IS 1893 (Part 2) : 2014
Hkkjrh; ekud
Indian Standard
(Reaffirmed 2019)
lajpukvksa osQ HkwdEijksèkh
fMtkbu osQ ekunaM
Hkkx 2 æo èkkfjr VSd
a
(ik¡pok¡ iqujh{k.k)
Criteria for Earthquake Resistant
Design of Structures
Part 2 Liquid Retaining Tanks
( Fifth Revision )
ICS 91.120.25
© BIS 2014
Hkkjrh; ekud C;wjks
B U R E A U O F I N D I A N ST A N D A R D S
ekud Hkou] 9 cgknqj'kkg T+kiQj ekxZ] ubZ fnYyh&110002
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI-110002
www.bis.org.in www.standardsbis.in
August 2014
Price Group 8
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
Earthquake Engineering Sectional Committee, CED 39
FOREWORD
This Indian Standard (Part 2) (Fifth Revision) was adopted by the Bureau of Indian Standards, after the draft
finalized by the Earthquake Engineering Sectional Committee had been approved by the Civil Engineering
Division Council.
In the fifth revision IS 1893 has been split into five parts. The other parts in the series are:
Part 1
Part 3
Part 4
Part 5
General provisions and buildings
Bridges and retaining walls
Industrial structures including stack like structures
Dams and embankments
Part 1 contains provisions that are general in nature and applicable to all types of structures. It also contains
provisions that are specific to buildings only. Unless stated otherwise, the provisions in Part 2 to Part 5 shall be
read in conjunction with the general provisions in Part 1.
This standard (Part 2) contains provisions for liquid retaining tanks. Unless otherwise stated, this standard shall
be read necessarily in conjunction with IS 1893 (Part 1) : 2002.
As compared to provisions of IS 1893 : 1984, in this standard following important provisions and changes have
been incorporated:
a) Analysis of ground supported tanks is included.
b) For elevated tanks, the single degree of freedom idealization of tank is done away with; instead a twodegree of freedom idealization is used for analysis.
c) Bracing beam flexibility is explicitly included in the calculation of lateral stiffness of tank staging.
d) The effect of convective hydrodynamic pressure is included in the analysis.
e) The distribution of impulsive and convective hydrodynamic pressure is represented graphically for
convenience in analysis; a simplified hydrodynamic pressure distribution is also suggested for stress
analysis of the tank wall.
f) Effect of vertical ground acceleration on hydrodynamic pressure is considered.
g) Quality control measures considered necessary in deign and construction of reinforced concrete tanks
for achieving safe performance under normal as well as seismic conditions are also included.
The units used with the items covered by the symbols shall be consistent throughout this standard, unless specifically
noted otherwise.
In the formulation of this standard due weightage has been given to international coordination among the standards
and practices prevailing in different countries in addition to relating it to the practices in the field of this country.
In the formulation of this standard considerable help has been taken by the Indian Institute of Technology Kanpur,
Institute of Technology Roorkee, Visvesvaraya National Institute of Technology, Nagpur and several other
organizations including Guidelines prepared by IIT, Kanpur for GSDMA.
Reference has been made to the following documents in the formulation of this standard:
a)
ACI 350.3, 2001, ‘Seismic design of liquid containing concrete structures’, American Concrete Institute,
Farmington Hill, MI, USA.
b) Eurocode 8, 1998, ‘Design provisions for earthquake resistance of structures, Part 1 General rules and
Part 4 – Silos, tanks and pipelines’, European Committee for Standardization, Brussels.
(Continued on third cover)
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
Indian Standard
CRITERIA FOR EARTHQUAKE RESISTANT
DESIGN OF STRUCTURES
PART 2 LIQUID RETAINING TANKS
( Fifth Revision )
1 SCOPE
(Ah)c = Design horizontal seismic coefficient for
convective mode
This standard (Part 2) covers ground supported liquid
retaining tanks and elevated tanks supported on staging.
Guidance is also provided on seismic design of buried
tanks.
(Ah)i = Design horizontal seismic coefficient for
impulsive mode
Av = Design vertical seismic coefficient
B = Inside width of rectangular tank perpendicular
to the direction of seismic force
Cc = Coefficient of time period for convective
mode
2 REFERENCES
The following standards contain provisions which,
through reference in this text, constitute provisions of
this standard. At the time of publication, the editions
indicated were valid. All standards are subject to
revision, and parties to agreements based on this
standard are encouraged to investigate the possibility
of applying the most recent editions of the standards
indicated below:
IS No.
456 : 2000
1893
(Part 1) : 2002
3370
(Part 1) : 2009
(Part 2) : 2009
(Part 3) : 1967
(Part 4) : 1967
4326 : 2013
11682 : 1985
13920 : 1993
Ci = Coefficient of time period for impulsive mode
d = Deflection of wall of rectangular tank, on the
vertical centre line at a height h, when loaded
by a uniformly distributed pressure q, in the
direction of seismic force
dmax = Maximum sloshing wave height
D = Inner diameter of circular tank
E = Modulus of elasticity of tank wall
Title
Code of Practice for plain and
Reinforced Concrete (fourth
revision)
Criteria for earthquake resistant
design of structures: Part 1 General
provisions and buildings (fifth
revision)
Code of Practice for concrete
structures for the storage of liquids
General requirements (first revision)
Reinforced concrete structures (first
revision)
Prestressed concrete structures
Design tables
Code of Practice for earthquake
resistant design and construction of
buildings (third revision)
Criteria for design of RCC staging
for overhead water tanks
Ductile detailing of reinforced
concrete structures subjected to
seismic sorces — Code of Practice
ELx = Response quantity due to earthquake load
applied in x - direction
ELy = Response quantity due to earthquake load
applied in y - direction
g = Acceleration due to gravity
h = Maximum depth of liquid
h = Height of combined centre of gravity of half
impulsive mass of liquid (mi/2) and mass of
( )
one wall m w
hc = Height of convective mass above bottom of
tank wall (without considering base pressure)
hi = Height of impulsive mass above bottom of
tank wall (without considering base pressure)
hs = Structural height of staging, measured from
top of foundation to the bottom of container
wall
ht = Height of centre of gravity of roof mass above
bottom of tank wall
hw = Height of centre of gravity of wall mass above
bottom of tank wall
3 SYMBOLS
The symbols and notations given below apply to the
provisions of this standard:
hc* = Height of convective mass above bottom of
