
C.MLM.04.01B.100
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-007
C.VSD.01.14A
OSCD Logic Board U40
031-01619-003
C.VSD.03.02
OSCD Logic Board U45
031-01618-002
C.VSD.02.03
Filter Logic Board U26
31-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-007
C.FTR.01.15
OPTIVIEW CONTROL CENTER MINIMUM VERSIONS REQUIRED FOR THE 419 HP DRIVE
PART NUMBER
MINIMUM VERSION NUMBER
Microboard U45
LOCATION
031-01796-003
C.MLM.00.03
YT Microboard U46
031-02004-001
C.MLM.02.04.104
YK and YKP Microboard U46
031-01797-001
C.MLM.01.08.105
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-007
C.VSD.01.14A
OSCD Logic Board U40
031-01619-003
C.VSD.03.04
OSCD Logic Board U45
031-01618-002
C.VSD.02.03
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-007
C.FTR.01.19
5
MICRO COMPUTER CONTROL CENTER VERSIONS REQUIRED FOR THE 292 HP DRIVE
PART NUMBER
MINIMUM VERSION NUMBER
YT Microboard U17
LOCATION
031-01676-002
C.YTV.05.21
YK Microboard U17
031-01675-002
C.YKV.06.23
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-007
C.VSD.01.14A
OSCD Logic Board U40
031-01619-003
C.VSD.03.02
OSCD Logic Board U45
031-01618-002
C.VSD.02.03
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-007
C.FTR.01.15
MICRO COMPUTER CONTROL CENTER VERSIONS REQUIRED FOR THE 419 HP DRIVE
LOCATION
PART NUMBER
MINIMUM VERSION NUMBER
YT Microboard U17
031-01676-002
C.YTV.05.23
YK Microboard U17
031-01675-002
C.YKV.06.29
ACC Board U22
031-01674-002
C.ACC.01.03
OSCD Logic Board U34
031-01617-007
C.VSD.01.14A
OSCD Logic Board U40
031-01619-003
C.VSD.03.04
OSCD Logic Board U45
031-01618-002
C.VSD.02.03
Filter Logic Board U26
031-01680-003
C.FTR.02.05
Filter Logic Board U42
031-01633-007
C.FTR.01.19
JOHNSON CONTROLS
91
FORM 160.00-M4
ISSUE DATE: 1/21/2013
NOTES
92
JOHNSON CONTROLS
FORM 160.00-M4
ISSUE DATE: 1/21/2013
The following factors can be used to convert from
English to the most common SI Metric values.
TABLE 6 - SI METRIC CONVERSION
MEASUREMENT
MULTIPLY ENGLISH UNIT
BY FACTOR
TO OBTAIN METRIC UNIT
Capacity
Tons Refrigerant Effect (ton)
3.516
Kilowatts (kW)
Power
Horsepower
0.7457
Kilowatts (kW)
Flow Rate
Gallons / Minute (gpm)
0.0631
Liters / Second (l/s)
Feet (ft)
0.3048
Meters (m)
Inches (in)
25.4
Millimeters (mm)
Weight
Pounds (lbs)
0.4538
Kilograms (kg)
Velocity
Feet / Second (fps)
0.3048
Meters / Second (m/s)
Feet of Water (ft)
2.989
Kilopascals (kPa)
Pounds / Square Inch (psi)
6.895
Kilopascals (kPa)
Length
Pressure Drop
TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 27.2°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
JOHNSON CONTROLS
93
P.O. Box 1592, York, Pennsylvania USA 17405-1592
Copyright © by Johnson Controls 2013
Form 160.00-M4 (113)
Issue Date: January 21, 2013
Supersedes:160.00-M4 (1007)
800-861-1001
www.johnsoncontrols.com
Subject to change without notice. Printed in USA
ALL RIGHTS RESERVED