Ah = Design horizontal seismic coefficient
1
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
tank wall (considering base pressure)
hi = Height of impulsive mass above bottom of
tank wall (considering base pressure)
wall
pv = Hydrodynamic pressure on tank wall due to
vertical ground acceleration
hcg = Height of centre of gravity of the empty
container of elevated tank, measured from the
top of footing
I = Importance factor given in Table 1
pww = Pressure on wall due to its inertia
q = Uniformly distributed pressure on one wall
of rectangular tank in the direction of ground
motion
Kc = Spring stiffness of convective mode
Ks = Lateral stiffness of elevated tank staging
Qcb = Coefficient of convective pressure on tank
base
Qcw = Coefficient of convective pressure on tank
wall
*
l = Length of a strip at the base of circular tank,
along the direction of seismic force
L = Inside length of rectangular tank parallel to
the direction of seismic force
Qib = Coefficient of impulsive pressure on tank base
Qiw = Coefficient of impulsive pressure on tank wall
m = Total mass of liquid in tank
mb = Mass of base slab or plate
R = Response reduction factor given in Table 2
(Sa/g) = Average response acceleration coefficient as
per IS 1893 (Part 1) and 4.5
mc = Convective mass of liquid
mi = Impulsive mass of liquid
t = Thickness of tank wall
tb = Thickness of base slab
ms = Mass of empty container (includes mass of
members like roof, wall, tank floor, floor
beams, etc) of elevated tank and one-third
mass of staging (mass of tower excluding
container and foundation. Mass of columns,
braces and any other mass attached to staging
shall be included in mass of staging. Mass of
pedestal above foundation can be assumed to
be attached to foundation)
mt = Mass of roof slab
Tc = Time period of convective mode (in s)
Ti = Time period of impulsive mode (in s)
V = Total base shear
Vc = Base shear in convective mode
Vi = Base shear in impulsive mode
x = Horizontal distance in the direction of seismic
force, of a point on base slab from the
reference axis at the centre of tank
mw = Mass of tank wall
y = Vertical distance of a point on tank wall from
the bottom of tank wall
Z = Seismic zone factor as per Table 2 of IS 1893
(Part 1)
mw = Mass of one wall of rectangular tank
perpendicular to the direction of loading
M = Total bending moment at the bottom of tank
wall
M* = Total overturning moment at base
Mc = Bending moment in convective mode at the
bottom of tank wall
*
M c = Overturning moment in convective mode at
the base
Mi = Bending moment in impulsive mode at the
bottom of tank wall
*
M i = Overturning moment in impulsive mode at the
base
p = Maximum hydrodynamic pressure on wall
pcb = Convective hydrodynamic pressure on tank
base
pcw = Convective hydrodynamic pressure on tank
wall
pib = Impulsive hydrodynamic pressure on tank
base
piw = Impulsive hydrodynamic pressure on tank
ρ = Mass density of liquid
ρw = Mass density of tank wall
φ = Circumferential angle
4 PROVISIONS FOR SEISMIC ANALYSIS
4.1 General
Hydrodynamic forces exerted by liquid on tank wall
shall be considered in the analysis in addition to
hydrostatic forces. These hydrodynamic forces are
evaluated with the help of spring mass model of tanks.
For tank full as well as empty conditions, tank shall be
analysed for all the load combinations as per IS 1893
(Part 1). For load combination with seismic load, the
amount of liquid considered in the tank shall be normal
liquid level under service condition only.
4.2 Spring Mass Model for Seismic Analysis
When a tank containing liquid vibrates, the liquid exerts
impulsive and convective hydrodynamic pressure on
2
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
the tank wall and the tank base in addition to the
hydrostatic pressure. In order to include the effect of
hydrodynamic pressure in the analysis, tank can be
idealized by an equivalent spring mass model, which
includes the effect of tank wall-liquid interaction. The
parameters of this model depend on geometry of the
tank.
4.2.1 Ground Supported Tank
4.2.1.1 Ground supported tanks can be idealized as
spring-mass model shown in Fig. 1. The impulsive
mass of liquid, mi is rigidly attached to tank wall at
height hi (or hi*). Similarly, convective mass, mc is
attached to the tank wall at height hc (or hc*) by a spring
of stiffness Kc.
(a) Impulsive and Convective Mass and
Convective Spring Stiffness
4.2.1.2 Circular and rectangular tank
For circular tanks, parameters mi, mc, hi, hi*, hc, h*c and
Kc shall be obtained from Fig. 2 and for rectangular
tanks these parameters shall be obtained from Fig. 3.
hi and hc account for hydrodynamic pressure on the
tank wall only and the tank base. Hence, the value of
hi and hc shall be used to calculate moment due to
hydrodynamic pressure at the bottom of the tank wall.
The value of h*i and h*c shall be used to calculate
overturning moment at the base of tank.
(b) Height of Impulsive and Convective Masses
FIG. 2 PARAMETERS OF THE SPRING MASS MODEL
FOR C IRCULAR T ANK
4.2.2.4 For elevated tanks, the two degree of freedom
system of Fig. 4c can be treated as two uncoupled single
degree of freedom systems (see Fig. 4d), one
representing the impulsive plus structural mass
behaving as an inverted pendulum with lateral stiffness
equal to that of the staging, K s and the other
representing the convective mass with a spring of
stiffness, Kc.
FIG.1 SPRING MASS MODELS FOR GROUND SUPPORTED
CIRCULAR AND RECTANGULAR TANK
4.2.2 Elevated Tank
4.2.2.1 Elevated tanks (see Fig. 4a) can be idealized
by a two-mass model as shown in Fig. 4c.
4.2.3 For tank shapes other than circular (like intze,
truncated conical shape), the value of h/D shall
correspond to that of an equivalent circular tank of
same volume and diameter equal to diameter of tank
at top level of liquid; and mi, , mc , hi, hi* , hc hc* and Kc
of equivalent circular tank shall be used. The equivalent
cylindrical tank should be assumed to be located such
that top level of the liquid in equivalent tank is same
as in actual tank.
4.2.2.2 For elevated tanks with circular container,
parameters mi, mc, hi, hi*, hc h*c and Kc shall be obtained
from Fig. 2. For elevated tanks with rectangular
container, these parameters shall be obtained from
Fig. 3.
4.2.2.3 In Fig. 4c, ms is the structural mass and shall
comprise of mass of tank container and one-third mass
of staging.
3
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
t = thickness of tank wall;
E = modulus of elasticity of tank wall; and
ρ = mass density of liquid.
NOTE — In some circular tanks, wall may have flexible
connection with the base slab (Different types of wall to
base slab connections are described in Fig. 6). For tanks
with flexible connections with base slab, time period
evaluation may properly account for the flexibility of wall
to base connection.
4.3.1.2 Ground supported rectangular tank
For a ground supported rectangular tank, wherein wall
is rigidly connected with the base slab, time period of
impulsive mode of vibration, Ti in s, is given by:
Ti = 2 π d g
(a) Impulsive and Convective Mass and Convective
Spring Stiffness
where
d = deflection of the tank wall on the vertical
center-line at a height of h, when loaded by
uniformly distributed pressure of intensity q.
mi
+ mw g
2
q=
Bh
mi
h
hi + mw
2
2
h =
mi
+ mw
2
mw = mass of one tank wall perpendicular to the
direction of seismic force; and
B = inside width of tank.
4.3.1.3 Elevated tank
(b) Height of Impulsive and Convective Masses
FIG. 3 PARAMETERS OF THE SPRING MASS MODEL
FOR R ECTANGULAR TANK
Time period of impulsive mode, Ti, in s, is given by:
4.3 Time Period
Ti = 2π
4.3.1 Impulsive Mode
where
4.3.1.1 Ground supported circular tank
ms = mass of empty container and one-third mass
of staging; and
Ks = lateral stiffness of staging.
For a ground supported circular tank, wherein wall is
rigidly connected with the base slab (see Fig. 6a, 6b
and 6c), time period of impulsive mode of vibration
Ti, in second, is given by:
Ti = Ci
mi + ms
Ks
Lateral stiffness of the staging is the horizontal force
required to be applied at the centre of gravity of the
tank to cause a corresponding unit horizontal
displacement.
h ρ
t/D E
NOTE — The flexibility of bracing beam shall be considered
in calculating the lateral stiffness, K s of elevated moment
resisting frame type tank staging.
where
Ci = coefficient of time period for impulsive
mode. Value of Ci can be obtained from
Fig. 5;
4.3.2 Convective Mode
Time period of convective mode can be calculated
using 4.3.2.1 and 4.3.2.2. However, shorter time period
shall be used for design purposes.
h = maximum depth of liquid;
D = inner diameter of circular tank;
4
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
Roof Slab
Container
Top of
Foundation
(a) Elevated Tank
(c)
(b) Spring Mass Model
Two Mass Idealization of Elevated Tank
(d) Equivalent Uncoupled System Tank
FIG . 4 TWO MASS IDEALIZATION
10
-!
t
I
I
I
I- I
1
1
-r
-I~·
-T -
r-
-
I
I
~t
~-i
!
\
j
\
ELEVATED TANK
r '- l -
r- - · - - I
r
I
r
I
I
I
I
I
I
1
I
I
I
I
1
I
j
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
1- --+-- '!- - - 1- - -t-- t- - -1- - -t-- t1
I
!
'
l
i
t
I
I
I
I
'
I
I
I
I
I
I
8
-I
I
FOR
I
1
I
I
I
,
I
\
I
I
I
1
I
I
I
(
I
I
I
I
I
I
I
Ie
I
I
I
~-t
-
I
-
.
T---r - -I-- --r - --T
- 1- - -; -
-r- -r- --t -- +- -
I
I
I
til
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
!
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
!
I
1
I
I
I
I
I
I
I
f
I
I
I
I
I
J
I
I
'
!
I
i
-
~-t
I
I
i
I
I
.
I
-t
I
I
I
I
I
-~1
I
I
""":1- - -t- - t-- -1---1
I
1
I
~-it
I
- -- -l -- - r ----'-I - - i
I
I
I
I
I
I
-t
-~
I
I
}--t-\l- -i --t --:--i - -r--:-- i- -r--1--1--t --:-- -t-- t--i---t- - t---:--4
\
1
I'
6 ~ __~ 1.
I
c
1\
l- L ~J-:
I
I
I
1
I-
~ - _i _-~
!\
!
I\
4 ~- ~ - ~ -~,:tT
I i
:
I
:
I
I
!
I
I
I
I
J
!
I
~ -
~ -~
-~i
-~_:
-w--l--L--L-l--L-J--J--l-J-- :
i
I
!
I
I
I
I
I
I
i
r-...,!
I
I
I
I
I
I
I
I
I
-1C - r-li
I
I
I
- t-
I
I
I
I
I
1
1
~ ~ -i
: - - ~-
t
I
I
!
~
I
I
I
I
+ -i
I . e'
I
I
I
I
I
I
I
I
I
I
I
I
1
1
I
1
- ~ -
!
-t
: -:
l-~
;
r- t-}---1:-+f - - r - - l--- l--rt-~
-+~
i- -+ - - ~- ~~
i : ,-r- -1- '- -1-- r - - j- - l - - , --1-- 1
'--1--1 - - f -- -1- -
2 ~- -: !- ~ I,I
j
1
~ -· ~lI
I
I
I
I
I
I
I
I
I
:-
-~I
,
~ -
1
i - ·~ -· ~ - :
:I : - ~
I
I
I
I
1
I!
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
· -~· - · · - - ~ l
I
I
I
I
I
-
o
L
0.5
~ - ~ I
I
I
I
I
I
I
-'l- - ·4 --' l---I- - 4----'---1- - -I- -4 --+- - -I~
- --1* - - 1- - 4 - - +-- ~I-1-- I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
J
I
I
I
I
I
j
I
I
I
I
J
J
I
I
I
I
I
,
I
:
I
I
___ L_.l __ L ____L __ .l _ _ L __ L _ _l _ _ L __ L_.l ___ L _--'-__ .l __ l.. _ __ L _ (
o
I
I
j;...-
I
I
I
I
I
t-I
I
I
~
I
I
-1-----'
I
I
I
L_ -.J __ ..1
1.5
2
hiD
F IG. 5 COEFFICIENT
OF I MPULSIVE AND
CONVECTIVE MODE TIME P ERIOD
5
FOR
CIRCULAR TANK
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
FIG. 6 T YPE
OF
CONNECTIONS BETWEEN TANK WALL
4.3.2.1 Time period of convective mode, in second, is
given by:
Tl = 2 π
BASE S LAB
where
Cc = coefficient of time period for convective
mode. Value of Cc can be obtained from
Fig. 7; and
L = inside length of tank parallel to the direction
of seismic force.
mc
Kc
The values of mc and Kc can be obtained from Figs. 2a
and 3a respectively, for circular and rectangular tanks.
4.3.3 For tanks resting on soft soil, effect of flexibility
of soil may be considered while evaluating the time
period. Generally, soil flexibility does not affect the
convective mode time period. However, soil flexibility
may affect impulsive mode time period.
4.3.2.2 Since the expressions for mc and Kc are known,
the expression for Tc can be alternatively expressed
as:
a)
AND
Circular tank — Time period of convective
mode, Tc, in s, is given by:
Tc = Cc
D
ρ
where
Cc = coefficient of time period for convective
mode. Value of Cc can be obtained from
Fig. 5; and
D = inner diameter of tank.
b) Rectangular tank — Time period of
convective mode of vibration, Tc, in second,
is given by:
Tc = Cc
FIG .7 COEFFICIENT OF CONVECTIVE MODE TIME
PERIOD (Cc) FOR RECTANGULAR TANK
L
ρ
6
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
4.4 Damping
Table 2 Suggested Values of ‘R’ for
Elevated Tanks
( Clause 4.5 )
Damping in the convective mode for all types of liquids
and for all types of tanks shall be taken as 0.5 percent
of the critical.
Sl
No.
(1)
Damping in the impulsive mode shall be taken as
2 percent of the critical for steel tanks and 5 percent of
the critical for concrete or masonry tanks.
Design horizontal seismic coefficient, A h shall be
obtained by the following expression, subject to 4.5.1
and 4.5.2:
Z I Sa
× ×
2 R g
where
Z = zone factor given in Table 2 of IS 1893
(Part 1);
I = importance factor given in Table 1;
R = response reduction factor given in Table 2 and
Table 3; and
Sa/g = average response acceleration coefficient as
given by Fig. 2 and multiplying factors for
obtaining values for other damping as given
in Table 3 of IS 1893(Part 1) and subject to
4.5.1 and 4.5.2.
(2)
(3)
2
3
2.5
3.5
4
2.5
4
3.5
4
1)
These R values are meant for liquid retaining tanks on frame
type staging which are inverted pendulum type structures. These
R values shall not be misunderstood for those given in other parts
of IS 1893 for building and industrial frames.
NOTE P , effect should be considered in the design of the
staging.
Table 1 Importance Factor, I
(Clause 4.5)
Sl
No.
(1)
R
i) Tank supported on masonry shaft
( Not permitted in zones IV and V ):
a) Masonry shaft reinforced with horizontal bands
b) Masonry shaft reinforced with horizontal bands
and vertical bars
ii) Tank supported on RC shaft:
a) RC shaft with reinforcement in one curtain (in
both directions) at center of shaft thickness
b) RC shaft with reinforcement in two curtains (in
both directions)
c) RC shaft with reinforcement in two curtains (in
both directions) and with stiffened openings and
bracings
1)
iii) Tank supported on RC frame :
a) Ordinary moment resisting frame (OMRF) type
staging
b) Special moment resisting frame (SMRF)
conforming ductility requirements of IS 13920
1)
iv) Tank supported on steel frame :
a) Special moment resistant frame (SMRF) without
diagonal bracing
b) Special moment resistant frame (SMRF) with
diagonal bracing
4.5 Design Horizontal Seismic Coefficient
Ah =
Type of Elevated Tank
Type of Liquid Storage Tank
1
(2)
(3)
Table 3 Suggested Values of ‘R’ for Ground
Supported Tanks
(Clause 4.5)
Tanks used for storing drinking water, non-volatile 1.5
material, low inflammable, etc, and intended for
emergency services such as fire fighting services.
Tanks of post earthquake importance
ii) All other tanks with no risk to life and with negligible 1.0
consequences to environment, society and economy
NOTE — Higher values of importance factor, I given
in IS 1893 (Part 4) may be used where appropriate.
i)
Sl
No.
(1)
Type of Ground Supported Tank
R
(2)
(3)
i) Masonry tank:
a) Masonry wall reinforced with horizontal bands 2.0
(Not permitted in zones IV and V )
b) Masonry wall reinforced with horizontal bands and 3.0
vertical bars at corners and jambs of openings
ii) RC / prestressed tank:
a) Fixed or hinged/pinned base tank (see Figs. 6a, 6b, 2.5
6c)
b) Anchored flexible base tank (see Fig. 6d)
3.0
c) Unanchored contained or uncontained tank (see 2.5
Figs. 6e, 6f)
iii) Steel tank:
a) Unanchored base
2.5
b) Anchored base
3.0
iv) Underground RC and steel tank (see Note)
4.0
NOTE For partially buried tanks, values of R can be
interpolated between ground supported and underground tanks
based on depth of embedment.
4.5.1 Design horizontal seismic coefficient, Ah shall
be calculated separately for impulsive (A h )i , and
convective (Ah)c modes.
4.5.2 Value of multiplying factor shall be taken as 1.0
for 5 percent, 1.4 for 2 percent and 1.75 for 0.5 percent
damping.
4.6 Base Shear
4.6.1 Ground Supported Tank
Base shear in impulsive mode, at the bottom of tank
wall is given by:
Vi = (Ah)i (mi + mw + mt) g
7
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
M*c = (Ah)c mc ( h*c + tb) g
and base shear in convective mode is given by:
Vc = (Ah)c mc g
where
where
Mb = mass of base slab/plate; and
tb = thickness of base slab/plate.
(Ah)i = design horizontal seismic coefficient for
impulsive mode;
(Ah)c = design horizontal seismic coefficient or
convective mode;
4.7.2 Elevated Tank
Overturning moment in impulsive mode, at the base
of the staging is given by:
mi = impulsive mass of water;
mw = mass of tank wall;
M i* = ( Ah ) i mi (hi* + hs ) + ms hcg g
mt = mass of roof slab; and
g = acceleration due to gravity.
and overturning moment in convective mode is given
by:
4.6.2 Elevated Tank
M*c = (Ah)c mc ( hcg+ hs) g
Base shear in impulsive mode, just above the base of
staging (that is, at the top of footing of staging) is given
by:
where
hs = structural height of staging, measured from
top of footing of staging to the bottom of
tank wall; and
hcg = height of centre of gravity of the empty
container of elevated tank, measured from
the top of footing.
Vi = (Ah)i (mi + ms) g
and base shear in convective mode is given by:
Vc = (Ah)c mc g
where
4.7.3 Total moment shall be obtained by combining
the moment in impulsive and convective modes
under 4.7.1 and 4.7.2 through square of sum of squares
(SRSS) and is given as follows:
ms = mass of container and one-third mass of
staging.
4.6.3 Total base shear V can be obtained by combining
the base shear in impulsive and convective mode
through square root of sum of squares (SRSS) rule and
is given as follows:
V=
Vi2 + Vc2
4.7.1 Ground Supported Tank
+ Mc2 )
M* =
(M
*2
i
+ Mc*2
and
)
4.8.1 Ground supported rectangular tanks shall be
analyzed for horizontal earthquake force acting nonconcurrently along each of the horizontal axis of the
tank for evaluating forces on tank walls.
Mi = (Ah)i (mi hi + mw hw + mt ht)g
and bending moment in convective mode is given by:
4.8.2 For elevated tanks, staging components should
be designed for the critical direction of seismic force.
Different components of staging may have different
critical directions.
Mc = (Ah)c mc hc g
where
hw = height of centre of gravity of wall mass; and
4.8.3 As an alternative to 4.8.2, staging components
can be designed for either of the following load
combination rules:
ht = height of centre of gravity of roof mass.
4.7.1.2 Overturning moment in impulsive mode to be
used for checking the tank stability at the bottom of
base slab/plate is given by:
=
2
i
4.8 Direction of Seismic Force
4.7.1.1 Bending moment in impulsive mode, at the
bottom of wall is given by:
(Ah)i [mi(h*i + tb)
(M
4.7.4 For elevated tanks, the design shall be worked
out for tank empty and tank full conditions.
4.7 Base Moment
M*i
M=
a)
+ mw(hw + tb) + mt(ht + tb)
+ mbtb/2] g
100 percent + 30 percent rule:
± ELx ± 0.3 ELy and ± 0.3 ELx ± ELy
b) SRSS Rule:
and overturning moment in convective mode is given
by:
EL2x + EL2y
8
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
φ
y
where
ELx = response quantity due to earthquake load
applied in x-direction; and
ELy = response quantity due to earthquake load
applied in y-direction.
= circumferential angle; and
= vertical distance of a point on tank wall from
the bottom of tank wall.
Coefficient of impulsive hydrodynamic pressure on
wall, Qiw (y) can also be obtained from Fig. 9a.
4.9 Hydrodynamic Pressure
Impulsive hydrodynamic pressure in vertical direction,
on base slab (y = 0) on a strip of length l’, is given by:
During lateral base excitation, tank wall is subjected
to lateral hydrodynamic pressure and tank base is
subjected to hydrodynamic pressure in vertical
direction.
x
sinh 1.732
h
Pib = 0.866( Ah )| ρgh
l′
cosh 0.866
h
4.9.1 Impulsive Hydrodynamic Pressure
The impulsive hydrodynamic pressure exerted by the
liquid on the tank wall and base is given by:
a)
x = horizontal distance of a point on base of tank
in the direction of seismic force, from the
centre of tank.
For Circular Tank (see Fig. 8a):
b) For Rectangular Tank (see Fig. 8b):
Lateral hydrodynamic impulsive pressure on the wall,
piw, is given by:
Lateral hydrodynamic impulsive pressure on wall piw ,
is given by:
piw = Qiw (y) (Ah )i ρ g h cos φ
piw = Qiw (y) (Ah )i ρ g h
D
2
Qiw (y) = 0.866 1 − ( y / h ) tanh 0.866
h
where
ρ
where
Qiw (y) is same as that for a circular tank and
can be read from Fig. 9a, with h/L being used
in place of h/D.
= mass density of liquid;
FIG . 8 GEOMETRY
OF
(a) CIRCULAR T ANK AND (b) RECTANGULAR T ANK
9
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
4.9.3 In circular tanks, hydrodynamic pressure due to
horizontal excitation varies around the circumference
of the tank. However, for convenience in stress analysis
of the tank wall, the hydrodynamic pressure on the
tank wall may be approximated by an outward pressure
distribution of intensity equal to that of the maximum
hydrodynamic pressure (see Fig. 12a).
Impulsive hydrodynamic pressure in vertical direction,
on the base slab (y = 0), is given by:
Pib = Qib (x) (Ah)i ρ g h
x
sinh 1.732
h
Qib (x) =
L
cosh 0.866
h
4.9.4 Hydrodynamic pressure due to horizontal
excitation has curvilinear variation along wall height.
However, in the absence of more exact analysis, an
equivalent linear pressure distribution may be assumed
so as to give the same base shear and bending moment
at the bottom of tank wall (see Figs. 12b and 12c). The
following expressions shall be used to linearise the
pressure distribution:
The value of coefficient of impulsive hydrodynamic
pressure on base Qib (×), can also be read from Fig. 9b.
4.9.2 Convective Hydrodynamic Pressure
The convective pressure exerted by the oscillating
liquid on the tank wall and base shall be calculated as
follows:
a)
Circular Tank (see Fig. 8a)
For circular tanks : qi =
Lateral convective pressure on the wall pcw , is given
by:
For rectangular tanks :
1
Pcw = Qcw (y) (Ah)c ρ g h D 1 − cos2 φ cos φ
3
qi =
y
cosh 3.674
D
Qcw(y) = 0.562 5
h
cosh 3.674
D
The value of Qcw(y) can also be read from Fig. 10a.
( Ah )i mi
2B
( Ah )i mi
πD 2
g and qc =
g and qc =
( Ah )c mc
2B
( Ah )c mc
πD 2
g
g
ai =
qi
q
4 h − 6 hi ), bi = 2i ( 6 hi − 2 h ) and
2 (
h
h
ac =
qc
q
4h − 6hc ), bc = c2 (6hc − 2h )
2 (
h
h
4.9.5 Pressure Due to Wall Inertia
Convective pressure in vertical direction, on the base
slab (y = 0) is given by:
Pressure on tank wall due to its inertia is given by:
Pww = (Ah)i t ρm g
where
Pcb = Qcb(x) (Ah)c ρ g D
where
ρm = mass density of tank wall; and
t = wall thickness.
x 4 x 3
h
Qcb(x) = 1.125 − sech 0.367 4
D 3D
D
The value of Qcb(x) may also be read from Fig. 10b.
4.10 Effect of Vertical Ground Acceleration
Due to vertical ground acceleration, effective weight
of liquid increases, this induces additional pressure on
tank wall, whose distribution is similar to that of
hydrostatic pressure.
b) Rectangular Tank (see Fig. 8b):
The hydrodynamic pressure on the wall pcw, is given
by:
pcw = Qcw (y) (Ah)c ρ g L
4.10.1 Hydrodynamic pressure on tank wall due to
vertical ground acceleration may be taken as:
Qcw(y) = 0.4165 [cosh (3.162 y/L)/cosh (3.162 h/L)]
Pv = (Av) ρ g h (1 – y/h)
The value of Qcw(y) can also be obtained from Fig. 11a.
Av =
The pressure on the base slab (y = 0 ) is given by:
Pcb = Qcb(x) (Ah)c ρ g L
2 Z I Sa
× ×
3 2 R g
where
x 4 x 3
h
Qcb(x) = 1.125 − sech 3 .162
L 3L
L
where
The value of Qcb(x) can also be obtained from Fig. 11b.
y = vertical distance of point under
consideration from bottom of tank wall, and
(Sa/g) = Average response acceleration coefficient
given by Fig. 2 and Table 3 of IS 1893 (Part
1) and subject to 4.5.2 and 4.5.3.
10
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
(a) On Wall of Circular and Rectangular Tank
12
I
I
0.8
A
'/
"
I
I
0.4
I""
Qib
t-- r--0.4
--
-0.2
r"'"
~
~
t::":
2.0
~ ~ ____
V
f""/
1.5
1.0 AI V
0.5 1/
h/L =0.25
-
1-"-
r- ....,.
~
........
~
0
~
xlL
~
~
~
~
......... :.- fo"""..,.::: ;..-
F""""
-- -
..-
0.4- -
0.2
-0.4
I
- 0.8
I
I
- 1.2
(b) On Base of Rectangular Tank
FIG. 9 I MPULSIVE PRESSURE COEFFICIENT (a) ON WALL (C) (b)
11
'/
/ ....... ~
ON
BASE
0.25
0.5
1.0
1.5
2.0
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
1
I
I
--r---
I
I ___ L
I __ _
_L
0.8
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
---1----+----
-
0.6
..c
>-
I
-+---I----f---__ ..JI ____ II- ___ LI __ _
0.4
I
0.2
0
0
0.1
0.2
0.4
0.3
0.6
0.5
Qcw
(a) On Wall
-__'T+~_:=.-Li
ID
-""] x
I
-;,I+~r1
-4~+.JL
I
O. 2 -}f~
I
I
I
I
0.4 -+--i
I
I
I
r--t--r--r--j--i--r--l
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
__ +-~
-j--t--t--i--l---i--t--t--1--l
-i--l---i--f---t--i--l---r--}--i
-1r~ti,f
-1~f+it
-,'r~14I
-'r+;I~
_~
__ L __
~
__ J __ ..J ___I- __
(b) On Base
F IG. 10 C ONVECTIVE PRESSURE COEFFICIENT FOR CIRCULAR TANK
(a) ON WALL (b) ON BASE
12
I
-1--j---r--t--t--j--l---j--i--1
L __ L __ __
~
~
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
----r----T----l----l----l-----r----r----r----r ----
1
1
1
1
1
1
1
----}----f----{----i---1
1
1
1
12
1
0.8 ----t---- .
I
1
1
~_
I 1.0
I
I
---t-- 1----1----1----
0.4
-~
1
1
-T~;
I
I
I
I
I
I0.5
1
I
1
1
1
1
1
1
1
1
1
1
I
1
1
1
-;r~
--- ----f----{---1 -~r
1
1
-- t-~
I
----r-----r---
I
-1ir~
I
1
h/L=0.2
I1
1
-~T;
1
I
1
1
~
1
I
1
1-~
1
1
1
1
----i-----I
I ____ I____ JI
_~
1
1
-1
-T--
11.___ 1
____ L
0.6
1
1
I
I
----t----t----1
I
I
I
I
-t----t----1----1
I
I
I
I
1
1
1
1
1
1
1
1
----}----f----{----i
1
1
1
1
-~
IfI -t~
- -t----t----I-- -1----1----11----1 --- r----t----t----I----1
0.2
Ou-~
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
o
0.2
0.1
1
0.3
Qcw
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0.5
0.4
0.6
(a) On Wall
~-T',_r0.3
1
~-}+t
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
~-+;rT
l-J~+r1
r-t+~_I0.2
1
1r-'J~t
1
1
r--'--,---r--r--t--i--,---r--r--
~-4t+{
~-{i+}
l-i~tjJL1
0.1
1
l __ J __ ~-+J
1
1
1
1
1
1
1
1
l-1_0.4Lj2~
'7"!~-r,
1
1
1
1
1
-; xlL
-4~LjJt
-JL~Il
-rti~1
-i~tIlr1
1
1
02
. -r'T~
1"'-+t;~
1
1
1
1
1
'I
1
1
1
1
1
1
04
1
1
.1 -T--'
1
. .1
1
1
1
-~ft+i
--I--,---r--r--t---I--'---r--t--i
-~tl4L
1
-'r~1
1
1
1
1
1
1
1
1
1
-4~LljJ JL __ L__ l __ l __ J __ JL __ L__ l __ l __ J
Q cb
(b) On Base
FIG. 11 C ONVECTIVE PRESSURE COEFFICIENT FOR R ECTANGULAR T ANK
(a) ON WALL (b) ON BASE
13
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
-
Pmax
Simplified Distribution
Actual Distribution
(a) Simplified Pressure Distribution in Circumferential Direction on Tank Wall
=
Actual Impulsive
Pressure Distribution
Equivalent Pressure
Distribution
+
Uniform
Linear
(b) Equivalent Linear Distribution Along Wall Height for Impulsive Pressure
=
Actual Impulsive
Pressure Distribution
Equivalent Pressure
Distribution
+
Uniform
Linear
(c) Equivalent Linear Distribution Along Wall Height for Convective Pressure
F IG. 12 HYDRODYNAMIC PRESSURE DISTRIBUTION
(a) ON WALL (b) ON BASE
14
FOR
WALL ANALYSIS
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
In case of rectangular tank, the same expression may
be used with L instead of D.
In absence of more refined analysis, time period of
vertical mode of vibration for all types of tank may be
taken as 0.3 s.
5 SEISMIC DESIGN OF LIQUID RETAINING
TANKS
4.10.2 The maximum value of hydrodynamic pressure
should be obtained by combining pressure due to
horizontal and vertical excitation through square root
of sum of squares (SRSS) rule, which can be given as:
P=
( Piw + Pww )
2
5.1 Two Mass Idealization
The rational method of analysis using the two masses
– impulsive and convective – as presented in 4.1 to 4.12
may be used for determining the seismic design forces
on ground supported as well as elevated water tanks
of any capacity and material of construction namely,
reinforced concrete or steel.
+ Pcw2 + Pv2
4.11 Sloshing Wave Height
Maximum sloshing wave height is given by:
a)
For circular tank:
dmax = (Ah)c R
5.2 One Mass Approximation
D
2
In the light of the on going practice for construction of
large number of water tanks, it is considered expedient
to permit the option of one mass idealization, in certain
cases, as stated here below, in which the whole water
mass is taken as if in impulsive mode.
b) For rectangular tank:
dmax = (Ah)c R
L
2
5.2.1 Ground supported or elevated liquid retaining
RC structure of up to and including 1 000 kl capacity,
wall of the container if in concrete, which can be
regarded as rigid.
where
(Ah)c = design horizontal seismic coefficient
corresponding to convective time period.
Circular ground supported tanks shall be anchored to
their foundation (see Fig. 13) when
5.2.2 Wall in steel may not be regarded as rigid, hence
for design of steel tanks by one mass model, the
capacity should not exceed 200 kl and h/D or h/L
should be 0.4 or higher.
h
1
>
D ( Ah )i
5.2.3 For one mass model, water mass in convective
mode shall not be considered. Total water mass shall
be assumed in impulsive mode and the impulsive force
4.12 Anchorage Requirement
F IG.13 INITIATION
OF
15
ROCKING
OF
TANK
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
∆ Effect
6.5 P-∆
shall be assumed to act at centre of gravity of the whole
water mass.
All staging of columns and braces (or beams) for
elevated tanks shall be designed for P-∆ effect.
5.2.4 The design shall be worked out both when the
tank is full and when empty. When empty, the weight
W used in the design shall consist of the dead load of
the tank and one-third the weight of the staging lumped
at the centre of gravity of the tank. When full, the
weight of the fluid contents is to be added to the weight
under empty conditions.
7 AESTHETICS
Elevated water tanks are prominently in public view
and visible from near as well as long distances. They
often become landmarks on the landscape. It is
therefore important that the shape and form of the
container and the supporting structure must receive due
attention from the point of aesthetics. Innovations in
the shape and form should be encouraged when they
improve the ambience and enhance the quality of the
environment.
6 MISCELLANEOUS
6.1 Piping
Piping system connected to tanks should be given
consideration of potential vibration and movement at
the pipe joints during earthquakes, and sufficient
flexibility should be introduced by proper detailing of
pipe joints to avoid de-function. Piping system and its
connection to the tank should be designed to comply
with the assumptions made and the likely performance;
merely neglecting the weight of piping system may
not be adequate in all cases.
Where unusual shapes and forms for supporting
structures are used, the designer may use some
discretion in choosing the value of response reduction
factor R consistent with expected seismic performances
and ductility. It will be incumbent on the designer,
however, to justify the choice of R value vis-à-vis the
seismic safety.
8 QUALITY CONTROL IN REINFORCED
CONCRETE TANKS
The piping system shall be designed so as not to impart
significant mechanical loading on tank. Local loads at
pipe connections can be considered in the design of
the tank. Mechanical devices, which add flexibility to
piping such as bellows, expansion joints and other
special couplings, may be used in the connections.
Quality control in design and constructions are
particularly important for elevated tanks in view of
several collapses of water tanks during testing. It is
necessary that quality of materials and construction
tolerances are strictly adhered to during construction
phase. Some construction tolerances and detailing are
listed below. The information given is not exhaustive
and designers and construction engineers are expected
to have competence to take adequate measures to
ensure required structural performance.
6.2 Buckling of Shell
Ground supported tanks (particularly, steel tanks) shall
be checked for failure against buckling of tank walls
under vertical board. Similarly, safety of shaft type of
staging of elevated tanks against buckling shall be
ensured.
NOTE — The design/construction details for reinforced
concrete tanks should strictly follow IS 456, IS 3370 (Parts 1 to
4), and IS 11682. The recommendations are made here to ensure
safety under normal as well as service loads.
6.3 Buried Tanks
Dynamic earth pressure shall be taken into account
while computing the base shear of a partially or fully
buried tank. Earth pressure shall also be considered in
the design of walls. In buried tanks, dynamic earth
pressure shall not be relied upon to reduce dynamic
effects due to liquid.
8.1 RC Frame Staging
8.1.1 Columns
a)
Minimum size of column should be 400 mm
(diameter and/or side of rectangular column)
except for tanks having 200 m 3 or less
capacity, columns of 300 mm size may be
used.
b) Clear height of column between braces should
not be more than ten times the size of column.
c) Reinforcement detailing including overlaps
in longitudinal bars should follow as shown
in IS 13920.
d) During construction and casting of columns,
some eccentricity in the verticality of column
6.4 Shear Transfer
The lateral earthquake force generates shear between
wall and base slab and between roof and wall. Wallto-base slab, wall-to-roof slab and wall-to-wall joints
shall be suitably designed to transfer shear forces.
Similarly in elevated tanks, connection between
container and staging should be suitably designed to
transfer the shear force.
16
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
may develop. Eccentricity up to 20 mm may
be allowed in column between two brace
levels. Additional moment due to this
eccentricity should be considered in the
analysis.
b) Circumferential reinforcement shall not be
less than 0.2 percent of concrete area in
vertical section. Since vertical reinforcement
is provided in two layers, circumferential
reinforcement shall be divided equally in two
layers. The spacing of circumferential bars in
each layer shall not be more than 300 mm or
shell thickness, whichever is less.
Circumferential reinforcement shall be placed
nearer the faces of shell.
c) At horizontal construction joints in shaft, one
additional layer of vertical bars projecting on
either side of the joint with Ld anchorage
length shall be provided. Continuity of
concreting at construction joint shall be done
with application of neat cement slurry.
d) Openings in shaft % Detailing of shaft at the
opening shall take into consideration effective
continuity of reinforcement at all sides. More
information on detailing near openings is
given in IS 11682. At vertical edges of door
opening stiffeners may be required.
e) In the tank ring beams, reinforcement bars in
direct tension shall have lap length twice the
development length in tension. The spliced
length of the ring beams in tension shall be
enclosed in spirals made of bars not less than
6 mm dia with pitch not more than 100 mm,
or enclosed in stirrups of 8 mm dia with pitch
not more than 150 mm, the stirrups shall have
135° hooks bent into the core concrete with
minimum 50 mm extension. If diameter is
more than 22 mm, couplers may be used.
8.2.3 Construction Control
8.1.2 Braces
a)
Minimum width of unflanged brace shall not
be less than 1/30th of its clear length between
junctions.
b) In Zones IV and V, use of diagonal bracings
in vertical plane shall be encouraged.
Information on detailing of RC and steel
diagonal bracings is given in IS 11682.
8.1.3 Foundation
For isolated footings, tie beam near top of footing shall
be provided as per IS 4326.
8.2. RC Shaft Staging
8.2.1
a)
Thickness of Shaft
Minimum thickness of shaft shall be suitable
for constructability which depends on height
of formwork for one lift of concrete.
Minimum thickness of shaft shall be 150 mm
for shaft diameter up to 4 m. For larger
diameter shafts, following equations shall be
used to arrive at minimum thickness:
1) For shafts with diameter less than 8 m,
tmin = 150 + (D – 4 000)/80 mm
2) For shafts with diameter equal to or
greater than 8 m,
tmin = 200 + (D – 8 000)/120 mm
where
D = diameter of shaft, in mm.
b) Additional thickening of shaft and extra
vertical and circumferential reinforcement
shall be provided at top and bottom level of
shaft (that is, at junctions with foundation and
with container). This is required to account
for secondary moments and eccentricities.
Additional vertical and circumferential
reinforcement shall be same as that required
as per design calculations.
a) Vertical Alignment — The centre point of
shaft shall not vary from its vertical axis by
more than 0.2 percent of shaft height.
b) Over any height of 1.6 m, wall of shaft shall
not be out of plumb by more than 10 mm.
c) Shaft diameter — The measured centerline
diameter of shaft at any section shall not vary
from the specified diameter by more than
20 mm plus 0.1 percent of the specified
theoretical diameter.
d) Shaft thickness — The measured wall
thickness shall not vary from the specified
wall thickness by more than –5 mm or
+10 mm.
8.2.4 Mat Foundation
8.2.2 Reinforcement in Shaft
a)
Minimum vertical reinforcement shall be 0.25
percent of concrete area. The reinforcement
shall be provided in two layers. The minimum
diameter of vertical bars shall be 10 mm.
Maximum centre-to-centre distance between
vertical reinforcement in each layer shall not
exceed 300 mm.
In case of mat foundations, lifting of mat on tension
side can be allowed at soil contact. The maximum
eccentricity at base may be permitted up to 0.25 times
the base diameter provided the maximum compression
remains within permissible limits.
17
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
IS 1893 (Part 2) : 2014
8.3 RC Tank and Shaft
1.4 times development length in tension; the
laps shall be staggered so that not more than
one-third the bars shall be spliced at any one
section.
a)
In the tank ring beams, reinforcement bars in
direct tension shall have lap length twice the
development length in tension. The spliced
length of the ring beams in tension shall be
enclosed in spirals made of bars not less than
6 mm diameter with pitch not more than 100
mm, or enclosed in stirrups of 8 mm diameter
with pitch not more than 150 mm, the stirrups
shall have 135° hooks bent into the core
concrete with minimum 50 mm extension.
b) In tank wall or shaft, not more than one-third
of vertical bars shall be spliced at any section.
For circumferential bars, lap length shall be
8.4 Strong Column – Weak Beam
For column and beam type of staging of elevated tank,
sum of moment of resistance of column at a junction
should not be less than 1.1 times the sum of moment
of resistance of beams in any one plane taken at a time.
This check is to be applied by limit state method.
8.5 Staircase Design
Provisions of IS 11682 shall be followed for the
staircase design.
18
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
(Continued from second cover)
c)
d)
e)
f)
g)
h)
i)
10.
Housner, G. W., 1963a, ‘Dynamic analysis of fluids in containers subjected to acceleration’, Nuclear
Reactors and Earthquakes, Report No. TID 7024, U. S. Atomic Energy Commission, Washington D.C.
Housner, G. W., 1963b, ‘The dynamic behavior of water tanks’, Bulletin of Seismological Society of
America, Vol. 53, No. 2, 381-387.
Jain, S. K. and Medhekar, M. S., 1993, ‘Proposed provisions for aseismic design of liquid storage tanks:
Part I – Codal provisions’, Journal of Structural Engineering, Vol. 20, No. 3, 119-128.
Jain, S. K. and Medhekar, M. S., 1994, ‘Proposed provisions for a seismic design of liquid storage
tanks: Part II – Commentary and examples’, Journal of Structural Engineering, Vol. 20, No. 4, 167-175.
Jaiswal, O. R. Rai, D. C. and Jain, S.K., 2004a, ‘Codal provisions on design seismic forces for liquid
storage tanks: a review’, Report No. IITK-GSDMA-EQ-01- V1.0, Indian Institute of Technology, Kanpur.
Jaiswal, O. R., Rai, D. C. and Jain, S.K., 2004b, ‘Codal provisions on seismic analysis of liquid storage
tanks: a review’ Report No. IITK-GSDMA-EQ-04-V1.0, Indian Institute of Technology, Kanpur.
Priestley, M. J. N., et al., 1986, ‘Seismic design of storage tanks’, Recommendations of a study group of
the New Zealand National Society for Earthquake Engineering.
Veletsos, A. S., 1984, ‘Seismic response and design of liquid storage tanks’, Standards for the seismic
design of oil and gas pipeline systems, Technical Council on Lifeline Earthquake Engineering, ASCE,
N.Y., 255-370, 443-461.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value
observed or calculated expressing the result of a test or analysis, shall be round off in the accordance with IS 2 :
1960 Rules for rounding off numerical values (revised)’. The number of significant places retained in the rounded
value should be the same as that of the specified value in this Standard.
Free Standard provided by BIS via BSB Edge Private Limited to VNIT Nagpur - Nagpur(ar4ind@gmail.com)
117.205.13.254 [for non-commercial use only].
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Review of Indian Standards
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards : Monthly Additions’.
This Indian Standard has been developed from Doc No.: CED 39 (7231).
Amendments Issued Since Publication
Amend No.
Date of Issue
Text Affected
BUREAU OF INDIAN STANDARDS
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones : 2323 0131, 2323 3375, 2323 9402
Website: www.bis.org.in
Regional Offices:
Central
: Manak Bhavan, 9 Bahadur Shah Zafar Marg
NEW DELHI 110002
Eastern
: 1/14 C.I.T. Scheme VII M, V. I. P. Road, Kankurgachi
KOLKATA 700054
Telephones
{
2323 7617
2323 3841
{
{
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113
Western
Branches:
: Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093
2337 8499, 2337 8561
2337 8626, 2337 9120
260 3843
260 9285
{
{
2254 1216, 2254 1442
2254 2519, 2254 2315
2832 9295, 2832 7858
2832 7891, 2832 7892
AHMEDABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE. DEHRADUN.
FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KOCHI. LUCKNOW.
NAGPUR. PARWANOO. PATNA. PUNE. RAJKOT. VISAKHAPATNAM.
Published by BIS, New Delhi